Download Print this page

Zencontrol zc-iot-fc Quick Start Manual

Advertisement

Quick Links

Wireless application controller zc-iot-fc
Product range
Order code
Description
zc-iot-fc
Wireless field mounted application controller
Specifications
Supply voltage
220 - 240 V ~ 50 Hz
Control system
IEC62386-104 over Thread
Radio support
IEEE 802.15.4
Frequency band
2.4 GHz
Max radio tx power
+8 dBm
Ethernet
10/100 TCP/IP Ethernet
Wiring
1 - 4 mm
Strip 6 - 7 mm
Operating temperature 0 to 55°C
Material
PC
Classification
Class II
Ingress protection
IP20
Wireless system overview
Wireless switch
IEC 62386-301
IEC 62386-104
over Thread
Wireless sensor
IEC 62386-303
IEC 62386-304
IEC 62386-101
zc-iot-bridge
IEC 62386-103
2
Wireless driver
IEC 62386-207
To
Wireless DT8 driver
zencontrol
IEC 62386-209
Cloud
zc-iot-fc
IEC 62386-103
D4i driver
Dimensions
Mounting options
Field mount
Fixing centres
195 mm
Dimensions
206 / 42 / 30 mm
206
Safety information
■ This product must only be installed by a licensed electrician.
■ Before commencing installation turn off and isolate the
electrical supply.
■ There are no user serviceable parts, attempting to service any
part of the product will void the warranty
■ DALI is not SELV and as such should be treated as LV.
■ As the installer, it is your responsibility to ensure you comply
to all relevant building and safety codes. Refer to application
standards for the relevant rules.
■ When the installation is complete, leave this manual with the
building's owner for future reference.
Installation
Remove the product from the box and inspect it for any damage. If you
believe the product to be damaged or otherwise unsound, do not install
the product. Please pack it back into its box and return it to the place of
purchase for replacement.
If the product is satisfactory, proceed with the installation:
1 Ensure safety warnings are adhered to.
2 Remove the end-covers by unscrewing the four fasteners to access
the mounting centres and terminals per fig 2.
3 Mount the application controller using the allocated mounting
centres, as per the above dimensions. Avoid mounting on metal
surfaces, as this will prevent the radio communication.
4 Wire as per fig 4 overleaf.
5 Reattach end-covers, ensuring adequate strain relief
To ensure adequate radio communication
DO NOT install device in a metal enclosure
Fastener
Cover
2
42
30
RJ45

Advertisement

loading

Summary of Contents for Zencontrol zc-iot-fc

  • Page 1 Wireless application controller zc-iot-fc Dimensions Mounting options Field mount Fixing centres 195 mm Dimensions 206 / 42 / 30 mm Product range Safety information Order code Description ■ This product must only be installed by a licensed electrician. zc-iot-fc Wireless field mounted application controller ■...
  • Page 2 5 second press Toggles identify function Reset 1 - 2 seconds press Force Cloud reconnect Reset 3 - 10 second press Reboot Reset 11 - 15 second press Factory reset Indicators LEDs Buttons Reset On /Off Ethernet zencontrol.com © zencontrol...