Page 1
English construction B35 hollow shaft design Configuration manual electronic overspeed switch ® ® (H)41 certificated according IEC 61508 SIL2 and DIN EN ISO 13849-1 PL d Read the configuration manual prior to assembly, starting installation and handling! Keep for future using! Translation of the original configuration manual issued November 2018 ID 74513...
Page 2
Configuration manual EGS(H)41 Trademark ® is a registered trademark of Johannes Hübner Fabrik elektrischer Maschinen GmbH. ® Windows is a registered trademark of Microsoft Corporation in the United States and other countries. Protected trademarks bearing a ™ or ® symbol are not always depicted as such in the manual. However, the statutory rights of the respective owners remain unaffected.
Configuration manual EGS(H)41 This document tells you how to adjust the program settings for EGS(H) 41 with the EGS41Pro soft- ware and transfer them to the device. PLEASE NOTE! The documentation and the dimensional drawings will be copied in the installation folder in PDF format by the installation.
Configuration manual EGS(H)41 1.3 Installing the software Ensure the EGS(H) 41 device and your notebook/PC are connected via the USB cable. Close the automatically started „Found new hardware wizard“ with a click on “Cancel“. Place the supplied CD containing the software into the CD drive or, alternatively, download the Set- up.exe.
Configuration manual EGS(H)41 1.4 Installing the driver manually PLEASE NOTE! You must log into a user account with administrator rights to install the software. Ensure all programs are closed. If it is necessary to install the driver manually, depending on your operating system, please check the following steps.
Page 8
Configuration manual EGS(H)41 Newer Windows versions: Now select the installation source via “Browse” and point to path of your installation, there select the folder drivers. The Installation begins with a click on Next. The following illustrations are for Windows XP Sp3 and newer Windows versions. Windows XP Sp3: Newer Windows versions: Click Next, the installation of the driver software for this device has been completed.
Configuration manual EGS(H)41 2 Configuring In this chapter you will learn how to configure the EGS(H) 41 using the configuration software EGS41Pro. For the purpose of clarity the user interface is divided up into different sections. The drawing below offers a schematic overview: ...
Configuration manual EGS(H)41 2.2 Configuration planning table PLEASE NOTE! A configuration planning table is provided below. Use a printout or a copy of the planning table below to plan the configuration of the EGS(H) 41. Parameter Factory setting New value User device designation Inverse speed alignment Not active...
Switch on the power supply to your EGS(H) 41. To launch the software EGS41Pro click 'Start \ Programs \ HUEBNER –GIESSEN \ EGS 41. When launching the software for the first time a window is displayed containing the licensing agree- ment.
Configuration manual EGS(H)41 The individual functions on the “Home screen” are described in more detail in Chapter 3.1. To establish a connection to the EGS(H) 41 proceed as follows: On the Home screen click the 'Establish connection' button. Communications have been successfully established when the communication status symbol rotates. You can now begin to configure the device.
Configuration manual EGS(H)41 3.2 Information section Information from the connected EGS(H)41 is displayed in the information section. The previously mentioned dynamic indicator symbolizing the communication status between the PC and the EGS(H)41 is displayed in the middle. Each successfully transmitted or received data packet causes the partial ring to rotate.
Configuration manual EGS(H)41 The reason why the switch symbol is highlighted red is because the switch is either defective or not connected correctly. The number of hours [h] in operation and the PCB temperature of the connected device is displayed below the switch symbol. When a switch is inactive it appears dimmed.
Configuration manual EGS(H)41 Changes are made to the settings of the EGS(H)41 on the pages Parameters 1 and Parameters 2. On the Operating data page you are able to view a collation of all of the device settings and print these out for documentation purposes.
Page 16
Configuration manual EGS(H)41 CAUTION! When switch delay is activated the actual switch-off speed is higher than the set switch- off speed! Observe also information on determining the switching deviation described in the Operat- ing and Assembly instruction EGS(H)41! After making changes to the switching speed settings click the 'Check input' button to check the new settings do not violate restrictions.
Page 17
Configuration manual EGS(H)41 You will again be required by a security prompt to verify and confirm your changes. Click the 'Confirm' button to confirm the changes you have undertaken and store these permanently in the connected device. To reject the changes click the 'Reject' button. The data in the temporary memory will be deleted.
Configuration manual EGS(H)41 4.1 Inverse rotation evaluation Clockwise rotation for the switches S1R and S2R is defined as anti-clockwise rotation when viewing the end of the shaft of the EGS(H)41. When inverse rotation evaluation is activated the allocations for S1R and S1L are inverted. 4.2 Underspeed Underspeed is detected.
Configuration manual EGS(H)41 5 Parameters 2 On this page the settings are made that define the safety-relevant characteristics of theEGS(H)41. 5.1 Broken wire detection Broken wire detection is available for the switching outputs S1 and S2. Detection is triggered as soon as the internal load current monitoring measures less than 5 mA when a switch is closed.
Configuration manual EGS(H)41 PLEASE NOTE The password on delivery of EGS(H) 41 is “huebner”. Please note that you must enter a new password to protect the configuration from unau- thorized changes! When the factory-set password is changed the padlock symbol at the top of the screen is displayed closed.
Configuration manual EGS(H)41 6 Monitoring screen These pages are available to all users, as they do not permit any changes to the device settings. Here you will find a graphic user interface based on the functions of an oscilloscope, for observation and analysis of EGS(H) 41's switching behaviour.
Configuration manual EGS(H)41 6.1 Functions Representation scaling: The input fields for entering values to adapt scaling are located on the right-hand side of the speed graphic. By entering the appropriate values in the 'Ymax' and 'Ymin' fields you can limit representations in the speed range.
Configuration manual EGS(H)41 7 Operating data Here you can see a summary overview of all settings for the connected EGS(H) 41. No settings can be adjusted here. The top section shows all major device settings and the parameters adjusted under “Parameter 2” with their current values.
Configuration manual EGS(H)41 8 Pulldown-Menu “file” With “Export” device data can be saved in the PC and with “Import” device data can be transferred from the PC to the device. 8.1 Save monitoring data “File Export Monitoring data” saves the recorded monitoring data (*.s41) in the PC. With “file ...
Configuration manual EGS(H)41 9 Pull-down-Menu “Settings” Here, system settings can be changed. 9.1 Reset Password Is an selected user password lost, you can request by telephone via the menu item “Reset Password” a reset code. With this code the device can be reset to “factory setting”. CAUTION! By the function “Reset Password”...
Configuration manual EGS(H)41 Boot loader firmware With the function “boot loader firmware” the device firmware can be replaced via the USB port. The boot loader is only available from version EGS41 1.07.00. To perform an update, you have to inform the manufacturer about the serial number of the device, an email address and recipient´s name.
Configuration manual EGS(H)41 11 Notes on configuration It is only possible to configure the device with a single password (user rights: administrator). The facto- ry-set administrator password is: huebner. For reasons of safety it is strongly advised that you create a user-defined password (max.
Page 29
Configuration manual EGS(H)41 12 Index Configuration planning table Notes on configuration Configuring Operating data Delayed overcurrent switch-off Diagnostics output Parameters 1 Directory Parameters 2 Display section Planning and configuration Error table Rotation direction dependent switching Establishing a connection and logging on Setting up Functions Slip angle detection...