Download Print this page

Circulating Pumps CP50 Installation And Operating Instructions Manual page 9

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
2 Technical data
2.1
Data
Connection voltage
Temperature class
Protection class IP
Energy Efficiency Index EEI *
Nominal connection diameter
(threaded connection)
Water temperatures at max. ambi-
ent temperature of +40 °C
Max. ambient temperature
Max. operating pressure
Minimum inlet pressure at +95 °C
* Reference value for the most efficient circulation pumps: EEI ≤ 0.20
2.2
Scope of delivery
• Pump
• Sealing rings
• Plug included
• Installation and operating instructions
3 Description and function
3.1
Intended use
The circulation pumps in this series are designed for warm
water heating systems and similar systems with constantly
changing flow volumes. Approved fluids are heating water
in accordance with VDI 2035, water/glycol mixture at a mix-
ing ratio of 1:1. If glycol is added, the delivery data of the
pump must be corrected according to the higher viscosity,
depending on the mixing ratio percentage.
Installation and operating instructions
CP50, CP60
1 ~ 230 V ±10%, 50/60 Hz
TF 95
See rating plate
See rating plate
DN 25 (Rp 1)
–10 °C to +95 °C
–10 °C to +40 °C
6 bar (600 kPa)
0.3 bar (30 kPa)
English
5

Advertisement

loading

This manual is also suitable for:

Cp60