STO MANUAL
STO circuit manual
Hardware STO implementation in
RoboteQ motor controllers
Revision: 13
11.06.2020
roboteq sto manual_13.docx
1 of 9

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the STO and is the answer not in the manual?

Questions and answers

Summary of Contents for RoboteQ STO

  • Page 1 STO MANUAL STO circuit manual Hardware STO implementation in RoboteQ motor controllers Revision: 13 11.06.2020 roboteq sto manual_13.docx 1 of 9...
  • Page 2: Table Of Contents

    Company Information: ..............Error! Bookmark not defined. Scope .............................. 4 Motor controllers ........................... 4 Safe Torque Off (STO) ........................4 Safe Torque Off (STO) on Roboteq Controllers ................4 Activating STO ..........................5 Deactivating STO ..........................5 Constraints when using STO ....................... 5 FAILURE MESSAGES ........................
  • Page 3: Revisions Of This Document

    Kostas Andriotis 02.04.2019 First draft Kostas Andriotis 03.04.2019 Added CH 14, minor changes Kostas Andriotis 04.04.2019 Added !STT command, Added STO levels Minor changes Kostas Andriotis 22.04.2019 Added Constraints when using STO section, minor changes Kostas Andriotis 30.04.2019 Added missing info...
  • Page 4: Scope

    STO enables safe working and has a wide range of use in motion control/ systems with moving axes. The advantage of the integrated STO safety function compared with standard safety technology using electromechanical switchgear is the elimination of separate components and the effort that would be required to wire and service them.
  • Page 5: Activating Sto

    2- STO Fault LED at Roborun+ utility in failure This failure can have several internal and external reasons. If the failure is shown, please check the cabling and the signals to STO 1 and STO 2. Both signals much have at all times the same level. ...
  • Page 6: Sto Firmware Implementation

    Same status LED pattern is used for undervoltage and overvoltage faults and that should not be confusing. If STO fault appear it is normal for the controller voltage to be off and undervoltage fault to trigger. Either way this Status LED pattern indicates a situation that should be treated with caution.
  • Page 7: Stt - Sto Self-Test

    This process is applicable only on motor controllers with latest firmware v2.x installed. The result of the test is returned automatically. In case of fault the Respective STO Fault bit in the Fault Flags is set. The fault is triggered when: ...
  • Page 8: 15. Installation - Maintenance

    = W2 bottom fault 13. Installation – Maintenance STO Installation test The STO circuit needs to be tested before first installation and at least every 3 months according to the below sequence: 1. Activate STO (both logic level 0) 2.
  • Page 9: Sto Voltage Source Specification Attention

    14. STO Voltage source specification attention In order to have maximum response at STO implementation, user/installer/integrator should use voltage source with low output capacitance. In any other case, latency in activation might occur. 15. Compliance and Safety Metrics The STO function is compliant to: ...