4.2.3
Navigation in the main menu
Fig. 5: ESM programmier controls
> Use the "Arrow up" and the "Arrow down" buttons to navigate to the required
option, or to change between options.
> Activate the option with the "Select" button.
4.2.4
Options
-Change speed 1
Speed 1 is the speed at which the fan operates when the 3rd (brown) lead is not
connected.
When this option is selected with the „Select" button, the currently programmed
speed is displayed (in rpm).
This speed can be adjusted in steps of 100 rpm.
> Set the required speed with the "Arrow right" and "Arrow left" buttons.
During programming, ensure compliance with the speed limit values
stated in the product documentation for the fan.
> Confirm this value with the "Select" button.
The fan is programmed within the space of a few seconds.
After successful programming, the message "PROGRAMMING COMPLETE" appears.
In the event of a communications error, an error message will be displayed.
As a rule, this will be caused by a poor connection between the fan and the ESM
programmer.
> Check the connection / plug and restart the procedure.
Change speed 2
Speed 2 is the speed at which the fan operates when the 3rd (brown) lead is con-
nected to L or N.
When this option is selected with the "Select" button, the currently programmed
speed is displayed (in rpm).
The programming procedure is the same as that for CHANGE SPEED 1.
Backlight
> Press the "Select" button to switch the backlighting on or off. The lighting
remains on until it is switched off again, also with the "Select" button.
Battery
> Press the "Select" button to read off the battery state.
When a measured value of 2.2 V is reached, the two 1.5 V AA alkaline batteries
must be changed. Higher values (in the range 2.3-3.3 V) are absolutely acceptable.
> Press the "Arrow up" and "Arrow down" buttons to return to the main menu.
Version
Shows the current software version.
Arrow buttons
Select button
4.2.5
Resetting ESM programmer
> Press the small white button on the top of the unit (see Figure 6) to reset the
ESM programmer.
Fig. 6: Resetting ESM programmer
4.2.6
Switching the unit off
> To switch the ESM programmer off, press the "On/Off" button and keep this
pressed until the message "ESM PROGRAMMER - POWER OFF" appears. The
display is then switched off.
If no button is pressed for 3 minutes, the unit will power down automatically.
4.3 Ending programming, starting fan operation
> Before you reconnect the power supply to the motor/fan, unplug the connector
cable and re-insert the cap.
NOTE
Sealing damage to the fan
The cap could be damaged and the fan is not sealed properly
> Replace the cap after programming.
> Turn the cap only for one-quater turn upon opening or closing.
4.4 Software upgrade
Should future software upgrades be necessary, a mini-USB connection is included
on the device (cable not included) for this purpose. The software would be made
available as a download to a personal computer which could then be uploaded to
the programmer.
Resetting program-
ming unit
Mini USB port for
uploading firmware
upgrades

Advertisement