Specifications; Ac Current Input Neutral; Ac Current Input Phase - Sel -2414 Manual

Transformer monitor
Table of Contents

Advertisement

Specifications

Compliance
Designed and manufactured under an ISO 9001 certified quality
management system
47 CFR 15B, Class A
Note: This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used
in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the
interference at his own expense.
UL Listed to U.S. and Canadian safety standards (File E220228;
NWGQ2, NWGQ8)
CSA certified for Hazardous Locations to Canadian and U.S.
Standards (File 205948; 2258-02, 2258-82)
CE Mark
RCM Mark
General
Operating Temperature Range
–40° to +85°C (–40° to +185°F), per IEC 60068
-
-
60068
2
2.
Note: LCD contrast impaired for temperatures below –20°C and
above +70°C (–4°F and +158°F, respectively).
UL/CSA Conformal
Coated:
–40° to +75°C (–40° to +167°F)
Operating Environment
Pollution Degree:
2
Overvoltage Category:
II
Relative Humidity:
5–95%, noncondensing
Maximum Altitude:
2000 m
Dimensions
See Figure 13 and Figure 14.
Weight
2.0 kg (4.4 lb)
Frequency
System Frequency:
50, 60 Hz
Inputs

AC Current Input Phase

I
I
NOM
NOM
Rated Range:
0.1–96.0 A
19.20 A
(according to IEC 60255
This is a linearity specification and is not meant to imply
Note:
continuous operation.
Continuous Thermal
Rating:
15 A
(according to IEC 60255
IEEE C37.90
1 Second Thermal:
500 A
(according to IEC 60255
Rated Frequency:
50/60 ±5 Hz
Burden (per phase):
< 0.050 VA
Measurement Category:
II
Schweitzer Engineering Laboratories, Inc.
-
-
2
1 and
= 5 A
I
= 1 A
NOM
0.02–
-
-
5, 60664
1)
3 A
-
6,
-
1989)
100 A
-
6)
50/60 ±5 Hz
< 0 .002 VA

AC Current Input Neutral

I
I
= 5 A
NOM
NOM
Rated Range:
0.05–10.00 A
(according to IEC 60255
This is a linearity specification and is not meant to imply
Note:
continuous operation.
Continuous Thermal
15 A
Rating:
(according to IEC 60255
IEEE C37.90
1 Second Thermal:
500 A
(according to IEC 60255
Rated Frequency:
50/60 ±5 Hz
Burden (per phase):
< 0.1 VA
Measurement Category:
II
AC Voltage Input (300 V)
Rated Operating
Voltage (U
):
100 –250 Vac
e
Rated Insulation Voltage: 300 Vac
10-Second Thermal:
600 Vac
Rated Frequency:
50/60 ±5 Hz
Burden:
< 0.1 W
DC Transducer (Analog) Inputs
Input Impedance:
200 Ω
Current Mode:
Voltage Mode:
>10 kΩ
Input Range (Maximum):
Current Mode:
±20 mA
Voltage Mode:
±10 V
Sampling Rate:
At least 5 ms
Step Response:
1 s
Accuracy at 25°C:
ADC:
16 bit
With user calibration:
0.05% of full scale (current mode)
0.025% of full scale (voltage mode)
Without calibration:
Better than 0.5% of full scale at 25°C
Accuracy Variation With Temperature:
± 0.015% per °C of full scale (± 20 mA or ±10 V)
DC Transducer (Analog) Inputs Extended Range Option
Input Impedance:
Voltage Mode:
>10 kΩ
Input Range (Maximum):
Voltage Mode:
±300 V
Sampling Rate:
At least 5 ms
Step Response:
1 s
Accuracy at 25°C:
ADC:
16 bit
With user calibration:
0.025% of full scale (voltage mode)
Without calibration:
Better than 0.5% of full scale at 25°C
Accuracy Variation With Temperature:
± 0.015% per °C of full scale (±10 V)
CMRR Typical:
65 db at 60 Hz
13
I
= 1 A
NOM
0.01–2.00 A
-
-
5, 60664
1)
3 A
-
6,
-
1989)
100 A
-
6)
50/60 ±5 Hz
< 0 .01 VA
SEL-2414 Data Sheet