OmniMetrix TrueGuard PRO Configuration Manual

Advertisement

Quick Links

The OmniMetrix (OMNI) TrueGuard PRO monitor, with Modbus TCP functionality,
comes with default network configurations, and since it is easy to configure the
network settings on the PowerZone (PZ) control in the field, please configure the PZ
as follows:
The OMNI unit is configured for these network values:
IP Address: 10.0.1.202
Subnet Mask: 255.255.0.0
Gateway: 10.0.1.1
For a single PZ control, set the following:
Modbus Slave ID = 1
IP Address: 10.0.1.101
Subnet Mask: 255.255.0.0
Gateway: 10.0.1.1 (this is not important)
If multiple PZ controls are to be connected, such as in an MPS
configuration, use the following:
MPS Gen #
1
2
3
4
5
6
7
8
Modbus Slave ID
IP Address
1
2
3
4
5
6
7
8
www.omnimetrix.net ▪
4295 Hamilton Mill Road, Suite 100 ▪ Buford, GA 30518 ▪
770-209-0012
Generac PowerZone Modbus TCP
Configuration Guide
Subnet Mask
10.0.1.101
255.255.0.0
10.0.1.102
255.255.0.0
10.0.1.103
255.255.0.0
10.0.1.104
255.255.0.0
10.0.1.105
255.255.0.0
10.0.1.106
255.255.0.0
10.0.1.107
255.255.0.0
10.0.1.108
255.255.0.0
sales@omnimetrix.net
IM-815-02
04-MAR-2020

Advertisement

loading

Summary of Contents for OmniMetrix TrueGuard PRO

  • Page 1 Generac PowerZone Modbus TCP Configuration Guide The OmniMetrix (OMNI) TrueGuard PRO monitor, with Modbus TCP functionality, comes with default network configurations, and since it is easy to configure the network settings on the PowerZone (PZ) control in the field, please configure the PZ...
  • Page 2 In the case of multiple PowerZone controls, connect the system using a Hub or Switch as shown. This Hub / Switch should be powered by a genset battery or other uninterruptible power source: www.omnimetrix.net ▪ sales@omnimetrix.net IM-815-02 4295 Hamilton Mill Road, Suite 100 ▪ Buford, GA 30518 ▪...
  • Page 3 The backside of the display, looking from the inside of the cabinet, is the point of connection for the OmniMetrix monitor. The OMNI CAT5 cable goes into the top RJ45 connector, initially labeled “COMPUTER”...
  • Page 4 (Red and Black) pick up BATTERY+ and DC GND from the customer connection area at the bottom of the cabinet. For reference, this is the PowerZone Synch Control. No connection from the OmniMetrix monitor is made to this panel. Customer Connection Area www.omnimetrix.net ▪ sales@omnimetrix.net IM-815-02 4295 Hamilton Mill Road, Suite 100 ▪...
  • Page 5 This device, shown to the right, is also the point of data connection for the control. Top view of Connectivity Server www.omnimetrix.net ▪ sales@omnimetrix.net IM-815-02 4295 Hamilton Mill Road, Suite 100 ▪ Buford, GA 30518 ▪ 04-MAR-2020...
  • Page 6 RJ45 connector in the center. Plug the OMNI CAT5 cable into this RJ45. Attach the OMNI power wires, Red and Black, to generator Battery + and – respectively. www.omnimetrix.net ▪ sales@omnimetrix.net IM-815-02 4295 Hamilton Mill Road, Suite 100 ▪ Buford, GA 30518 ▪...

This manual is also suitable for:

Generac powerzone