General Information General Information Validity of these Instructions The devices correspond to the following directives and standards: • DIN EN 298: 2012 • DIN EN 60730-2-5: 2015 • DIN EN 746-2: 2011 • 2014/68/EU Pressure Equipment Directive • 2009/142/EG Gas Appliance Directive •...
Safety Safety For Your Safety The following symbols are used in this document to draw the user's attention to important safe- ty information. They are located at points where the information is required. It is essential that the safety information is observed and followed, and that applies particularly to the warnings. DANGER! This draws the user's attention to imminent danger.
Product Description Product Description Design The compact flame scanner is composed of a cylindrical casing comprising an axial lightinci- dence aperture, a processing status indicator at the rear of the unit and operational controls which can be accessed by removing the cover. The device is connected through an integrated standard plug and using a connection cable required for this with coupler.
Page 7
For 60 Hz application, please indicate separately in your order form. The related stop ranges are changed in factory. LAMTEC offers a version without mains frequency suppression for special applications. This design requires additional measures during installation. Please contact LAMTEC Support for further information...
Technical Data Operating conditions Input parameters Auxiliary energy, input - Supply voltage 24 VDC ± 20%, protection class III 4 W, 380 mA (100 ms peak) - Power consumption 28.8 V 750 mA (100 ms peak) - inrush current spectral radiation range and sight angle - F200K1 UV-2 and F200K2 UV-2(Ex) 210 ...
Page 9
72 h operating according TRD604 Creepage distances and clearances IEC 60730-1:2010, ÜK III, VG 2 Interference susceptibility IEC 60730-1:2010, EN 61000-4 Emitted interference DIN EN 55011/A1, class B NOTICE Only a cross-section of 0.5 mm /20 AWG is possible for the F200K Ex.
Instructions for Maintenance Instructions for Maintenance Display and Operational Controls Represented in chapter 6.1 Layout of the Operational Controls. 5.1.1 Sensitivity Range - Indication This display type only exists in the F200K2 execution type. The display shows the sensitivity ranges I or II activated by external selection. The range I (normal sensitivity) is mainly used for high flame intensities, whilst range II (higher sensitivity) is used for weaker flame intensi- ties.
The flame scanner can be checked for proper functionality without a flame being present. Carry out the complete electrical installation of the flame scanner and connect it to thesup- ply voltage. A LAMTEC test emitter of the FFP30 type (IR + UV) can be used as an aux- iliary means for flame simulation.
This may chiefly be due to the interference emission of the ignition trans- former during ignition. – Check the shielding and FPE for proper connection to the F200K – Carry out a proper grounding of the ignition transformer –...
Instructions for Maintenance 5.2.5 Faults During Ignition Faults occurring during ignition may have several causes. In case of additionally monitoring of pilot flame and main flame, the pilot flame may not sufficiently be detected. • Check the pilot flame for stable operation Interference Refer to chapter 5.2.4 Fault on Flame Detection Defect in the device.
Instructions for Maintenance Troubleshooting on apparently immaculate functioning according to the indicator elements Check the output contact fuse and the contact – Disconnect the flame scanner from the supply voltage – Check the normally closed output contact at the 1st clamping point behind the flam scanner between the brown (BR) and the white (WH) connection wire (avoid low re- sistance continuity check - fuse 500 mA) –...
Appendix Appendix Layout of the Operational Controls Fig. 6-1 Monitoring and control elements F200K2 LED (green): Indication, ’Flame in’ state Intensity indicator for flame signal in the range 0 ... 100 % LED (yellow), only for F200K2, lights for active range. LED (red): Indication, "Flame out state"...
Fig. 7-2 1. (1) Positions of the internal jumper IR + UV Fig. 7-3 Dimensional drawing FFP30 A, B, C Threaded receptacle for F200K, F300K Plug-in receptacle for FFS05, FFS06, FFS07, FFS08, F200K Changing battery (9 V, 500 mA - turn left to open housing) Toggle switch...
Page 17
- Battery life approx ca. 3 years Housing Design: Cylindrical aluminium housing Montage: Direct connection to: - Threaded receptacle for F200K, F300K - Plug-in receptacle for FFS05, FFS06, FFS07, FFS08, F200K Environmental conditions Protection class: IP54 Level of protection: Weight: 0.52 kg/1.15 lb...
Page 18
The information in this publication is subject to technical changes. LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG Wiesenstraße 6 D-69190 Walldorf Telefon: +49 (0) 6227 6052-0 info@lamtec.de Telefax: +49 (0) 6227 6052-57 www.lamtec.de Printed in Germany | Copyright 2019...