Daikin REYQ72-456XATJU Service Manual page 257

60 hz
Hide thumbs Also See for REYQ72-456XATJU:
Table of Contents

Advertisement

SiUS371901EB
[2-78]:
Heat pump lockout
Part 5 Field Settings and Test Operation
Heat pump lockout temperature
Heat pump would be locked out when the outdoor air temperature is smaller than
the Heat Pump Lockout Temperature below – this setting is only affective when heat
pump lockout mode has been set. Unit will switch to heat pump lockout.
Fahrenheit (°F)
temperature
0 (default)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Celsius (°C)
–15
–26.1
–10
–23.3
–5
–20.5
0
–17.7
5
–15
10
–12.2
15
–9.4
20
–6.6
25
–3.8
30
–1.1
35
1.6
40
4.4
45
7.2
50
10
Forced heat pump lockout
Field Setting from Outdoor Unit
250

Hide quick links: