13.4.8.2. Constant speed mode vs capacity
The speed of the pump depends on the capacity of the unit. This speed range is determined during commissioning to adjust
the power of the pump to the load drops of the installation.
Speed set-point
100%
Mod. pump
max speed
Mod. pump
min speed
Mod. pump
standby speed
0%
Step 1
Setting
Mod. pump max speed
Mod. pump min speed
Mod. pump standby speed
Capacity for max speed
13.4.8.3. Constant output pressure mode
The controller manages the pump's speed to maintain an even water pressure at the output of the unit, regardless of the
number of operating terminals.
The hydraulic facility must include a system that retains the required minimum water pressure when the
CAUTION
terminals' two-way valves are shut.
FCU 1
FCU 2
FCU 3
FCU n
Installation of one or more three-way valves on the facility to maintain the minimum required pressure.
Capacity for
100%
max speed
Capacity
Default
Min.
Max.
100%
0%
100%
70%
0%
100%
60%
0%
100%
100%
0%
100%
Pump configuration
Pump configuration
Pump
Pump
Continuous pump
Continuous pump
Modulation
Modulation
Acceleration delay
Acceleration delay
--------------------------
--------------------------
---------------
---------------
Anti seizing act.
Anti seizing act.
Anti-seizing frequency
Anti-seizing frequency
Anti-seizing duration
Anti-seizing duration
--------------------------
--------------------------
---------------
---------------
Mod. pump max speed
Mod. pump max speed
Mod. pump min speed
Mod. pump min speed
Mod. pump standby speed
Mod. pump standby speed
Capacity for max speed
Capacity for max speed
EWC
LWC
34
1/13
1/13
Single
Single
Off
Off
2 stages
2 stages
10 s
10 s
Active
Active
72h
72h
120s
120s
80,0%
80,0%
40,0%
40,0%
20,0%
20,0%
100,0%
100,0%
VE
WP
PHE
Hz
FDWP
WPT