Download Print this page

Lennox 73W51 Installation Instructions page 3

Ld4120 replacement smoke detector kit

Advertisement

1− Holes in sampling tube must face upward
toward blower.
2− Insert tubes from the back side of the smoke
detector until tubes snap into place.
3− Install the red cap on the end of the sampling
tube that is exposed to the air stream.
4− Place magnet on sheet metal close to the
detector.
5− Apply foil tape over the two sampling tube
holes closest to the smoke detector.
Smoke detector rotated 180°
when detector being replaced is
not equipped with a 15−pin plug.
DISCONNECT SEPARATE POWER SUPPLY
(WHEN PRESENT)
Disconnect 24v wires
to smoke detector.
FIGURE 4
SMOKE DETECTOR − SUPPLY AIR INSTALLATIONS
SAMPLING
TUBE
Knockout this hole
and route wiring here.
FIGURE 3
Page 3
MAGNET
RED CAP
EXHAUST
BRACKET
TUBE
SMOKE
DETECTOR
TABLE 1
Smoke Detector Terminal Marking
DH400
DH100
1
9
2
10
3
2
4
11
5
15
6
20
7
19
8
4
9
5
10
14
11
3
12
120 VAC
13
120 VAC
15
16
16
6
17
17
18
7
19
18
20
8
21
13
22
12
23
1
BLOWER
DECK
Descrip-
LD4120H
tion
1
24V AC/DC
2
24V AC/DC
3
R Reset
4
R Test
5
Alarm
6
Aux Out −
7
Aux Out +
8
Alarm, Com
9
Alarm, NO
10
SUP, NO
11
SUP, Com
12
120 VAC
13
120 VAC
15
Aux A, NC
16
Aux A, Com
17
Aux A, NO
18
Aux B, NO
19
Aux B, Com
20
Aux B, NC
21
SUP, NC
22
Int+
23
Int/Aux−

Advertisement

loading

This manual is also suitable for:

73w52Lb−90945rB−90945s