American Innovations Lightning Arrester Surge Kit Quick Reference Manual

Advertisement

Installation and Configuration
Required Tools
Field Update Tool (FUT)
Windows
Laptop PC
®

Installing the Surge Arrester Kit

The following procedures are general steps for a typical installation. For additional information, please contact Technical
Support at 1-800-229-3404 or support@aiworldwide.com.
To prevent electrostatic discharge (ESD) damage when handling electronic equipment, always wear an anti-static
WARNING
:
wrist strap attached to an unpainted, grounded metal object. Ensure the wrist strap has maximum contact with bare skin.
NOTE:
For recti er types other than JA
do not need to install the Storm Trapper HE Surge Arrester.
1
Power Off All Devices & Install Storm Trapper
Ensure power has been terminated on recti er and all devices.
1
Install Storm Trapper HE Surge Arrester on AC input:
2
Install black leads across Line 1 and Line 2 of recti er's AC input.
a
These lines should be routed to the breaker.
Connect white lead to recti er chassis.
b
NOTE:
If an arrestor is already installed on the AC input, then install the Storm
Trapper HE Surge Arrester in parallel. Replace spade terminals with
terminals for easier connection to where existing arrester is connected.
Secure Storm Trapper HE Surge Arrester by zip-tie to suitable location or
4
place on oor of recti er.
2
Install DC Lightning Arrestor & Surge Detector
Attach DC Lightning Arrestor's black leads to recti er
1
2
Thread
DC Lightning
the Surge Detector's current transformer.
3
Connect a spade connector (included in kit) to the end of the
Arrestor's white wire and connect to common ground location.
4
Wire and connect the Surge Detector to the Bullhorn RMU's digital Channel 5. Be
sure to observe proper polarity.
5
Connect
DC Lightning
Polarity is not important as long as one wire is on the positive input and the other is
on the negative input.
6
DC Lightning Arrestor
installation tidy.
WARNING:
If wires are to be buried or covered, use conduit to protect the wires.
April 2020
RM4010
USB Mini-b cable
Bullhorn
Tools con guration software
®
Installation tools
If a non-Delta high energy surge arrestor is already installed on the AC input, you
Arrestor's white wire through the hole (marked Pulse) on
Arrestor's two yellow wires to Bullhorn RMU's Channel 6.
can be placed on recti er oor or anywhere to keep the
Lightning Arrester Surge Kit
Quick Reference Guide
Optional Items
at
DC
outputs.
DC Lightning
1 of 2
Quick Reference Guide
Hook-up wire for eld installation
Ground rod and copper wire
Storm Trapper HE
Surge Arrester
DC Lightning Arrestor
Surge Detector
(Continued on back)
Part No. 122248-000 Rev. 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Lightning Arrester Surge Kit and is the answer not in the manual?

Questions and answers

Summary of Contents for American Innovations Lightning Arrester Surge Kit

  • Page 1 Lightning Arrester Surge Kit RM4010 Quick Reference Guide Installation and Configuration Quick Reference Guide Required Tools Optional Items Field Update Tool (FUT) USB Mini-b cable Hook-up wire for eld installation    Windows Laptop PC Bullhorn Tools con guration software Ground rod and copper wire ...
  • Page 2 Ensure Channel 5 is enabled and the accumulator is turned on. Ensure Channel 6 is enabled. For additional information or questions, please contact Technical Support at 1-800-229-3404 or support@aiworldwide.com Part No. 122248-000 Rev. 1 © 2020 American Innovations, Ltd. Lightning Arrester Surge Kit Installation Quick Reference Guide 2 of 2...

Table of Contents