Ecotech GTS RIV-601P Applications Manual

Ecotech GTS RIV-601P Applications Manual

Ir flame detector

Advertisement

Quick Links

IR FLAME DETECTOR
RIV-601P/F
EN 54-10 class 1
VdS approval G 211093
EC-certificate of conformity no. 0786 - CPD - 21103
application manual
rev. 5 NOV18
ECOTECH GTS SRL Via del Plan del Sant, 24 38012 Predaia Fraz. Mollaro (TN) P.IVA 02553340221
Tel. 0463 461049 |Fax 0463 461375 info@ecotechgts.com www.ecotechgts.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GTS RIV-601P and is the answer not in the manual?

Questions and answers

Summary of Contents for Ecotech GTS RIV-601P

  • Page 1 VdS approval G 211093 EC-certificate of conformity no. 0786 - CPD - 21103 application manual rev. 5 NOV18 ECOTECH GTS SRL Via del Plan del Sant, 24 38012 Predaia Fraz. Mollaro (TN) P.IVA 02553340221 Tel. 0463 461049 |Fax 0463 461375 info@ecotechgts.com www.ecotechgts.com...
  • Page 3: Table Of Contents

    IR FLAME DETECTORS SUMMARY Page • RIV-601P/F general notions ......................3 • RIV-601P/F description .........................4 • Electrical and general characteristics ..................5 • RIV-601P/F inside view .........................6 • RIV-601P/F mechanical dimensions .....................7 • RIV-601P/FA explosion-proof model with SOA-875 variable direction stand ......8 •...
  • Page 4: Riv-601P/F Description

    IR FLAME DETECTOR RIV-601P/F General notions At higher temperature a shorter wavelength is generated and viceversa. The IR flame detector sees very well this IR radiation but is The IR flame detector model RIV-601P/F is an electronic optical fire near blind to the visible light. detector device that responds immediately to the thermal infrared Furthermore the thermal infrared radiation passes through the smoke, radiation emitted by fire, and is tuned to the pulse frequency of the...
  • Page 5: Riv-601P/F Operation

    IR FLAME DETECTOR RIV-601P/F DESCRIPTION It is equipped with the “teletest” device for remote monitoring of detector. The IR flame detector model RIV-601P/F is an electronic optical fire This device simulates a flame inside the detector so as to stimulate a detecting device which responds immediately to the thermal infrared sensor response like to a real fire.
  • Page 6 IR FLAME DETECTOR MODEL RIV-601P/F IR FLAME DETECTOR MODEL RIV-601P/FA watertight enclosure explosionproof enclosure ELECTRICAL AND GENERAL SPECIFICATIONS DESCRIPTION AND SPECIFICATIONS • Cast aluminium watertight case, IP66 grade protection (dust and water All same as for RIV-601P/F model except: spray). Explosion-proof available with the model RIV-601P/FA. •...
  • Page 7: Riv-601P/F Flame Detector Applications

    RIV-601P/F IR FLAME DETECTOR Inside view After the enclosure is opened, the inside view looks as follows: mounting through holes which don’t have any lid mounting contact with the inside screws space 20 mm base DELAY TIME SETTING INFRARED INCANDESCENT SENSOR BULB RELAY...
  • Page 8 RIV-601P/F IR flame detector mechanical dimensions • IP66 grade protection (dust and water spray). • Dimensions 180x85x65(H)mm (mounting holes 125x70mm). • Weight 700grams. 4 mounting through holes which don’t have any contact with the inside space RIV-601P/F IR FLAME DETECTOR 0786 - CPR - 21103 EN 54-10 class 1 VdS approval G 211093...
  • Page 9 RIV-601P/FA IR Flame detector explosion-proof model RIV-601P/F model plus ADF-600AP explosion-proof enclosure The explosion proof model RIV-601P/FA is made by mounting the watertight model RIV-601P/F inside the explosion-proof case. The RIV-601P/FA shipping package includes: • 1 IR flame detector model RIV-601P/F •...
  • Page 10 RIV-601P/F IR flame detector operation The RIV-601P/F infrared Flame Detector turns on into the alarm state The detector field of view is a 90° cone, starting at the optical window after a pre-set delay time (waiting time) from the moment a flame is centre.
  • Page 11: Vertical Application With Full Area Coverage

    RIV-601P/F IR flame detector applications Mounting information For example, from a height of 10 m a floor area of 14x14m can be The waterproof model RIV-601P/F can be installed without any controlled. bracket by means of four screws. This sort of installation uses the full detector field of view, that is the The explosion-proof model RIV-601P/FA is made by mounting the best one.
  • Page 12: Vertical Application With Partial Area Coverage

    RIV-601P/F IR flame detector applications The smallest detectable flame size is 20 cm on the centre (2%  - Vertical application with PARTIAL area coverage of 10m distance) and 28cm on the border (2% of 14m When ceiling is low or not high enough for full coverage, the distance).
  • Page 13: Diagonal Application With Full Area Coverage

    RIV-601P/F IR flame detector applications  Also, the diagonal mounting makes the detector seeing other strong - Diagonal application with FULL area coverage infrared lights entering into its field of view, like lamps and sun, which When ceiling is too low for full area coverage with centre vertical can cause false alarms.
  • Page 14: Vertical Application Of Two Detectors With Full Area Coverage

    RIV-601P/F IR flame detector applications  This type of application is the double of the “A” type described above, - Vertical application of two detectors with FULL area coverage and has a better performance than the “C” type of the previous page. When a room cannot be under the field of view of one detector, then In the case of a room 10 m high with a floor of 14x28 m the smallest the room can be divided into two detection areas, each of them being...
  • Page 15: Diagonal Application Of Two Detectors With Full Area Coverage

    RIV-601P/F IR flame detector applications  In the second case the room is the same but the two detectors are - Diagonal application of two detectors with FULL area coverage mounted in a slightly different position. The disadvantages of the diagonal mounting must be considered In this example of application two detectors are mounted diagonally before deciding for this solution.
  • Page 16: Vertical Application Over Pole With Full Area Coverage

    RIV-601P/F IR flame detector applications In the case sensitivity is too high for the application, one or more  - Vertical application over pole with FULL area coverage attenuation optical filter can be added on the front of the optical For outdoor applications the rules to be followed are the same as the window.
  • Page 17 RIV-601P/F IR flame detector electrical connections Output: The electrical connections are done on 7-way screw type terminal block, plug in type. • One static output on the “S” terminal from an NPN collector. Each terminal function is printed on the top of every terminal and on Normally it is high (+24V).
  • Page 18 RIV-601P/F IR flame detector remote test function The test function makes it possible to remotely monitor the full The T+ terminal is connected to +24V through a normally open test detector operation both if in alarm state or if faulty. This function is pushbutton.
  • Page 19 RIV-601P/F IR flame detector automatic remote fault warning Electrical connections to a standard fire alarm panel Both the normally open (C-L) and the normally closed (C-R) relay contacts are used. The normally open contact (C-L) is used for the fire alarm and provides the line current determined from the R1 and R2 resistors parallel.
  • Page 20 FIL 39G attenuation optical filter Sometimes the presence of strong noise, coming from sun or One filter disc decreases the detector sensitivity from the standard incandescent lights modulated by moving trees or other things, that value of 2% to 3%. cannot be avoided by changing the detector position, needs to Then the smallest detectable flame size becomes 3% of the distance.
  • Page 21 SOR-876 VARIABLE DIRECTION STAND for IR Flame Detector RIV-601P/F Description The Variable Direction Stand SOR-876 is a useful accessory for installing IR Flame Detector RIV-601P/F when an easy change of direction of the optical field of view toward the area of interest is needed.
  • Page 22 MAFP 21-GB rev. 1 DEC16...
  • Page 23 rev. 0 NOV11 MAFP 22-GB...
  • Page 28 ECOTECH GTS SRL Via del Plan del Sant, 24 38012 Predaia Fraz. Mollaro (TN) P.IVA 02553340221 Tel. 0463 461049 |Fax 0463 461375 info@ecotechgts.com www.ecotechgts.com...

This manual is also suitable for: