General Information; Tank Construction - Lochinvar Thermal-Stor 100 Series Installation And Operation Manual

Heat pump storage tank
Table of Contents

Advertisement

1

General information

The following chart (Table 1A) details the relationship of
water temperature and time with regard to scald injury
and may be used as a guide in determining the safest water
temperature for your applications.
Table 1A Approximate Time / Temperature Scald Chart
APPROXIMATE TIME / TEMPERATURE
RELATIONSHIPS IN SCALDS
120°F
125°F
130°F
135°F
140°F
145°F
150°F
155°F
• Before using product, read and
WARNING
understand instructions.
• Save these instructions for future
reference.
• All work must be performed by
qualified personnel trained in the
proper application, installation, and
maintenance of the water systems in
accordance with all applicable codes
and ordinances.
• To prevent serious burns, wear heat
resistant gloves when handling hot
equipment.
Failure to follow this warning could cause
property damage, personal injury, or
death.
More than 5 minutes
1 1/2 to 2 minutes
About 30 seconds
About 10 seconds
Less than 5 seconds
Less than 3 seconds
About 1 1/2 seconds
About 1 second
Storage Tank Installation and Operation Manual
This manual is intended to cover installation, operation, and
maintenance procedures for Lochinvar's Heat Pump Storage
Tank.
If questions are not answered by this manual, or if specific
installation, operation, and/or maintenance procedures are not
clearly understood, contact Lochinvar for clarification before
proceeding.
Heat Pump Storage Tanks are designed for indoor use only.
It should be located on a level surface (no more than one-half
degree of slope), capable of supporting the total weight of the
unit when filled to capacity.
The unit should be mounted to the floor following applicable
architectural and local code requirements for the specific
installation site.
The high quality enamel paint, applied to the jacket of the
unit, will provide years of protection against corrosion. If it is
necessary to clean the outside of the unit, a mild cleaning agent
should be used that will not damage the paint.
For all piping connections, the use and/or type of joint
compound or sealer on the joints should be determined
by referring to local codes, accepted standards, and/or the
requirements of the installing contractor.

Tank construction

Heat Pump Storage Tanks are pre-engineered and pre-assembled
complete with all fittings. And like every Lochinvar product,
they are thoroughly tested to ensure proper performance from
the moment they are installed.
Tank Models -- Lochinvar offers four models of the Heat Pump
Storage Tank: HP250G, HP500G, HP750G, and HP1000G.
Tank Orientation -- Lochinvar Heat Pump Storage Tanks are
constructed in a vertical orientation.
Tank Lining -- Lochinvar Heat Pump Storage Tanks are
constructed with glass lining.
ASME -- All Lochinvar storage tanks are constructed per ASME
Section IV requirements, or Section VIII.
Pressure Rating -- Lochinvar tanks are available in 125 psi
working pressure (standard).
Cathodic Protection -- All glass lined tanks are equipped with
magnesium anodes to provide protection against corrosion.
Manway - A 12" x 16" manway is standard on all Heat Pump
Tank models (HP250G, HP500G, HP750G, and HP1000G).
Jacketing -- Lochinvar Heat Pump Storage Tanks are fitted with
a round sheet metal jacket.
3