LEGACY WIRING
Sometimes legacy wiring (unshielded and straight through, rather than shielded
twisted pair, often 22-6) results in slower connections and dropped packets between
the Openpath Reader and ACU. To remedy this, you can switch GND and VIN with +B
and -A connections on the ACU and readers to ensure the data pair (+B and -A) are
using the alternate pair of legacy wires.
RESETTING THE ACU
SOFT RESET
To soft reset the ACU, disconnect power from the ACU, wait 10 seconds, then
reconnect the power.
HARD RESET
WARNING: Only hard reset the ACU if absolutely necessary and if instructed by
Openpath. This will clear all of the data off of the ACU and will require
reprovisioning.
To hard reset the ACU:
1.
Disconnect power from the ACU
2. Hold down the ADMIN button for 15 seconds
3. While still holding down the ADMIN button, reconnect the power, and continue
to hold the button for another 15 seconds.
4. Wait 15 minutes before
PROVISIONING THE ACU
Provisioning the ACU means registering it in the Control Center and getting it up and
running with the latest firmware. You will need to re-provision in the case of
RESETTING THE
ACU.
Note: If you're provisioning ACUs for a customer account, the customer org will need
to be created by Openpath first.