DiP 3
Reserved for custom functions
DiP 4
DiP 5
DiP 6
DiP 7
DiP 8
With DIP switch 8 in the ON position, the actuator will move to 4 positions. When switch 8 is off, the
actuator is limited to three positions. Switch 8 also changes the function of the output signals.
DiP 9
Run / Calibrate
Putting DIP switch 9 into the off position will disable the actuator positioning control, and the motor
will not move regardless of the input signals.
When DIP 9 is moved back into the on position, the actuator will perform it's homing routine, and then
move to the position commanded by the input signals.
DiP 10
DiP 11
Off
Off
Off
On
On
Off
On
On
DiP 10
DiP 11
Off
Off
Off
On
On
Off
On
On
DiP 12
DiP 12 sets the direction of rotation
Functionality of the RDx-B-xxxDT:
The RDx can operate as a 3-position or 4-position actuator. The 4
3-pos Functionality (Dip 8 OFF)
Input#1
Input#2
(Pin 1)
(Pin 2)
High
High
Low
High
High
Low
Low
Low
The feedback from the RDx-B-xxxDT is as follows:
Output#1
Output#2
(Pin 3)
(Pin 4)
High
High
High
Low
Low
High
Low
Low
Page 4 of 8
Rev. 1 2019
Description
Low torque
Medium-low
Medium-high
High torque
Approximate stall torque
RDL
40 in-lbs
120 in-lbs
53 in-lbs
160 in-lbs
60 in-lbs
180 in-lbs
65 in-lbs
195 in-lbs
Action taken
Moves to or remains in center position
Moves to or remains in right position
Moves to or remains in left position
Moves to or remains in right position (Input#1 has precedence
Meaning High = 4.5vDC Low = 0.8vDC
Actuator output is in center position
In Right position
In Left position
Actuator is moving, or has stalled and given up trying to reach
a requested position.
You may retry to reach any position again by setting Input#1
and Input#2. I.E.: toggle Input #1 low for a few milliseconds
and back to high if this was what you were asking for initially.
If the problem persists, you have to trouble shoot the unit.
User Manual RDx-B-xxxDT-10.31 Battery Fail Safe
0.75A
1A
2A
3A
RDM
RDH
405 in-lbs
540 in-lbs
608 in-lbs
657 in-lbs
th
position is enabled by turning Dip 8 ON.
over Input #2)
Approximate stall current
RDF
756 in-lbs
3348 in-lbs
1008 in-lbs
4464 in-lbs
1134 in-lbs
5022 in-lbs
1241 in-lbs
5440 in-lbs
Top View
onto valve or
Left
appliance
www.hanbayinc.com
1 800 315 4461
hanbaysales@hanbayinc.com
RDU
Right
other