WATER-COOLED REFRIGERANT RECOVERY AND RECYCLING UNITS OPERATION & MAINTENANCE Supersedes: 50.40-OM1 (904) Form 50.40-OM1 (713) LD17585 PORTABLE RECOVERY PAK™ LD17584 EASYTANK™ LD17583 RSR UNITS Issue Date: July 17, 2013...
Page 2
All wiring must be in accor dance with Johnson Controls’ published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals.
Page 3
FORM 50.40-OM1 (713) ISSUE DATE: 07/17/2013 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls’ policy for contin- these documents, the technician should verify whether uous product improvement, the information contained the equipment has been modified and if current litera- in this document is subject to change without notice.
Page 4
FORM 50.40-OM1 (713) ISSUE DATE: 07/17/2013 THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
JOB SITE, OR LOSS OF PARTS. containers of gasoline or other flammable prod- ucts. If damage is found, Johnson Controls must be notified and action must be taken to prevent further damage or • This equipment should be used in a location with deterioration of the machinery, i.e.: a slow refrigerant...
The unit has permanent-mounted ball valves to allow the unit to remove, replace, or distill refrigerant without hav ing to break hoses to the chiller. Eight feet of heavy duty refrigerant hoses with flare fittings are included to allow connection to the chiller. JOHNSON CONTROLS...
119 x 36 x 77 112 x 42 x 90 Wheels Included Optional Optional Relief Valves (2) 5/8” Flare (2) 3/4” FNPT (2) 1” FNPT (2) 1” FNPT ASME Approved *Wheels add 13" to overall height dimension of RSR-4436 and 4445 JOHNSON CONTROLS...
3022 x 914 x 1956 2845 x 1067 x 2286 Wheels Included Optional Optional Relief Valves (2) 5/8” Flare (2) 3/4” FNPT (2) 1” FNPT (2) 1” FNPT ASME Approved *Wheels add 330 mm to overall height dimension of RSR-4436 and 4445. JOHNSON CONTROLS...
CUT IN REFRIGERANT HIGH PRESSURE LOW PRESSURE HIGH PRESSURE LOW PRESSURE PSIG IN HG PSIG IN HG CFC-12/HFC-134a 1034 Manual Reset CFC-500 1241 Manual Reset CFC-502 1724 Manual Reset HCFC-22 1724 Manual Reset CFC-11/HFC-123 Manual Reset CFC-114 Manual Reset JOHNSON CONTROLS...
Page 14
Low Pressure Units for the correct procedure to add valve on the top of the storage vessel and the refriger- or remove oil from the vacuum pump and oil separator. ant connection on the condenser of the portable RSR unit. JOHNSON CONTROLS...
(con nection between valves 1 & step.) 2), open valves 1, 2, 3, & 4 during evacuation – close valve 5. (See Figure 1 on page 15) LD01105 FIGURE 1 - YORK RSR SYSTEM FLOW DIAGRAM JOHNSON CONTROLS...
Open Closed Open Valve 5 Open Closed Closed Closed Open Compressor Water to Condenser Heater CHILLER/AIR CONDITIONER Valve 6 Open Closed Closed Closed Open Valve 7 Open Open Open Open Open Chiller Water Pump Either Condenser Water Pump JOHNSON CONTROLS...
After a waiting period of 5 minutes, the pressure in the refrigeration unit is to be checked. If the pressure has risen due to residual refrigerant re- maining in the refrigeration unit, the Gas Pump Out JOHNSON CONTROLS...
10.2 Set the valves and pumps as indicated in column 5 of Table 26.5 13.2 6 on page 16. Turn the toggle switch on the RSR to the 26.0 16.4 ON position. 25.4 20.1 10.4 24.7 24.0 13.3 JOHNSON CONTROLS...
220.3 358.9 263.7 *Vapor pressures are shown as PSIG. Screened figures are shown 37.7 234.6 381.5 280.7 as inches of mercury vacuum. *Vapor pressures are shown as PSIG. Screened figures are shown as inches of mercury (HG) vacuum. JOHNSON CONTROLS...
ISSUE DATE: 07/17/2013 Johnson Controls supplies mating "Twist-Lock" plug for field wiring connection by customer. (1) flex cord with special interlock plug supplied by Johnson Controls for wiring to customer's Pumpout vessel pressure liquid level switch. *Interlock Receptacle will not allow Legend EASYPAK Compressor to operate unless...
Switch-Heater Belt High Pressure Vessel Refrigerant Hoses Base for Unit Relief Assembly Valve Belt Guard Sight Glass Power Wire Gauges Casters Oil Separation Purge Valve Heater Float Switch FIGURE 7 - PIPING DIAGRAM RSR-2212, -2222, -2240, -4436, -4445 JOHNSON CONTROLS...
The belt tension adjustment should be made so the belt is taut, but not too taut to create excessive bearing loads. Due to the pulsating load created by the compressor, the JOHNSON CONTROLS...
Page 30
And next, crack the flare fitting on the tube that connects the valve manifold to the oil separator to purge air from the compressor and oil separator. 11. Open the manifold valves as required for the next re covery operation. JOHNSON CONTROLS...
If pressure drops more than 5 Ibs. (34.5 kPa) in one minute, this indicates the discharge valves of the valve assembly are leaking and should be replaced. If in doubt as to whether the discharge valves leak, JOHNSON CONTROLS...
Page 32
3. All gasket material adhering to the head, valve plate, or cylinder, should be carefully removed in such a manner that the machined sealing surfaces are not scratched or nicked. JOHNSON CONTROLS...
1. Gasket Kit BMK-683-7 contains one complete set of all gaskets 2. Parts included inside broken lines are sold as kits per B/M shown. [Example: BMK-680-6 would be (3) parts only] LD17582 FIGURE 9 - COMPRESSOR REPLACEMENT PARTS – MODEL CFC-1000 JOHNSON CONTROLS...
BMK683-7 Gasket Kit 6. Before putting on end plate, thoroughly clean and oil with 300 viscosity refrigeration oil on both seal- BMK679-1 Valve Plate Kit ing faces. Install floating seats in end plate as fol- lows: BMK665-8 Seal Kit JOHNSON CONTROLS...
FORM 50.40-OM1 (713) SECTION 5 - REPLACEMENT PARTS AND KITS ISSUE DATE: 07/17/2013 LD01115 FIGURE 10 - COMPRESSOR REPLACEMENT PARTS – DISCONTINUED MODEL 16799 JOHNSON CONTROLS...
16714* Discharge Valve Spring 16715* Discharge Valve Screw 16716* Discharge Valve Lock Wire 19 Ga.* Valve Plate Assembly (includes repair gaskets) 16717 Shaft Seal Spring Shaft Seal Ring Shaft Seal Carbon Shaft Seal Assembly (includes repair gasket) 16999 JOHNSON CONTROLS...
Do not allow any solvent to seep into crank case oil. 11. Replace cylinder head and tighten belts, using the torque requirement specified for the valve plate (See Table 18 on page 36). JOHNSON CONTROLS...
FORM 50.40-OM1 (713) SECTION 5 - REPLACEMENT PARTS AND KITS ISSUE DATE: 07/17/2013 LD03861 FIGURE 11 - COMPRESSOR REPLACEMENT PARTS – MODELS RA AND CK JOHNSON CONTROLS...
Suction Cover Plate 41110-2 Capscrew 10010-8 Suction Strainer Assembly 27508 Gasket (Suction Cover Plate) 30016 507-2 Suction Cover Plate 41110-1 Union 60213 Main Bearing 41099-P1 Dowel Pin 41074 Capscrew 10010-7 End Plate 41152 Gasket (End Plate) 30063 507-2 JOHNSON CONTROLS...
Page 42
AI605 Piston Ring 41150-1 Piston Pin 21509 AI605 Flywheel Locknut CBW2708 675-7 Flywheel 25531-2 Rod Bearing Inserts CBW2508 A1606-1 AI604-1 Note: Only parts that can be ordered over-sized are 41150-2 .030, AI605 .030, AI613 .030 and CBW2508 .010. JOHNSON CONTROLS...
Tighten the mounting oil change may be all that is required. screws uniformly and refill the pump with DuoSeal oil. Follow instructions included in repair kit. LD01114 FIGURE 12 - VACUUM PUMP REPLACEMENT PARTS – MODEL CRR-1 JOHNSON CONTROLS...
Repairing Technique Thin composition gaskets are generally used for large irregu larly shaped areas. A replacement joint of this type should be thoroughly cleaned of all previous gas- ket material and the mating surfaces cleaned of any nicks. JOHNSON CONTROLS...
FORM 50.40-OM1 (713) SECTION 5 - REPLACEMENT PARTS AND KITS ISSUE DATE: 07/17/2013 LD17570 FIGURE 13 - COMPRESSOR DATA SHEET – MODEL 51VSM JOHNSON CONTROLS...
(°C), subtract 32° and multiply by 5/9 or 0.5556. Example: (45.0°F - 32°) x 0.5556 = 27.2°C To convert a temperature range (i.e., a range of 10°F) from Fahrenheit to Celsius, multiply by 5/9 or 0.5556. Example: 10.0°F range x 0.5556 = 5.6 °C range JOHNSON CONTROLS...