Download Print this page
Pepperl+Fuchs 6500 Series Instruction Manual

Pepperl+Fuchs 6500 Series Instruction Manual

Purge and pressurization system

Advertisement

Quick Links

Instruction Manual
1. Marking
6500 series
Purge and pressurization system for Zone 1 or Zone 21
6500-01-****-***-*** control unit
EPV-6500-**-** relief vent
6500-MAN-DV-** manifold valve
ATEX approval and IECEx approval
Group, category, type of protection, temperature classification
The *-marked letters of the type code are placeholders for versions of the
device.
You will find the exact device designation on the nameplate.
Observe the specific conditions of use.
Pepperl+Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
2. Target Group, Personnel
Responsibility for planning, assembly, commissioning, operation,
maintenance, and dismounting lies with the plant operator.
The personnel must be appropriately trained and qualified in order to carry
out mounting, installation, commissioning, operation, maintenance, and
dismounting of the device. The trained and qualified personnel must have
read and understood the instruction manual.
Prior to using the product make yourself familiar with it. Read the
instruction manual carefully.
3. Reference to Further Documentation
Observe laws, standards, and directives applicable to the intended use
and the operating location.
The corresponding datasheets, manuals, declarations of conformity, EU-
type examination certificates, certificates, and control drawings if
applicable supplement this document. You can find this information under
www.pepperl-fuchs.com.
For more information see the manufacturer declaration.
If you use the device in safety-related applications, observe the
requirements for functional safety. You can find these requirements in the
functional safety documentation under www.pepperl-fuchs.com.
4. Intended Use
Observe the instruction manual and the certificate of the installed
apparatus.
Devices for which specific conditions of use apply have the X marking at
the end of the certificate number.
The device is only approved for appropriate and intended use. Ignoring
these instructions will void any warranty and absolve the manufacturer
from any liability.
Use the device only within the specified ambient and operating conditions.
The device is not a safety component according to the Machinery
Directive. Do not use the device to prevent personal injury.
If you use the device in safety-related applications, observe the
information for safety function and safe state.
5. Improper Use
Protection of the personnel and the plant is not ensured if the device is not
used according to its intended use.
6. Mounting and Installation
Prior to mounting, installation, and commissioning of the device you
should make yourself familiar with the device and carefully read the
instruction manual.
Observe the ambient and operating conditions when mounting and
installing the device.
If you intend to install the device or enclosure in areas that may be
exposed to aggressive substances, ensure that the stated surface
materials are compatible with these substances. If required, contact
Pepperl+Fuchs for further information.
Mount the device in a way that the device is protected against mechanical
hazard.
If you use the device in environments subject to adverse conditions, you
must protect the device accordingly.
Place warning marking "Warning – Refer to instruction manuals!" visibly on
the surrounding enclosure.
Protect pneumatic components against mechanical hazard.
Ensure that the overpressure in the cabinet does not exceed the
permissible peak value.
If you install the device in safety-related applications, observe the
requirements for functional safety.
DOCT-B2W9 / 2021-05
Observe the tightening torque of the screws.
When connecting intrinsically safe devices with intrinsically safe circuits of
associated apparatus, observe the maximum peak values with regard to
explosion protection (verification of intrinsic safety). Observe the
standards IEC/EN 60079-14 or IEC/EN 60079-25.
For intrinsically safe circuits, the dielectric strength of the insulation against
other intrinsically safe circuits and against the shield must be
at least 500 V according to IEC/EN 60079-14.
Safety-relevant markings are found on the nameplate supplied. Ensure
that the nameplate is present and legible. Take the ambient conditions into
account.
The device is heavy. In order to avoid personal injuries or property
damage, make appropriate provisions for the mounting procedure.
When installing additional components, make sure that these components
are listed in the relevant certificates.
Select suitable conductors in order to ensure that the maximum permitted
temperature of the conductors fit to the maximum permitted ambient
temperature of the terminal box.
For control panels with IECEx certification, only use cable glands with
metric thread or NPT thread.
Requirements for Cable Glands
Observe the tightening torque of the cable glands.
Only use cable glands that are suitably certified for the application.
Only use stopping plugs that are suitably certified for the application.
Only use cable glands with a temperature range appropriate to the
application.
Protect plastic cable glands against mechanical hazard.
Ensure that the degree of protection is not violated by the cable glands
and the stopping plugs.
Requirements for Cables and Connection Lines
Only use cables and connection lines with a temperature range
appropriate to the application.
Install cables and cable glands in a way that they are not exposed to
mechanical hazards.
Observe the permissible core cross section of the conductor.
The insulation stripping length must be considered.
Requirements for Non-Hazardous Area
The device may be installed in the non-hazardous area.
Requirements for Hazardous Area
The enclosure has a ground connection. Connect an equipotential
bonding conductor with a minimum cross section of 4 mm
connection.
Observe the installation instructions according to IEC/EN 60079-14.
Observe the installation instructions according to IEC/EN 60079-25.
Only remove the cover in the absence of a potentially explosive
atmosphere.
Requirements in Relation to Intrinsic Safety
Observe the respective peak values of the field device and the associated
apparatus with regard to explosion protection when connecting intrinsically
safe field devices with intrinsically safe circuits of associated apparatus
(verification of intrinsic safety). Also observe IEC/EN 60079-14 and
IEC/EN 60079-25.
Keep the separation distances between all non-intrinsically safe circuits
and intrinsically safe circuits according to IEC/EN 60079-14.
Requirements for Surrounding Enclosures
The housing must not be opened when the device is energized.
Do not install fuse terminals, relays, miniature circuit breakers, contactors
etc. in the enclosure.
When the enclosure cover is fitted, ensure that all fasteners are fully
tightened.
7. Operation, Maintenance, Repair
Prior to using the product make yourself familiar with it. Read the
instruction manual carefully.
Do not remove the nameplate.
Observe the warning markings.
Do not connect or disconnect the electrical connection when energized.
Do not exceed the maximum permitted output current. Prevent short
circuits.
Do not exceed the maximum power dissipation. Refer to nameplate for
maximum power dissipation.
Observe IEC/EN 60079-17 for maintenance and inspection.
If there is a defect, always send back the device to Pepperl+Fuchs.
When energized, only open the housing in the absence of a potentially
explosive atmosphere.
Substitution of components may impair intrinsic safety.
Remove all adhering residues from the device. These residues can be
hazardous to health.
Fill in the form "Declaration of Contamination". You can find this form on
the product detail page at www.pepperl-fuchs.com.
1 / 2
2
to this ground

Advertisement

loading

Summary of Contents for Pepperl+Fuchs 6500 Series

  • Page 1 Observe IEC/EN 60079-17 for maintenance and inspection. hazard. If there is a defect, always send back the device to Pepperl+Fuchs. If you use the device in environments subject to adverse conditions, you When energized, only open the housing in the absence of a potentially must protect the device accordingly.
  • Page 2 If you operate the device in safety-related applications, observe the requirements for functional safety. In case of operating in low demand mode, plan appropriate intervals for the proof test. Remove the dust before opening the housing. 8. Delivery, Transport, Disposal Check the packaging and contents for damage.