paasche F910-2 Operating Instructions & Replacement Parts page 2

Automatic humidifier unit (2 spray heads)

Advertisement

1. Mount Humidifier Unit in convenient location using
Mounting Bracket (not shown).
2. Connect air supply to HF-1/4" Air Inlet Valve.
3. Connect water supply to HF-1/4" Water Inlet Valve.
4. Open air inlet valve and water supply valve under air
supply valve check for leaks. Tighten connections if
required.
5. Turn humidistat control dial on item #1 counter-
clockwise to off position before plugging cord into
grounded outlet.
6. Reduce water flow by turning U-3670 needle stop
adjustment knob at back of spray gun. Do not use to
shut off spray. If tightened too much needle can be
pushed through tip.
7. Set Regulator item #2, between 45 & 60. Start at 45 PSI
and increase until you get a nice atomization. Shop air
must be 80 PSI or higher.
8. Plug unit into properly grounded Outlet (115V., 60cy).
9. Turn Humidistat control dial to on position and desired
humidity. You will hear a "click" when activated.
10. Water flow rate may be adjusted using Item #13 for
Fluid Adjusting on back of each Spray Gun. Mist
should always be absorbed into the surrounding
air without settling out onto the floor under the unit.
CAUTION:
DO NOT AIM DIRECTLY AT CEILING,
WALL, MERCHANDISE OR MACHINERY.
SAFETY NOTE:
Do Not allow water vapor to
condense or leaks to drip onto floor or unit, if this
condition exists, check for:
a. Water leaks from connections or Spray Gun nozzles.
b. Insufficient atomization. Correct by increasing air
pressure and/or decreasing fluid flow.
c. Humidistat setting too high. Lower setting if necessary.
d. Open drain valve on R-76 Regulator/Condenser item #2
periodically to drain airline moisture buildup.
CAUTION:
Guard Face and Eyes so escaping air and
moisture do not cause injury.
WARNING:
Humidifier must never be used to create
a fog condition in which water may collect on the unit
and produce an electrical hazard.
No.
Part No.
Description
1.
AR-15-1
Aircap
2.
AU-12
Aircap Nut
3.
AU-1
Fluid Tip
4.
A-AU-2-29/32
Needle
5.
AU-7B
Fluid Body
6.
U-3632
Small O-ring
7.
U-3633
Large O-ring
8.
U-3045
Cylinder Shell
9.
U-3664
PTFE Piston Assembly
1
2
3
F900
PAASCHE
- Series Automatic Humidifier
HUMIDIFIER INSTALLATION
4
5
4
16
6
7
F910-2 UNIT
2
6
3
5
7
9
MAJOR COMPONENTS FOR F900-SERIES HUMIDIFIERS
No.
Part No.
1.
845
2.
R-76
3.
AH-JUR-1
4.
T-04-10
5.
F9-90-1/8
6.
F9-90-1/4
7.
1/4 AHPP
8.
F9-1-1/4
9.
T-04-4.5
10.
SM-880
11.
HF-1/4
10.
U-2500
11.
U-3669
12.
H-153
13.
U-3670
14.
U-1432A
15.
U-1399
16.
U-3687
8
10
Needle Lock
9
14
15
10
Located behind
Humidistat
Water Inlet
6
6
Located behind
regulator
Description
Humidistat
Regulator & Moisture Trap
2 Spray Gun Heads
Water Tubing (10 Inches)
Air Fitting to Regulator
Fitting to Mount 90° (3)
Pipe Plug
Fluid Inlet
AirTubing (4 1/2 Inches)
Solenoid Valve
Valve Assembly (1)Water & (1) Air
Piston Spring
Rear Cap
Set Screw
Needle Stop Adjustment Knob
Ball Stud
Swivel Nut
Packing Set
11
12 13
Do Not Use as a Shutoff by
turning all the way Down, It will
split the Tip.
Screw
1
Air Inlet
11
8