Hitachi Primairy Series Installation & Maintenance Manual page 21

Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS
Electrical wiring diagram
Model (capacity)
Power supply
3.0/3.5HP
220-240V ~, 50Hz
4.0HP
220-240V ~, 50Hz
5.0/6.0/6.5HP
380-415V 3N ~, 50Hz
Max. Running Current (A): REFER TO NAMEPLATE
NOTE:
1 Follow local codes and regulations when selecting field wires, and all the above are the minimum wire size.
2 Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord. (Cord designation H07RN-F).
3 The wire sizes marked with *1 in the above table are selected at the maximum current of the unit according to the European
Standard, EN60335-1.
4 When transmission cable length is more than 15 meters, a larger wire size should be selected.
5 Install main switch and ELB for each system separately. Select the high response type ELB that is acted within 0.1second.
6 In the case that power cables are connected in series, add each unit maximum current and select wires below.
1 When connecting the terminal block using stranded
wire, make sure to use the round crimp-style terminal for
connection to the power supply terminal block. Place the
round crimp-style terminals on the wires up to the covered
part and secure them in place.
2 When connecting the terminal block using a single core wire,
be sure to perform curing.
17
HO2019292HA
ELB
Rated current (A)
25
40
32
Selection According to EN60335-1
Current i (A)
i≤6
6<i≤10
10<i≤16
16<i≤25
25<i≤32
32<i≤40
40<i≤63
63<i
*2: In the case that current exceeds 63A, do not connect cables in series.
<Attentions when Connecting the Power Supply Wiring>
Power source
cable size
Nominal sensitive
EN60335-1*1
current (mA)
30
3x2.5mm
30
3x4.0mm
30
5x2.5mm
Wire Size (mm
0.75
1
1.5
2.5
4
6
10
*2
Round crimp-
style terminal
Transmission
cable size
Circuit breaker
EN60335-1*1
4x1.5mm
2
2
4x1.5mm
2
2
4x1.5mm
2
2
)
2
Covered part
Stranded wire
Terminal
Single core wire
(A)
25
40
32