Lennox CHX35 Series Installation Instructions Manual

Indoor coil

Advertisement

THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for noncompliance.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
IMPORTANT: Special procedures are required for clean-
ing the aluminum coil in this unit. See page 8 in this in-
struction for information.
Shipping and Packing List
Package 1 of 1 contains:
1 - Evaporator coil
Check the components for shipping damage; if found, im-
mediately contact the last carrier.
INSTALLATION
INSTRUCTIONS
CHX35 Series Coils
INDOOR COILS
507835-01 (067198001)
4/2018

Table of Contents

Model Number Identification ...........................................2
Specifications ................................................................2
Releasing Air Charge .....................................................3
Installation .....................................................................3
Refrigerant Line Connections ........................................5
Leak Testing, Evacuating and Charging ........................6
Sealing Ducts ................................................................6
Condensate Drain Connections .....................................6
Blower Speed Selection ................................................7
Maintenance ..................................................................8
General Information
CHX35 horizontal evaporator coils are designed for use
with air conditioners and heat pumps and are supplied
with a factory-installed HFC-410A check/expansion valve.
The coil drain pan has a maximum service temperature
of 500°F. The drain pan must be at least 2" away from a
standard gas-fired furnace heat exchanger and at least
4" away from any drum-type or oil-fired furnace heat ex-
changer. Closer spacing may damage the drain pan and
cause a leak.
Refer to the Product Specification bulletin (EHB) for the
proper use of these coils with specific furnaces, outdoor
units and line sets.
These instructions are intended as a general guide and
do not supersede local or national codes in any way. Au-
thorities who have jurisdiction should be consulted before
installation.
Page 1

Advertisement

Table of Contents
loading

Summary of Contents for Lennox CHX35 Series

  • Page 1: Table Of Contents

    INSTALLATION INSTRUCTIONS CHX35 Series Coils INDOOR COILS 507835-01 (067198001) 4/2018 Table of Contents Model Number Identification ...........2 Specifications ..............2 Releasing Air Charge .............3 THIS MANUAL MUST BE LEFT WITH THE Installation ..............3 HOMEOWNER FOR FUTURE REFERENCE Refrigerant Line Connections ........5 WARNING Leak Testing, Evacuating and Charging ......6...
  • Page 2: Model Number Identification

    Model Number Identification X 35 Unit Type Cabinet CH = Indoor Coil - Horizontal F = Cased Refrigerant Type Metering Device X = HFC-410A 6 = Factory-Installed Check/Expansion Valve Series for HFC-410A Refrigerant (non-bleed port) Nominal Cooling Capacity Cabinet Width 18 = 1.5 tons 48 = 4 tons A = 14-1/2 in.
  • Page 3: Releasing Air Charge

    Specifications – cont’d 48B – 60D General Data CHX35 CHX35 CHX35 CHX35 Model No. -48B-2F -48C-2F -51C-2F -60D-2F Nominal size - tons 3.5 / 4 3.5 / 4 Line Suction/Vapor o.d. - in. sweat Connections Liquid o.d. - in. sweat Condensate drain (fpt) - in.
  • Page 4 NOTE – When the coil is connected directly with a con- densing furnace, the coil must be level from return end to supply end. The front (access side) of the furnace may be TEST HOLE FIELD FABRICATED pitched downward up to 1 inch to accommodate a ½-inch INSULATED BLOCK- OFF PLATE pitched coil.
  • Page 5: Refrigerant Line Connections

    BRAZING GUIDELINES Refrigerant Line Connections Use a silver alloy brazing rod (5 or 6 percent silver alloy for copper-to-copper connections or 45 percent silver al- LINE SIZES loy for copper-to-brass or copper-to-steel connections). The refrigerant line sets should be sized according to the Before making brazed connections, place a field-provided recommendations given in the air conditioner or heat pump heat shield, such as a wet rag, against the unit cabinet...
  • Page 6: Leak Testing, Evacuating And Charging

    LIQUID LINE CONNECTION IMPORTANT Use the following procedure to connect the liquid line to the indoor coil: DUCT SYSTEM SIZING - The duct system should be 1 - Remove rubber plug from the stubbed connection. properly sized and installed according to the ASHRAE Standard Manual D.
  • Page 7: Blower Speed Selection

    OVERFLOW DRAIN LINE ABOVE ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOT POSSIBLE TO FINISHED ROUTE OVERFLOW DRAIN LINE, INSTALL LOW VOLTAGE SPACE? VENT MUST EXTEND OVERFLOW SWITCH KIT. WIRE SHUT DOWN ABOVE HEIGHT OF COMPRESSOR PER INSTRUCTIONS. COIL DRAIN PAN BY TWO INCHES VENT OEM CATALOG#...
  • Page 8: Maintenance

    (less than 50psi). If the coil cannot from other metal parts. Use wire ties to secure tubes be cleaned using water alone, Lennox recommends use of a coil cleaner with a pH in the range of 5 to 9.

This manual is also suitable for:

Chx35-18a-2fChx35-24a-2fChx35-24b-2fChx35-30a-2fChx35-30b-2fChx35-36a-2f ... Show all