8. Turn off the system power.
9. Disconnect the connectors from the Ethernet and USB ports (#2,7 in the Diagram on
page 2).
10. Disconnect the UAC-01EC2 module from the adjacent units: slide its Bus Connector
Lock to the right. If there is a unit located on its right, slide the lock of this module to
the right as well.
11. On the UAC-01EC2 module, pull the top DIN-rail clip up and the bottom clip down.
12. Open the door of the UAC-01EC2 and hold it with two fingers as shown in the figure on
page 3; then pull it carefully from its place.
Wiring
 All wiring activities should be performed while power is OFF.
 Unused points should not be connected (unless otherwise specified). Ignoring
this directive may damage the device.
 Double-check all wiring before turning on the power supply.
Wiring Procedure
Functional ground terminal (
Use a wire of minimum thickness of 14 AWG (2 mm
crimp terminal, stud size #6.
Tighten the screw enough to make sure the ring/fork crimp terminal is not loose.

Wiring Guidelines

In order to ensure that the device will operate properly and to avoid electromagnetic
interference:
 Use a metal cabinet. Make sure the cabinet and its doors are properly earthed.
 Connect the functional ground terminal (
metal cabinet chassis).
 Individually connect each functional ground point (
(preferably to the metal cabinet chassis). Use the shortest and thickest wires possible:
less than 1m (3.3') in length, minimum thickness 14 AWG (2 mm
 Ensure shield continuity when extending shielded cables.
For detailed information, refer to the document System Wiring Guidelines, located in
N
OTE
the Technical Library in the Unitronics' website.
4
)
2
); terminate it with a ring or fork
) to the earth of the system (preferably to the
) to the earth of the system