MINIMUM ACCEPTABLE SIZE FOR FRAMEWORK AND BRACING
Duct Diameter Ø
Plate thickness
(in)
(in)
5 to 24
3/16
26 to 36
1/4
TABLE 8 - Minimum Acceptable Size for Framework and Bracing for Model CAX1-(BC)
VENTILATED ANCHOR PLATE WITH LENGTH (APVL)
The APLV has a free anchor plate integrated on a length. It cannot be
used has a fixed support for vertical or horizontal installation. Refer to the
Ventilated Anchor Plate (APV ) for all the warnings / details, except for the
installation. See Figure 33 for an APLV
Figure 33: Ventilated Anchor Plate with Length (APVL)
It is assembled exactly like flange-to-flange assembly with the V-Band
(BSI) (See JOINT ASSEMBLY Section).
The part doesn't have any outer wall, but Outer Band (BSE) is provided to
secure the insulation on the part. See Figure 34, 35 & 36 for the three steps
to install the CAX1-(BC).
18
Bracing
Framework
(in)
(in)
2 x 2 x 3/16
2 x 2 x 1/4
Channel or Equivalent
Channel or Equivalent
3 x 3 x 1/4
3 x 3 x 1/4
Channel or Equivalent
Channel or Equivalent
Figure 34: Step 1 of installation of APVL
Figure 35: Step 2 of installation of APVL
For vertical installation, small brackets must be on the bottom side when
the bottom Outer Band will be installed, these Brackets will hold the
Casing Band (BSE) right to the support plates. See Figure 36.