Troubleshooting
UUC112WC* / UUC118WC* / UUC124WC* / UUC130WC*
Fan Motor Not Operating
Fan motor will not operate
Inspect wiring and verify for
proper voltage
Check fan capacitor
Pass
Replace the fan motor
Model
UUC112WC*
UUC118WC*
UUC124WC* / UUC130WC*
Both Fan Motor and Compressor Not Operating
Start
Fail
Replace capacitor
µ
Capacitor
F
8
3
5
Fan motor & compressor will
Verify voltage and check wiring.
Check if contactor pulls in.
Pass
Check Discharge
Temperature Switch (FT)
Pass
Check High
Pressure Switch
CONNECT SERIES SERVICE MANUAL
Compressor Not Operating
Compressor will not operate
Inspect wiring and verify for
Check compressor capacitor
Replace the compressor
Model
UUC118WC*/UUC124WC*
Start
not operate
Fail
Replace contactor
Open
Temperature Switch (FT)
Open
Pressure Switch
Start
proper voltage
Pass
Fail
Replace capacitor
Capacitor
UUC112WC*
70
40
UUC130WC*
Replace Discharge
Replace High
µ
F
55
9