TEMPERATURE CONTROLLER FOR TWO-BATTERY
AIR HANDLING UNIT
OPTIONAL
C
BUS
XTA 624
C1 Eng.
• Temperature control in air handling units
• Communication systems :
– C-Bus : XTA 624 Telemanagement optional;
to enable Telemanagement use the "C-Bus Plug-in" type ACB 400 C1 or later,
to be ordered separately as accessory.
• 24 V ~ power supply; DIN rail mounting
1. APPLICATION
XTA 624 is designed for temperature control in air handling units composed of:
• 2 hot/chilled water or vapor batteries with 3-wire modulating control
or electric batteries with 1-,2-, or 3-stage On-Off control
or direct expansion batteries with 1- or 2-stage On-Off control
• 1 air mixing unit with 0...10 V– air damper actuators
or 1 heat recuperator with 0...10 V– or On-Off control (CSV 304 converter).
The equipment can be included in a Telemanagement system through the C-Bus connection.
2. OPERATION
The main features of XTA 624 are as follows:
• Two 3-wire modulating outputs or 2-stage On-Off (two equal loads) or 3-stage (two unequal loads) outputs,
configurable for:
– room temperature control (heating or cooling) with summer external compensation if desired, minimum
and maximum flow limits to prevent cold drafts.
– flow temperature control (heating or cooling) with winter and summer compensation if desired
– pre-heating temperature control at a fixed value
• One 0...10 V– progressive output, configurable for:
– air mixing control based on temperature comparison or with minimum external air limit
– heat recuperator On-Off control according to room-external temperature comparison
• 2 pump control On-Off outputs accoring to output load
• Manual seasonal switching from a display or an external switch.
• Remote-controlled temperature setting adjustment
• Alarms for short and open detector circuits and for system and equipment malfunction.
• Programming by means of 25 24-hour programs, five 7-day programs, and 25 annual period programs
• Enabled for data transmission via C-Bus with local PCs or remote Telemanagement PC.
• Optional C-Bus transmission of data with local PCs or remote Telemanagement PC.
To enable data transmission and Telemanagement use the "C-Bus Plug-in" type ACB 400 C1 or later
To communicate locally with a PC use the test Plug-in type ACX 232
3. ACCESSORIES
No.
Description
1
Duct flow air temperature detector
1
Duct outside air temperature detector
or
wall outside air temperature detector
1
Duct extract air temperature detector
or
room air temperature detector
1
Duct pre-heating temperature detector
1
Temperature set-point adjuster
1
Outside air minimum distance positioner
Accessory for Telemanagement
1
Plug-in for communicating via C-Bus
We reserve the right to make changes without notice
COSTER
E 136 - XTA 624 C1 Eng.
Type
Application range
0...60 °C
STA 010
STA 001
–30...+40 °C
SAE 001
–30...+40 °C
STA 010
0...40 °C
0...40 °C
SAB 010
0...40 °C
STA 010
CDB 100
± 5 °C
PCS 04
ACB 400 C1
22.11.10 AM REV. 02
Sensing
element
NTC 10 kΩ
NTC
1 kΩ
NTC
1 kΩ
NTC 10 kΩ
NTC 10 kΩ
NTC 10 kΩ
E 136
22.11.10 AM
REV. 02
Code
Data
sheet
B1
B2
B2
B3
B3
B4
Rt°
Rs
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the XTA 624 and is the answer not in the manual?

Questions and answers

Summary of Contents for Coster XTA 624

  • Page 1 • 24 V ~ power supply; DIN rail mounting 1. APPLICATION XTA 624 is designed for temperature control in air handling units composed of: • 2 hot/chilled water or vapor batteries with 3-wire modulating control or electric batteries with 1-,2-, or 3-stage On-Off control or direct expansion batteries with 1- or 2-stage On-Off control •...
  • Page 2: Technical Data

    COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 4. TECHNICAL DATA (default values in bold print) Preheating temperature (B4) 0…10…40 °C • Electrical data Power supply 24 V ~ ± 10% Temp. proportional band (base value): Frequency 50 …...
  • Page 3: Wiring Diagrams

    COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 7. WIRING DIAGRAMS 7.1 3-Wire Modulating Valve Control Y .. : M O D U L A T I N G R un T i m e : x x x s B1 –...
  • Page 4 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 9. WHERE TO PLACE DEVICES Controller The controller should be placed in a dry environment, in compliance with acceptable environment conditions as described under “Technical Data”. If located in environments classified as “hazardous” it should be installed in switchboards built in accordance with applicable regulations depending on hazard class.
  • Page 5 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 11. TEMPERATURE CONTROL – EXAMPLES Room temperature control B2 – Outside temp. detector (for compensation only) B3 – Room or extract temperature detector Rt° – Temperature set point adjuster (optional) D e t e c t o r s L a y o u t –...
  • Page 6 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 13. USE OF Y1, Y2 OUTPUT – EXAMPLES – 1 Preheating modulating battery – 1 Post-heating modulating battery – 1 Humidifying On-Off unit (controlled from outside the controller) B1 –...
  • Page 7 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 – 1 Winter heating modulating battery – 1 Summer cooling direct expansion On-Off battery – 1 Humidifying On-Off unit (controlled from outside the controller) B1 – Flow temperature detector B2 –...
  • Page 8: Operation

    22.11.10 AM REV. 02 14. OPERATION XTA 624 is a microprocessor-operated digital controller for temperature control in air handling units composed of: 2 units with 3-wire or 1, 2 or 3-stage On-Off modulating control. The units can have the following functions: Preheating; Heating; Cooling.
  • Page 9 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 Control through room detector (B3) only or discharge air detector (B1) only The controller compares the values if B3 is used H e a t . T . R o o m C o o l .
  • Page 10 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 Operating modes The controller can operate in the following modes: – ON Winter; OFF Winter C u r r e n t m o d e : – ON Summer; OFF Summer W i n t e r –...
  • Page 11 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 Summer compensation of desired room Cooling temperature This function can only be used if detectors B2 and B3 or B1, B2 and B3 are connected. It is useful S e a s o n S w i t c h i n g to prevent excessive temp.
  • Page 12 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 19. OUTPUT Ys Output Ys with 0...10 V– control signal can be used for: • AIR DAMPER TEMP. = Temp. comparison air damper control RECUPERATOR = Heat recuperator control Air damper control through temperature comparison Whenever actual outside temperature t°r exceeds the target...
  • Page 13 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 • Automatic season switching according to outside temp. (only if B2 is connected). S e a s o n S w i t c h i n g When outside temp.
  • Page 14 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 21. PROGRAMS & PERIODS WITH DATES XTU 614 can start and shut down the air handling sites using: – 25 24-hour programs – 5 7-day programs – 25 annual periods with dates...
  • Page 15: Complementary Functions

    COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 22. M1, M2 PUMP CONTROLS The controller controls M1 pump output depending on control output Y1 load, and M2 pump output depending on control output Y2 load: – Pump on with load over 0% D e l a y O f f M 1 : x x m –...
  • Page 16 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 24. ALARMS The controller processes two types of alarms: – alarms related to functional irregularities affecting the controller and the controlled systems (LED 6. – alarms related to short and open detector circuits (LED 6.
  • Page 17 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 26. SEQUENCE OF DISPLAY PAGES (the data and functions are those set at factory) S i t e - - - - - - - - - - - - C u r r e n t m o d e : H e a t T .
  • Page 18 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 M0. NORMAL USE Ref. Display Description Notes Sect. S i t e - - - - - - - - - - - - Site name. Set in M2.
  • Page 19 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 M1. TIME SETTINGS AND PERIODS Ref. Display Description Notes Sect. H o w m a n y d a i l y Selection of amount of 24-hour programs to be...
  • Page 20 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 M3. EQUIPMENT CONFIGURATION Ref. Display Description Notes Sect. D e t e c t o r s L a y o u t Configuration of connected detectors (outputs B-M) 1 : Flow temp.
  • Page 21 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 M4. TESTING Ref. Display Description Notes Sect O u t p u t : Y 1 M O D U L . Select outputs to be tested Output selection:...
  • Page 22 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 We reserve the right to make changes without notice...
  • Page 23 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 We reserve the right to make changes without notice...
  • Page 24 COSTER E 136 - XTA 624 C1 Eng. 22.11.10 AM REV. 02 Amendments to data sheet Data Revision No. Page Section Amendment description Firmware Software version version 01.09.09 VM Change to version C1 > 0.99.2650 New section 21. Programs & periods ...