INSTALLATION INSTRUCTIONS LD4120 SMOKE DETECTOR REPLACEMENT KIT (73W51
& 73W52; LB−90945R & S) USED WITH SGA/SCA/LGB/LCB/LGE/LCE036−240 UNITS
Shipping and Packing List
Package 1 of 1 contains:
1− Smoke detector
3− Sampling tubes (two tubes on 73W52)
1− Smoke detector bracket
1− Sampling tube bracket (73W52 only)
1− Bag assembly containing:
1−Magnet
6−#10−16 X 5/8" screws
2−#8−32 X 1" screws
Application
The smoke detector replacement kit is used on
SGA/SCA/LGB/LCB/LGE/LCE036, 060, 120, 240, & 288
units. LD4120 replaces DH400 and DH100 smoke detectors.
73W51 is used in return air installations and 73W52 is used
in supply air installations.
Smoke detector will send a 24vac signal to the unit A55
IMC when smoke is sensed. IMC default mode will
de−energize unit. Some units will interrupt the main power
signal to the unit to de−energize the unit when smoke is
detected.
METAL
SAMPLING TUBE
SENSOR HEAD
MAGNET TEST LOCATION
02/11
*2P0211*
PACKAGED UNITS KITS
AND ACCESSORIES
506748−01
2/2011
Supersedes 506592−01
Installation
Refer to manufacturer's instructions provided with smoke
detector.
Install Sampling Tubes
1− Install sampling and exhaust tubes in smoke detector
Improper installation, adjustment, alteration, ser-
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser-
vice must be performed by a qualified installer, ser-
vice agency or the gas supplier
SMOKE DETECTOR
EXHAUST TUBE
FIGURE 1
Page 1
LD4120 REPLACEMENT
SMOKE DETECTOR KIT
before installing smoke detector or bracket in unit.
The exhaust tube is packaged with the smoke
detector. See figure 1. Also refer to figure 2 and 3 for
supply air installations and figure 5 for return air
installations. Discard unused tubes.
Unit
Supply Air
036/060
18
120
30
240
30
WARNING
POWER BOARD
POWER BOARD MODULE COVER
SENSOR MODULE
COVER
*P506748-01*
Tube Length (in.)
Return Air
18
30
36
506748−01