Qualified Refrigerants; Lubrication - Emerson Copeland Scroll ZH 15 K4E Application Manuallines

Scroll compressors for dedicated heat pumps
Table of Contents

Advertisement

5

Qualified Refrigerants

R407C has been qualified for the compressor models ZH 15 K4E ... ZH 45 K4E.
6

Lubrication

The compressor is supplied with an initial charge of polyolester (POE) lubricant. In the field the oil level could be
topped up with Mobil EAL Arctic 22 CC. The recharge values can be taken from Copeland Selection Software.
Although there is no flexible mounting of the internal compressor parts, the number of start/stop cycles should be
limited to 10 per hour. A high cycling rate will pump oil into the system and may lead to lubrication failure. Oil leaves
the compressor at start-up regardless of the low oil carry over of the Copeland Scroll. The short running time is
insufficient to return the oil to the compressor and possibly results in a lack of lubricant.
It must be considered that the entire system will be coated with oil to some extent. Oil viscosity changes with
temperature. System gas velocity changes depending on temperature and load. In low load conditions gas velocity
may not be high enough to return oil to the compressor. System piping should be designed to return oil under all
operating conditions.
One characteristic of POE is that it is far more hygroscopic than mineral oil (Figure 3). Only brief exposure to ambient
air is needed for POE to absorb sufficient moisture to make it unacceptable for use in a refrigeration system. Since
POE retains moisture chemically it is not possible to completely remove it through the use of vacuum.
Compressors supplied by Copeland contain oil with a low moisture content, and this may rise during the system
assembling process. Therefore it is recommended that a properly sized filter-drier is installed in all POE systems. This
will maintain the moisture level in the oil to less than 50 ppm. If oil is charged into a system it is recommended to
charge systems with POE containing no more than 50 ppm moisture content. If the moisture content of the oil in a
refrigeration system reaches unacceptable high levels, corrosion and copper plating may occur.
The system should be evacuated down to 0.3 mbar or lower. If there is uncertainty, as to the moisture content in the
system, an oil sample should be taken and tested for moisture. Sight glass/moisture indicators currently available can
be used with the HFC refrigerants and lubricants; however, the moisture indicator will just show the moisture contents
of the refrigerant. The actual moisture level of POE would be higher than the sight glass specifies. This is a result of
the high hygroscopicity of the POE oil. Oil samples would have to be taken from the system and analyzed to
determine the actual moisture content of the lubricant.
C6.2.9/0203-1004/E
For proper lubrication the minimum differential between bottom shell
(tb) and evaporating (te) temperatures should be carefully observed
as laid out in Figure 2. On the other hand, the maximum bottom shell
temperature should never exceed 93°C, measured close to the bottom
center of the compressor.
Figure 2: Minimum bottom shell temperature (tb)
4