Description
The Y99AB-4 Test Kit combines four test functions
to enable service contractors to test BASO® controls
and thermocouples in the field. These four functions
are:
Millivoltmeter with 0 to 50 and 0 to 1000 ranges
for checking the open and closed circuit
millivoltage of thermocouple leads.
Performance Tester with a source of power for
holding open BASO power units while taking
open circuit millivolt readings of the
thermocouple when the main burner is in
operation.
Milliammeter with a 0 to 500 (50 on scale)
range for checking the current dropout range of
BASO power unit assemblies. (There are
10 milliamperes for each division on the dial.)
Continuity Tester for detecting a broken or
open circuit.
© 2002 Johnson Controls, Inc.
Part No. 24-8711-838, Rev. —
A
PPLICATION
Y99AB-4 BASO® Test Kit
64119-1D
Adapter Assembly
44549-4
Lead Assembly
44549-7
Lead Assembly
0-500
ADJUST
MILLIAMPS
40073-4
Lead Nut
N
OTE
Definitions
Automatic Pilot - A device employed with gas burning
equipment, which automatically shuts off the gas supply
to the burner being served by either direct or indirect
means when the pilot flame is extinguished. The pilot
burner may or may not be constructed integrally with the
device.
Closed Circuit - Millivoltage measured with the BASO
control attached to the thermocouple.
Couple Lead - The thermocouple, current carrying
conductors, and attaching nut.
Dropout - The point, defined by a millivolt or milliampere
reading, at which the electromagnet releases the
armature.
Milliampere - One thousandth of an ampere.
Abbreviation mA used to check BASO control dropout.
Millivolt - One thousandth of a volt. Abbreviation mV
used to measure thermocouple output.
Open Circuit - Millivoltage measured without the BASO
control attached to the thermocouple.
Power Unit - Electromagnet unit that is internally
connected to the seat of the gas valve and cuts off the
gas when pilot flame fails. Also called a power unit
assembly or hood.
Reset Button - The button that is manually depressed to
place the BASO control in operation.
Thermocouple - The pair of dissimilar metallic elements
joined to produce a millivoltage when the junctions are at
different temperatures.
Application Note
Y99AB-4
Issue Date
May 15, 2002
www.johnsoncontrols.com
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the Y99AB-4 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls Y99AB-4

  • Page 1 Description Power Unit - Electromagnet unit that is internally The Y99AB-4 Test Kit combines four test functions connected to the seat of the gas valve and cuts off the to enable service contractors to test BASO® controls gas when pilot flame fails.
  • Page 2: General Instructions

    Limit Switch 0-1000 position. Figure 4: Junction Block Thermocouple 5. Re-establish pilot flame. 6. The millivolt reading should agree with the values listed in Table 1 with a normal pilot flame (see Figure 3). Y99AB-4 BASO Test Kit Application Note...
  • Page 3 Lead Adapter Note: When taking a fixed load millivolt reading Assembly on a junction block thermocouple, the junction Figure 5: Fixed Load Millivolt Reading Connection block terminal must be shorted (see Figure 4). Diagram Y99AB-4 BASO Test Kit Application Note...
  • Page 4 If flames do not extinguish, refer to the Troubleshooting section. MILLIAMPS 0-500 DC MILLIVOLTS 0-1000 0-50 44549-7 PENN-BASO CONTROLS MILLIVOLTS JOHNSON CONTROLS, INC WATERTOWN, WI., U.S.A ADJUST MILLIVOLTS MILLIAMPS Reset Button 44549-8 Gas Valve Figure 6: Dropout Testing Connection Diagram Y99AB-4 BASO Test Kit Application Note...
  • Page 5: Continuity Testing

    Table 1. MILLIAMPS 0-500 DC M ILLIVOLTS PENN-B ASO CONTROLS 0-1000 0-50 MILLIVOLTS ADJUST MILLIAMPS MILLIVOLTS 44549-8 Black Reset Button Thermocouple Lead High Pressure Gas Valve Figure 7: Closed Circuit Test Connection Diagram Y99AB-4 BASO Test Kit Application Note...
  • Page 6 Figure 8: Typical Thermocouple-operated Gas Valve Connection Diagram Power Source Thermostat Transformer “B” Valve BASO Power Shutoff Unit Valve Reset Button 44549-7 BASO Magnetic Operator 44549-8 Black Pilot Burner Gas Line Thermocouple Lead Figure 9: Typical Electrically-operated Gas Valve Connection Diagram Y99AB-4 BASO Test Kit Application Note...
  • Page 7 “L” Series Control Power Source Thermostat Transformer Shutoff Valve “B” 44549-7 Valve 44549-8 Black Pilot Burner Gas Line Thermocouple Lead Figure 10: Typical Safety Shutoff Device Connection Diagram Y99AB-4 BASO Test Kit Application Note...
  • Page 8: Troubleshooting

    Perform the Dropout Testing procedure. Defective orifice Clean or replace orifice. Unusually strong drafts Baffle secondary air or shield burner. Controls Group 507 E. Michigan Street P.O. Box 423 Printed in U.S.A. Milwaukee, WI 53201 www.johnsoncontrols.com Y99AB-4 BASO Test Kit Application Note...