Page 1
High-torque actuator GHT336.1A.. GHT336.1A/400 GHT336.1A/90 GHT336.1A/35 GHT336.1A/600 GHT336.1A/150 High-torque actuator for large area damper and combination damper ● Operating voltage AC 220 V ● On/off control and signal feedback ● Nominal angle of rotation 0…90° ● Manual operation with handwheel ●...
Page 2
The actuators have a reversible asynchronous motor and gear train. For GHT336.1A/35, the spring is fitted with a handwheel shaft, and the handwheel is engaged when pushed in. For others, the worm shaft is fitted with a direct-acting handwheel. Manual operation can be performed at any time using manual/electric auto changeover.
Page 3
Environmental compatibility Product environmental declaration A5W90001904 Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download Notes Security CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage ●...
4. Factory setting of the position limit is 0...90°. Do not adjust the limit during commissioning to ensure normal operation. Operation Manual operation mode GHT336.1A/35 Handwheel is engaged by pushing the handwheel in. Manual operation can be performed only when the power supply is switched off. GHT336.1A/90 The handwheel is always engaged.
Dispose of the device through channels provided for this purpose. ● Comply with all local and currently applicable laws and regulations. Warranty The actuator can only be used within the permissible range of Technical data. Otherwise, Siemens rejects any and all warranties. Siemens A6V10984826_a Building Technologies 2017-01-20...
Die-cast aluminum alloy Cover Die-cast aluminum alloy GHT336.1A/35 GHT336.1A/90 GHT336.1A/150 GHT336.1A/400 GHT336.1A/600 Max. external supply line fusing * The documents can be downloaded from: http://siemens.com/bt/download。 General ambient conditions Operation Transportation Storage EN 60721-3-4 EN 6071-3-2 EN 60721-3-1 Temperature -25…70 ℃...
3 (Y1) Control signal (open) 4 (Y2) Control signal (closed) Auxiliary switch, closed position Auxiliary switch, open position * If Q3 and Q4 are closed at the same time, the actuator will not working properly. Siemens A6V10984826_a Building Technologies 2017-01-20...
Page 8
Dimensions Dimensions in mm Product no. Weight EN ISO [kg] 5211 GHT336.1A/35 11×11 4-M8 Product no. Weight EN ISO [kg] 5211 GHT336.1A/90 14×14 35 4-M8 GHT336.1A/150 17×17 35 4-M8 GHT336.1A/400 22×22 55 4-M10 GHT336.1A/600 27×27 55 4-M12 Revision numbers Type Valid from rev.