Upgrading can be accomplished by placing the controller in a supplemental bay or in the same bay as the original equipment. Appendix A is a list of the various Lucent Technologies rectifiers, both J- and KS-coded, that have the automatic restart feature and are compatible with the ECS-6U.
For other customers worldwide, contact your local field support center or your sales representative to discuss your specific needs. Product Repair Repair and return service is provided for Lucent Technologies customers around the world. For customers in the United States, and Return...
Page 13
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 conformance issues prior to customer ownership, contact your local customer service. Issue 4 August 1998 Introduction 1 - 5...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Product Description Overview The ECS-6U Controller consists of a chassis equipped with two slide-out trays. The upper tray is equipped with a standard analog control unit, 113A2, which consists of two circuit packs: the control board (CP1) and the display board (CP4).
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Basic The basic ECS-6U controller monitors and controls any combination of up to six Lucent Technologies switchmode or Controller ® Lineage 2000 ferroresonant rectifiers and provides a single interface point for power alarm and status reporting. Equipped with a 113A2 Control Unit, a RIB, and a Fuse Alarm Board, the basic controller performs traditional analog control functions.
Page 19
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Office Alarm Alarm contacts are provided on the 113A2 that may be Contacts and connected to the office alarm system by the installer. (See Alarm Battery Section 4, “Wiring.”) Each set of contacts is a Form C or transfer Supply type, i.e., a combination of normally open and normally closed...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Battery on If rectifier output is insufficient to supply the load current for any Discharge Alarm reason (such as an ac power failure), the battery reserve will provide the necessary current. Such a battery discharge can be detected by a drop in the plant bus voltage.
Page 21
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 the external alarm system. HV is considered a Major alarm, so all Power Major alarm groups are also issued. When reporting the alarm, the controller sends a simultaneous shutdown signal to all rectifiers. Since the outputs of all rectifiers are paralleled in the plant, their output voltages are forced to be the same.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 113A2. DIP switches provide a visual verification of the shutdown set point at all times. For plants configured with the float/equalize feature, a separate high voltage shutdown threshold is used when the plant is in equalize mode.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 is intended to prevent multiple shutdown/restart cycles during heavy lightning storms that would otherwise stress the power equipment. Rectifiers that have not shut down are not affected by the restart signal from the controller and continue to run normally.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 condition. If the controller is equipped with CP2, the alarm can also be issued remotely. If it is equipped with CP3, the controller can be programmed to provide a hardware RFA alarm.
Page 25
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 occurs when a battery string disconnect switch is turned off manually or electronically. The Open String alarm (OS) is passed as a separate alarm to the microprocessor board. If the OS signal is wired directly to the controller alarm terminal blocks, it will generate a Minor Fuse Alarm whenever a battery string is open.
Page 26
The ECS-6U controller may be connected to the four output signals (TR1, TR2, TR3, and TR4) provided by a Rectifier Sequence Controller, such as Lucent Technologies model Issue 4 August 1998 Product Description 2 - 13...
Page 27
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 J87339A-1. These signals are used to turn off rectifiers or groups of rectifiers. Since sequence control is typically part of the ac engine system rather than part of the dc battery plant system, the rectifier sequence controller is often outside the battery plant and interfaces with the rectifiers through the battery plant controller.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 rectifiers in the plant from float mode to equalize mode and back again. This control is disabled when equalize is hardware disabled with the jumper described above. External Timer Panel: The 113A2 may interface with an external equalize control panel.
Board controller to permit non-Lineage rectifiers, whether manufactured by Lucent Technologies or not, to be used in any combination in the battery plant. This permits the user to obtain the latest technology features of the ECS controller in a variety of battery plants.
Isolator Circuit, are not part of the controller but can be used with it in certain applications. Boost Charge This circuit is approved for use only with Lucent Technologies Circuit 50 ampere or 25 ampere ferroresonant rectifiers in an FT-Series G plant configuration of two or three rectifiers.
One Plant types with each requiring different cable types. Cables for each rectifier type are available; however, only cables for rectifiers other than those made by Lucent Technologies will require ® termination in the field. If Lucent Technologies Lineage 2000 ®...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Table 2-B: Battery Plant Alarm Voltage Ranges 48-volt Plant Range Accuracy High Voltage Shutdown +/-0.5V Thresholds (adjustable 49.0V to 60.0V in 0.5V increments) Equalize High Voltage Shutdown Thresholds +/-0.5V 51.0V to 60.0V (adjustable in 0.5V...
Table 3-A: ECS-6U Controller Ordering Information List Description ECS-6U Controller for -48 volt plants. Provides ® interface to 6 Lucent Technologies Lineage 2000 rectifiers ECS-6U Controller for +24 volt plants. Provides interface to 6 Lucent Technologies ® Lineage 2000 rectifiers ECS-6U Controller for -24 volt plants.
FT-Series G embedded maintenance system Power cable to connect one Lucent Technologies boost charge panel (ED83108-30) to a List 1 or 3 controller Same as List A (CP2), with X.25/TL1 features Same as List B (CP2), with X.25/TL1 features...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Spare Parts Table 3-C lists the recommended spare parts for the ECS-6U Controller. Table 3-C: Recommended Spare Parts Comcode Description 106671746 113A2 Control Unit J85501E-1 48V Microprocessor Board without voice List A...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Documentation This document is part of a set of documents developed to assist equipment engineering and installation. Document No. Document Description Assembly, Ordering, and Installation J85501E-1 Drawing for ECS-6 Controller T-83122-30 Wiring Drawing for ECS-6U Controller...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Installation and Setup Introduction This section covers the installation and setup procedures for all configurations of the ECS-6U controller. Follow all the applicable steps in the following sections in the order they are presented.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 must be returned to the factory due to damage, reuse the crate and packing material. Check the contents against the shipping bill for completeness. • Assembled ECS-6U Controller J85501E-1 • Self-tapping mounting screws (#12-24 size) •...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Frame Mounting The controller is designed for 23-inch or 26-inch frame mounting. Two mounting brackets (standard) are shipped loose and should be assembled as shown in Figure 4-1. Brackets shown in Figures 4-2 and 4-3 are ordered per List BA to provide alternative mounting positions.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Hardware Setup Jumper straps are located on the upper tray backplane, and a combination of jumper straps and DIP switches are located on the control unit and the rectifier interface board (RIB). These jumpers and switches must be set properly before powering the controller.
Not all Lucent Technologies rectifiers are equipped with the equalize feature. Use equalize only if all the rectifiers have the equalize feature. The following is a list of Lucent Technologies rectifiers that have the equalize feature: 4 - 6 Installation and Setup...
Page 44
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 24 and 48 volt, 125 ampere, J85502C-1 24 and 48 volt, 200 ampere, J85503B-2 48 volt, 400 ampere, J85503C-2 48 volt, 400 ampere, J85503C-3 24 volt, 100 ampere, SR364B series 48 volt, 50 ampere, SR364A series...
S3 respective positions on the RIB to On (closed). To connect Lucent Technologies switch mode (SR) rectifiers or non-Lucent rectifiers, or if no rectifier is connected, open the S3 respective positions on the RIB.
(J85502 series) Control cable required to connect one non-Lucent Technologies rectifier or one H285-226, Lucent Technologies rectifier not listed on this table Control cable required to connect one Lucent H285-226, Technologies rectifier J87434 or J87435 equipped with SP3...
OPEN RESPECTIVE SWITCH POSITION IF NO RECTIFIER OR IF A LUCENT SWITCH MODE (SMR) RECTIFIER IS CONNECTED TO THAT PORT. Figure 4-9: RIB DIP Switch Settings Figure 4-10: Control Cable for Non-Lucent Technologies Rectifier Connection 4 - 14 Installation and Setup Issue 4 August 1998...
Board (RAB) pre-Lineage rectifiers either manufactured by Lucent Technologies or manufactured for Lucent Technologies to a J or KS specification. (See Figure 4-11.) DIP switches S1 through S6 on the RAB must be set corresponding to the port used for each ®...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Table 4-E: Non-Lucent Technologies Rectifier Control Signals Signal Signal Description Designation Positive voltage from point of regulation Negative voltage from point of regulation Restart, Restart Return: An isolated contact closure that is sent from the controller to the...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 E6-TO DISCHARGE BATTERY VIA WIRE KIT 846832343 TO J203 ON CP2 OF ECS CONTROLLER VIA TELEPHONE CORD (106595684) E5 - TO GROUND VIA WIRE KIT 846832343 P13 - ORDER WIRE SIGNAL LEADS...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Table 4-F: External Connections Required to Establish a Communication Link over the FT-Series G Embedded Telemetry System 417 Repeater 1.7 Repeater Terminal SD-7C441-01 T-96654-32 T-96654-37 T-96653-32 Connection For Site Fig. Note Fig.
Page 57
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Optional Boost The Boost Charge Panel shown in Figure 4-14 is optional for the Charge Panel plant. (FT Series G Only) All three of the following criteria must be satisfied to insure that a Boost Charge Panel is suitable for a particular battery plant.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 To J707 on Backplane Mounts to Shunt W-BL To P506-4 To P506-3 O-BK 847268679 ( 2 . 9 Panel Assy 846903730 Cable Assy 900557513 Scr. HHS .190-32 X 3/8 (3 Places) 406043489 ( 2 4 .
Page 59
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Shunt Isolator When a plant whose shunt is located in the “Batt” lead is Circuit connected to the ECS-6U, or the shunt size is not compatible with the ECS-6U (i.e., not listed in Table 4-C), the AKC1B Shunt Isolator Circuit must be used.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 2. For shunts with voltage ratings other than those listed in Table 4-G, select the next lower voltage rating for SW1. 3. Measure plant shunt voltage with voltmeter and record the reading.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Wiring Each circuit pack in the controller may require connection to systems outside the power plant or to other parts of the power system. The user must provide these connections. Basic Controller The installer wiring associated with the basic controller is connected to four removable terminal blocks on the 113A2.
Page 63
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Table 4-I: Terminal Block Pin Assignments for 113A2 Control Unit Pin No. Designation Definition Transfer Shutdown from TB101-11 Engine Transfer Shutdown from TB101-12 Engine Battery on Discharge External, TB102-1 BDEC alarm causes closure...
Page 64
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Table 4-I: Terminal Block Pin Assignments for 113A2 Control Unit Pin No. Designation Definition Power Major Audible, alarm TB104-1 PMJAC causes closure TB104-2 PMJAR Power Major Audible, return Power Major Audible, alarm...
Page 65
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 isolated contacts with a common return (TF/ER). A momentary closure between TEQ and the common return starts equalize. A momentary closure between TFL and the return stops equalize. The TR inputs from the external rectifier sequence controller should be contact closures to discharge ground (DG) to turn off rectifier groups.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 terminal blocks are each polarized differently and are therefore not interchangeable. 8. Slide the drawer in and out to ensure that the amount of cable slack is adequate. When the desired length is found, tie off the cable bundle with the wire ties and tie.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 TB101 Battery Disconnect Alarm -48V 1K Ohm Return Bulk Ringer Minor Alarm -48V 4.64K Ohm Major Alarm -48V 4.64K Ohm Return 113A2 Control Unit RMN and RMJ are general purpose alarm inputs that can be used for auxiliary equipment.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Office TB101 TB103 TB102 Alarm System PMNVC ACFEC PMNVR ACFER PMNVO ACFEO (Lamp Lights on Alarm) (A) AC Fail Paralleled with Power Minor Visual Alarm for Closure-on-Alarm Type System TB101 TB104 TB102...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Acceptance Testing Test Procedures The ECS-6U controller is tested as a unit and as a part of a battery plant system in the factory. This section of the manual is provided for those users who wish to repeat some of those test procedures as part of the installation and turn-up process.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Unless otherwise indicated in the test procedures, at least one NOTE rectifier must be on line in batteryless plants. Meter Calibration The controller voltmeter has an accuracy of 0.05% and a resolution of one digit. To verify the calibration of the voltmeter, an external meter with better than 0.05% accuracy is needed.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 normal, and repeat Step 5 by adjusting the rectifier voltage down slowly. Refer to the rectifier product manual for voltage adjustment procedures. 6. With the BD alarm present, check with a multimeter or...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 3. Momentarily short together pins 2 and 6 on TB101 on CP1 with a piece of wire. This simulates an equalize initiation signal from an external timer panel. Verify that the equalize LED lights and the rectifiers change to equalize mode.
Page 73
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 not still available to maintain the load, the red BD LED may also light. 7. Within ten (10) seconds of rectifier shutdown, the controller should automatically restart all rectifiers. The RFA LED should extinguish and the NORM LED should come on.
Page 74
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 12. Verify that only the NORM LED is lit on the controller. Reset the restart timer in the controller by pressing switch SW107, shown on Figure 4-5. This will prevent the controller from ignoring any HV shutdown that might occur in the next ten minutes.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 PMNE, PMNV, PMN, MNF 2. Remove the paper clip. The alarms should retire and the MNF LED extinguish. The PMN and MNF alarms in the terminal block should clear. 3. Repeat Steps 1 and 2 for all minor fuses, including F502 through F509.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Remote On/Off 1. Attach one end of a piece of wire to Discharge Ground (TR Signal) Test (DG) on pin 1 of TB101 on CP1. This wire will be used to ground the TR input signals to simulate a Rectifier Sequence Controller or other remote on/off device for controlling rectifiers.
Page 77
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 4. Disconnect the lead from the resistor, and note that the alarms retire and the NORM LED turns on. 5. Remove the resistor from TB101 pin 4, and connect it to the Ringer Minor Alarm input (RMN) on pin 5 of TB101.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Operation Front Panel The front panel switches and indicators provide the only operator interaction in a basic controller which is functioning Switches and normally. In the event of a controller malfunction, refer to Indicators Section 7, Troubleshooting.
Page 79
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Table 6-A: Front Panel Switches and Indicators MJF indicator Red LED, when lit, indicates an overcurrent protector on a critical circuit has operated. Such protectors include load circuit breakers/fuses, some controller fuses, and may also include auxiliary devices such as battery disconnects.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Troubleshooting Flowcharts This section contains five flowcharts for the purpose of troubleshooting the ECS-6U Controller, verifying controller alarms, and meter calibration. The flowcharts are listed below. Office Alarms Received 113A2 Control Unit Has Lost Power...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Figure 7-2.1: 113A2 Control Unit Has Lost Power Issue 4 August 1998 Troubleshooting 7 - 3...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Figure 7-2.2: 113A2 Control Unit Has Lost Power (continued) 7 - 4 Troubleshooting Issue 4 August 1998...
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 C. VERIFY CONTROLLER ALARMS SHEET 3 OF 4 IF A 12. IS CP2 INSTALLED? 13. GO TO STEP 46, SHEET 5 16. IS LED STILL LIT? 14. IS CP2 FUNCTIONING? 15. REMOVE CP2 18.
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Product Warranty A. Seller warrants to Customer only, that: 1. As of the date title to Products passes, Seller will have the right to sell, transfer, and assign such Products and the title conveyed by Seller shall be good;...
Page 92
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 Warranty Period Product Type New Product Repaired Product or Part Central Office Power 24 Months 6 Months Equipment *The Warranty Period for a repaired Product or part thereof is as listed or, in the case of Products under Warranty, is the period listed or the unexpired term of the new Product Warranty Period, whichever is longer.
Page 93
® Lucent Technologies Lineage 2000 ECS-6U Controller J85501E-1 the site. Products returned for repair or replacement will be accepted by Seller only in accordance with its instructions and procedures for such returns. The transportation expense associated with returning such Product to Seller shall be borne by Customer.