Boiler electrical connection

Pumps with power consumption greater than 2 A or connection for HE pump

N
L
C
L
N
B
Fig. 27
Pump (on site)
A
To the control unit
B
Contactor (on site)
C
Separate power supply (observe manufacturer's
D
instructions)

Pumps 400 V~

L1 L2 L3 N PE
N
L
C
B
M
A
3~
Fig. 28
Pump (on site)
A
To the control unit
B
Contactor (on site)
C

External demand via switching contact

Connection options:
EA1 extension (accessory, see separate installation
instructions)
Plug
lH
When the contact is closed, burner operation is load-
dependent. The boiler water is heated to the set value
selected in parameter/coding address "9b" in the
"General"/1 group. The boiler water temperature is
limited by this set value and by the electronic maxi-
mum limit (coding address "06" in the "Boiler"/2
group).
24
(cont.)
D
L N
L
N PE
External
ON/OFF
A
For switching the contactor
Rated current
Recommended connecting
cable
!
Please note
Live contacts lead to short circuits or phase fail-
ure.
The external connection must be floating and
meet the requirements of protection class II.
4(2) A~
2
H05VV-F3G 0.75 mm
or
2
H05RN-F3G 0.75 mm