Fault Diagnosis - rada Pulse Product Manual

Electronic control box
Table of Contents

Advertisement

Symptom
1. All outlets do not
operate
(e.g. washbasin,
shower, urinal,
W.C).
2. Individual outlets
do not operate.
3. Outlets continue
running or run for
e x c e s s i v e
periods
4. Outlets only run
for a short period
of time.
prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556

FAULT DIAGNOSIS

Cause/Rectification
a. Check power to Pulse control box (power light illuminated
on PCB).
b. If there is power to the control box, check fuse in
transformer.
a. Check output fuse on PCB. Replace as necessary.
b. Plug in hand held controller and check that non operating
outlet is set up correctly.
c. Plug in hand held controller and complete a system info
'error' check. This will identify if the sensor or solenoid
is incorrectly installed or faulty. Replace parts or products
as required.
d. Check solenoid. Replace if necessary.
a. Plug in hand held programmer and check timing for
outlet. Reprogram if necessary.
b. Check solenoid valve. Maintain or replace parts if
required.
a. Plug in hand held programmer and check timing for
outlet. Reprogram if necessary.
9

Advertisement

Table of Contents
loading

Table of Contents