Installation Instructions

Location
The preferred installation location for the Odorox® IDU™ unit is in the return duct as the air will be treated before
the filter and HVAC coil. If it is not possible to install in the return duct, it may be installed in the supply duct. If a
humidifier is present, the IDU should be installed in the air stream before the humidifier. Make sure the location
can be supplied with the necessary power requirements. The IDU™ unit has a power consumption of 96 watts
and requires a 120 / 220 volt, 50/60 Hz power source.
Note: The IDU™ unit is not waterproof. If installing outdoors, the IDU™ unit must be installed in a watertight enclosure.
The light/energy produced from the optics used in this product may
damage if direct exposure to certain plastics and exposed wires. If any
plastic or wires are within the light exposure area, wrap exposed plastic
with aluminum tape and cover wires with metal conduit.
Important Airflow Information:
direction (refer to the Air Flow directional arrows on the side of the reflection chamber). The IDU™ unit can be
installed vertically or horizontally, depending on the duct location.
Odorox® IDU
Installation
TM
STEP 1: Remove the IDU™ unit from its packaging.
STEP 2: Remove the optics from the packaging material. The optics are fragile, use extreme care. Do not touch
the glass on the optic with bare hands. Handle the optic from the ceramic ends.
STEP 3: Position the optics inside the aluminum chamber. The side of the optic containing the four-pronged
connector must be pushed into the two optic clamps (use caution to ensure the two small white wires do
not get pinched by the clamp). The curved portion of the optic must get pushed into the remaining third
optic clamp.
STEP 4: Connect the wire harness to the optic connector. The wire harness fits in one direction only. If the wire
harness will not connect to the optic, turn the harness 180 degrees.
STEP 5: Remove paper backing from foam gasket on the back of the IDU™ unit and from the duct reinforcement
plate (IDU02MD130).
The Odorox® IDU™ unit must be installed in the air stream in the proper