Mitsubishi Electric CITY MULTI CMY-R100NCBK Installation Manual page 3

Advertisement

PURY-(E)P264 to (E)P336
Set model
Set Unit
Twinning type
Twinning pipe - BC Controller
Twinning pipe - BC Controller
Twinning pipe - Outdoor unit
(2) Slope of twinning pipes
Make sure the slope of the twinning pipes are at an angle
within ±15˚ to the horizontal plane.
If the slope exceeds the specified angle, the unit may be
damaged.
(3) The length of the straight pipe between indoor units and the twinning pipe
Use the pipes supplied in the twinning kit, and make sure the section of the field-supplied pipe that connects to the twinning pipe has
at least 500 mm [19-11/16 in] of straight section. (The section of the field-supplied pipe that connects to the twinning pipe must have
at least 500 mm [19-11/16 in] of straight section.) If the straight section is less than 500 mm [19-11/16 in], it may result in equipment
damage.
(4) Pipe connection
• Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards.
Unit 1
100 mm
A
[3-15/16 in]
Downward slope
max
Twinning pipe
Total pipe length = A + B < 5 m [16-7/16 ft]
• If twinning pipe is installed above the base of the outdoor unit,
it should be no more than 200 mm [7-7/8 in].
• If the length of the pipe between the branching point and the outdoor unit exceeds 2 m (6 ft), provide a trap within 2 m (6 ft) from the
branching point.
The trap must be at least 200 mm (7-7/8 in) in height. (low-pressure pipe only) If there is no trap, oil can accumulate inside the pipe,
causing a shortage of oil and may damage the compressor.
* Small dots in the figures indicate branching points.
2 m (6 ft)
PURY-(E)P264
Unit 1
PURY-(E)P144
Unit 2
PURY-(E)P120
High-pressure
a
Low-pressure
b
Unit model
High-pressure
PURY-HP72
ø15.88 [5/8]
PURY-HP/(E)P96
ø19.05 [3/4]
PURY-HP/(E)P120
ø19.05 [3/4]
PURY-(E)P144
ø22.2 [7/8]
PURY-(E)P168
ø22.2 [7/8]
Unit 2
Unit 1
B
To BC controller
≤ 2 m (6 ft)
PURY-(E)P288
PURY-(E)P144
PURY-(E)P144
ø34.93 [1-3/8]
Low-pressure
ø19.05 [3/4]
ø22.2 [7/8]
ø28.58 [1-1/8]
ø28.58 [1-1/8]
ø28.58 [1-1/8]
Slope of the twinning pipe is at an angle within ±15° to the horizontal plane.
Unit 2
To BC controller
Upward slope
200 mm
[7-7/8 in]
max
Ⓐ To indoor units
Ⓑ Trap (low-pressure pipe only)
Ⓒ High-pressure pipe
3
PURY-(E)P312
PURY-(E)P168
PURY-(E)P144
CMY-R300NCBK
ø28.58 [1-1/8]
ø41.28 [1-5/8]
Twinning pipe
Unit 1
PURY-(E)P336
PURY-(E)P168
PURY-(E)P168
Unit 2
Twinning pipe
To
BC controller