nVent ERICO System 3000
Installation, Operation and Maintenance Manual
nVent.com/ERICO | 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ERICO System 3000 and is the answer not in the manual?

Questions and answers

Summary of Contents for nvent ERICO System 3000

  • Page 1 ERICO System 3000 Installation, Operation and Maintenance Manual nVent.com/ERICO | 1...
  • Page 2 Purchased From: __________________________________________________________________________________ Signature of Installation Contractor: _______________________________________________________________ ©2020 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.
  • Page 3: Table Of Contents

    Table of Contents nVent ERICO System 3000 ................5 Installation, Operation and Maintenance Manual ................5 Warning and Safety Instructions ............... 6 Pre-Installation Requirements ................7 Checking Lightning Protection Components Prior to Installation ...........7 nVent ERICO System 3000 Installation.............. 8 Grounding Systems..........................
  • Page 4 Installation Methods for Ericore Exceeding 70 m ................37 Parallel Splicing ..........................37 Series Splicing ..........................39 Lower Termination of Ericore Downconductor ..........41 Upper Termination of Ericore Downconductor ..........42 Operation and Maintenance ................43 Maintenance Record ..........................50 Specifications ....................51 Glossary ......................54 4 | nVent.com/ERICO...
  • Page 5: Nvent Erico System 3000

    As a system, the combination of the products and the placement method used in the design and installation of the nVent ERICO System 3000 does not comply with any particular standard. However, the actual components of the System 3000 are in full compliance with certain standards (in terms of lightning current handling ability, material of construction, etc).
  • Page 6: Warning And Safety Instructions

    Warning and Safety Instructions WARNING: 1. nVent ERICO products shall be installed and used only as indicated in nVent ERICO product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your nVent ERICO customer service representative.
  • Page 7: Pre-Installation Requirements

    • That there is no obvious damage to It assumes that the system to be installed the cable. has been designed by an authorized nVent • Make sure that the end of cable is ERICO representative. The system design properly sealed to prevent moisture will include: migragting into cable strands.
  • Page 8: Nvent Erico System 3000 Installation

    3. Termination of the downconductor to the grounding system 4. Construction of the mast, insertion of the upper termination into the FRP mast and connection to the nVent ERICO Dynasphere air terminal 5. Termination of bonding cable from upper termination to structure is required to be grounded (refer to Downconductors section of the manual on page 13) 6.
  • Page 9 @ 600 mm (24 in.) depth or greater if required, Ground Enhancement Material to ensure that it is below the frost line. (GEM25A) Figure 1: Radial ground nVent ERICO ground rods are connected Conductive to the grounding conductors using Copper ground tape grid Saddles Cadweld exothermic or mechanical 5m x 5m (17 x 17 ft.)
  • Page 10 Figure 4: Precautions required for Inspection Well excavation and lower termination corrosion protection It is advised that an Inspection Well is This provides a convenient access point for installed where the end of the downconductor disconnection and future testing. terminates to the grounding system. 10 | nVent.com/ERICO...
  • Page 11: Ground Resistance Lowering Compounds

    When driving ground rods it is advisable GEM25A can be used to increase the to use nVent ERICO ground rod drivers or total surface area of grounding drive sleeves to prevent mushrooming on conductors, thereby reducing the ground the top of the rod. When coupling rods, use resistance / impedance.
  • Page 12: Conductor To Grounding System Connection

    System Connection The labelling of Inspection Wells or grounding systems to local requirements is the When determining the length of nVent responsibility of the customer / installer. ERICO Ericore conductor required in a particular situation it is prudent to make the...
  • Page 13: Ericore Downconductor

    Depending on site requirements, the downconductor(s) may have their upper terminations completed at a pre-specified end of the cable by nVent ERICO before shipment. These terminations will be protected by a short length of flexible PVC tube. It is VERY IMPORTANT that when removing these tubes, they are not removed with a knife or cut in any way as this will damage the outer layer of the termination.
  • Page 14 Downconductor un-terminated end lowered to the ground Downconductor preterminated end on the outside of drum Figure 6: Cable pre-termination and drum locations INCORRECT CORRECT Figure 7: Incorrect and correct cable hoisting methods 14 | nVent.com/ERICO...
  • Page 15: Penetrations

    • The Ericore cable must be installed in a downward fashion. Radius < 500 mm (20 in.) < 2000 mm (80 in.) INCORRECT CORRECT INCORRECT Figure 8: Correct & incorrect cable routing methods nVent.com/ERICO | 15...
  • Page 16 ERICO Dynasphere terminal in the top of the FRP mast. Radius < 500 mm (20 in.) INCORRECT <2000 mm...
  • Page 17: Securing The Downconductor

    FRP mast against the terminal for at mechanically secure and electrically bond least one turn. the nVent ERICO Ericore to the structure, while minimizing stress points on the cable. If the downconductor is damaged during installation, it is no longer Only use nVent ERICO provided usable and must be replaced.
  • Page 18 • Use of exothermic fastening methods on nVent ERICO brand of saddles is NOT recommended. • Use of nVent CADDY ERISTRUT (or other similar strut system) is recommended where suitable (see Figure 11). 18 | nVent.com/ERICO...
  • Page 19: Labelling

    This must be connected to If more labels are required, contact your a conductive structural point to relieve the nearest nVent ERICO Distributor. electrical stresses on the downconductor and masonry surfaces. The use of the Structure Bonding Braid is NOT optional, and MUST always be used.
  • Page 20 MUST be secured with Any metallic surfaces that the nVent ERICO brand of saddles to the mast at downconductor may be secured to, if 1 m (40 in.) intervals (max.). The mast in turn possible, should be electrically connected to must be electrically bonded to the nearest the structural steel work.
  • Page 21 Figure 14: Connection of bonding cable to structural steel work To upper termination kit bonding braid or mast base Structure bonding Concrete Panel cable Cadweld, bolted, or other suitable electrically bonding method Reinforcing Steel Figure 15: Connection of bonding cable to concrete reinforcing nVent.com/ERICO | 21...
  • Page 22: Terminals And Masts

    The nVent ERICO Dynasphere is the air terminal of the nVent ERICO System 3000. Suitable for use in: • General purpose applications Figure 16 – nVent ERICO Dynasphere with two spare • Temperatures of up to 100°C (212°F) finial tips. • Corrosive environments (salt or acid atmosphere) Warning –...
  • Page 23: Mast Wind Loading

    This isolated from volatile areas by installing information helps the structural engineer the nVent ERICO System 3000 at least to select the proper hardware to support 5 m (17 ft.) away from those areas. the installation.
  • Page 24: Mast Couplings And Guying Points

    ERICO Dynasphere air terminal and anchored to a concrete roof, then they need the top of the mast, the FRP mast must...
  • Page 25: Guying

    Comms Tower Figure 19: Guyed and cantilevered mast examples Guying nVent ERICO has standard 4 m (13 ½ ft.) and 7 m (24 ½ ft.) guying kits. If the guying of a fiberglass mast is required, then the appropriate guying kit should be selected to suit the application.
  • Page 26 • Grips are correctly orientated - grip base anchors or similar should be used. (saddle) on the ‘live’ side of the guy and • nVent ERICO can provide wind load ratings ‘U-bolt’ over the ‘dead’ side or tail of per mast type to the structural engineer.
  • Page 27: Raising Of Mast

    • The downconductor has been If the mast is to be raised by hand, correctly terminated and the structure ensure that it can be safely and easily bonding cable has been attached to managed manually. the termination. nVent.com/ERICO | 27...
  • Page 28 Ensure the base will bonding braid Secure guying not slip during the lift Protect the Ericore from abrasion during the lift Removable gin pole and associated rigging Figure 22: Removable gin pole to assist raising the mast 28 | nVent.com/ERICO...
  • Page 29 • Any extra rigging that is required for the • When slinging the mast, ensure that the lift only, can be removed after the mast is slings or ropes can not foul the nVent in place. ERICO Dynasphere terminal. • The mast can be easily and safely •...
  • Page 30: Lightning Event Counter

    Refer to the instructions supplied with the strikes that the nVent ERICO System 3000 LECV when installing the unit. has intercepted. The nVent ERICO LECV is When mounting the LECV, ensure that: the latest event counter model and features •...
  • Page 31: Special Applications

    • nVent ERICO manufactures components design and report must be completed by a allowing connection of the conventional member of the nVent ERICO Applications conductor with the Dynasphere terminal. Engineering team and must be presented • A FRP mast shall not be used with to the customer in its entirety.
  • Page 32: Using The Mast As A Downconductor

    Dynasphere to the conductors. nVent ERICO does not offer different mast sections. products that connect the Dynasphere • nVent ERICO also allows the use of a to composite conductors, and is not water pipe with UNC or British threads, presently recommended.
  • Page 33 Engineers and all components are single conductor may be used manufactured and supplied by nVent • nVent ERICO offers a custom design of ERICO. The system must comply to heavy steel, freestanding masts made to the latest revision of the nVent ERICO...
  • Page 34: Protection Of Tall Structures

    In LP protection of substations, all terminal placement methods mentioned in IEEE 998 are applicable including the Collection Volume method. nVent ERICO System 3000 can be mounted directly on the structure, or on freestanding mast that would be supplied by the customer.
  • Page 35: Practical Examples For Long Lengths Of Ericore Downconductor

    (typically greater examples give typical guidance. than 140 m (460 ft.) in height) need to use the series connection method. The nVent TELECOM TOWERS ERICO application engineering group will Most towers would be less than 70 m determine the allowable lengths of the (230 ft.), or so, in height so that a single...
  • Page 36 ® Proposed ERITECH ERICORE length Determine the thunderday level at the proposed installation site. A single length of nVent ERICO Additional measures ae required. Ericore is acceptable. Read on further in this section. No additional action is required. Figure 26: Determination of maximum single Ericore length...
  • Page 37: Ericore Maximum Lengths

    ERICORE MAXIMUM LENGTHS 2. Series splicing - Connect two or more Ericore cables in series between the air The construction of the nVent ERICO terminal and the first grounding point. Ericore cable has been carefully designed Terminate each section to a busbar that...
  • Page 38 ERICO Ericore cable they split to the oposite side of the structure is fitted with an nVent ERICO Ericore (see Figure 27). The usual conductive saddle lower termination kit, and attached to the spacing applies.
  • Page 39: Series Splicing

    Very tall buildings will have a number of connection points depending on their height. Details of where to provide the joint will be provided by the nVent ERICO application engineers, after consideration of the building details. nVent.com/ERICO | 39...
  • Page 40 Rod Clamp Compression Copper Ground Rod Busbar To Grounding System Figure 31: Termination to busbar and ground rod Inspection Well Downconductor lower termination bound in waterproofing mastic LECV Ground Rod Figure 32: Completed termination for downconductor 40 | nVent.com/ERICO...
  • Page 41: Lower Termination Of Ericore Downconductor

    If the instructions are not followed correctly, or if any of the insulation layers or the copper foil are incorrectly cut, then the integrity of the whole lightning protection is affected. nVent.com/ERICO | 41...
  • Page 42: Upper Termination Of Ericore Downconductor

    If the instructions are not followed correctly, or if any of the insulation layers or the copper foil are incorrectly cut, then the integrity of the whole lightning protection is affected. 42 | nVent.com/ERICO...
  • Page 43: Operation And Maintenance

    Operation and Maintenance The nVent ERICO System 3000 lightning 3. Inspect the finial tip on top of the nVent protection system requires no user ERICO Dynasphere to ensure that it is not operation and is completely automatic excessively burnt, deformed or missing. A in operation.
  • Page 44 M.Report any problems, defects of F. Reconnect the structure ground bonding inconsistencies to your nearest nVent cable to the lightning protection ground ERICO Distributor. system, then measure & record in column 3 of ground resistance readings.
  • Page 45 (12 AWG) Remove the waterproofing Wire Temporarily Disconnected mastic from the lower termination to expose the connection. Ground Resistance Meter Structure Bonding Cable (Disconnected from L P Ground) LP Grounding System Figure 37: Grounding and downconductor continuity testing nVent.com/ERICO | 45...
  • Page 46 Measure the ground resistance of Structure Bonding Cable the lightning protection grounding (Disconnected from L P Ground) system and record in column 1 of LP Grounding System ground resistance readings. Figure 39: Grounding and downconductor continuity testing 46 | nVent.com/ERICO...
  • Page 47 (This should be greater than 1,000 ohms). Ground Resistance Meter Structure Bonding Cable (Disconnected from L P Ground) LP Grounding System Figure 41: Grounding and downconductor continuity testing nVent.com/ERICO | 47...
  • Page 48 (12 AWG) Wire Temporarily Disconnected Ground Resistance Meter Report any problems, defects of inconsistencies to your nearest nVent ERICO Distributor. Structure Bonding Cable (Disconnected from L P Ground) LP Grounding System Figure 43: Grounding and downconductor continuity testing 48 | nVent.com/ERICO...
  • Page 49 25 m 40 m 10 m 30 m 50 m Note the 62% factor to be used, as approximated in the table above. The earth electrode of interest must be disconnected from its connection to the site. 100% nVent.com/ERICO | 49...
  • Page 50: Maintenance Record

    NOTICE Users are advised that the nVent ERICO System 3000 Lightning Protection System may not function to its full efficiency under ice or snow conditions or on chimneys or stacks emitting gasses or pollutants. For advice on temperature or corrosion concerns, please contact your local nVent ERICO Distributor.
  • Page 51: Specifications

    Specifications nVent ERICO Dynasphere Enhanced Terminal Capture point of the nVent ERICO System 3000. Initiates an upward leader during storm conditions to attract lightning discharges over a greater radius than conventional protection. Height: 140 mm (5 ½ in.) Diameter: 255 mm (10 in.) Weight: 2.8 kg (6 lbs.)
  • Page 52 7 m Guy Kit 4 mm (⁵⁄ ₃₂ in.) 5 mm (³⁄ ₁₆ in.) Guy Diameter: Actual Guy Length: 6 m (20 ½ ft.) 10 m (34 ft.) Guy Tensile Strength: 430 kg (946 lb.) 560 kg (1232 lb.) 52 | nVent.com/ERICO...
  • Page 53 Purpose designed cable ties for securing of Ericore downconductor to the mast. Length: 521 mm (20 ½ in.) 7.9 mm (⁵⁄ ₁₆ in.) Width: Material: Stainless Steel Maximum Bundle Diameter: 152 mm (6 in.) Minimum Loop Tensile Strength: 250 lbs. nVent.com/ERICO | 53...
  • Page 54: Glossary

    5 m (17 ft.) of the upper termination. 54 | nVent.com/ERICO...
  • Page 55 | 55...
  • Page 56 ©2020 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice. ERICO-IM-E645IS12WWEN-System3000-USEN-2010...

Table of Contents