Download Print this page

DANLERS DBPSU Installation Notes

Dali / dsi power supply unit

Advertisement

Quick Links

Circuit Diagram
L
N
DALI / DSI
DBPSU
Ballast
DALI Control Lines
DANLERS
DALI / DSI Device
Wiring connections
L
DBPSU
L
DALI / DSI Power Supply Unit
Input: 100-230V. 50/60Hz
Output power supply:
40mA (20 ballasts)
N
t
: 0°C ...50°C
amb
N
DANLERS Limited
www.danlers.co.uk-
Made in UK
Precautions and Warranty
This product conforms to EN 60598-1 and DALI standard IEC 60929 (DALI VO) and IEC
62386 (DALI V1).
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided (protected with the appropriate MCB) 1kV over voltage.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: sales@danlers.co.uk
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
05/09/16
DALI / DSI
Ballast
To control more than 20 ballasts (64
max) additional DBPSU can be installed
in the middle of the system with cable
split into equal lengths to minimise
voltage drop. Polarity sensitive when
installing multiple DBPSU.
DA1
-DA
DALI/
DSI
+
Status
DA
DA2
INS007 DBPSU
DALI / DSI Power Supply Unit
DBPSU
DALI / DSI Power Supply Unit (DBPSU) is designed for use with
DANLERS DALI or DSI dimmable devices.
The DALI / DSI Power Supply Unit is rated at 40mA (DALI standard
allows 250mA maximum). The controls interface of a DALI ballast
normally sources at 2mA.
Individual DALI / DSI circuits must not exceed 40mA.
Standard 2-core mains cable of minimum guage 1.5mm
recommended.
The maximum cable length of the DALI / DSI signal wires must not
exceed 300m or drop more than 2V on the signal line voltage.
To minimise voltage drop on the cable, the DBPSU can be installed
at the middle of the system so the cable is split into 2 equal lengths.
Technical Data
Supply Voltage:
120-240V
Supply Frequency:
50/60Hz
Supply Load:
4W maximum
Output:
DALI / DSI
Output Current:
40mA
Output Voltage
Load Off:
18V maximum
Ambient temperature:
0-50 ºC maximum permitted.
Glow wire test: According to EN 60598-1 passed.
DALI standard: DALIPS is designed to supply control gear with DALI standard IEC 60929
(DALI VO) and IEC 62386 (DALI V1).
Installation notes
is
2

Advertisement

loading

Summary of Contents for DANLERS DBPSU

  • Page 1 DALI / DSI DBPSU Ballast Ballast DALI / DSI Power Supply Unit (DBPSU) is designed for use with DANLERS DALI or DSI dimmable devices. DALI Control Lines The DALI / DSI Power Supply Unit is rated at 40mA (DALI standard allows 250mA maximum).
  • Page 2 DALI / DSI DBPSU Ballast Ballast DALI / DSI Power Supply Unit (DBPSU) is designed for use with DANLERS DALI or DSI dimmable devices. DALI Control Lines The DALI / DSI Power Supply Unit is rated at 40mA (DALI standard allows 250mA maximum).