Weighing device for indicating loss of a critical mass of extinguishant
PED-category:
Fluid group:
Product line
Sinorix ™
Weighing Device SBT WD2005
CX ref. no.
560000
SAP
S54476-B45-A1
EN 12094-11
The weighing device SBT WD2005 by SIEMENS indicates the loss of a critical mass
cylinders.
The weighing device set consists of weighing device plus counterweight depending of the cylinder volume.
S54476-S45-A1 = S54476-B45-A1 + S54476-B52-A4 (counterweight 1.5 kg for 67 L)
S54476-S45-A2 = S54476-B45-A1 + S54476-B52-A5 (counterweight 2.0 kg for 80 L)
If the weighing device is to be used outdoors, it must be protected against the ingress of water.
Technical data
material
working temperature
max. humidity
max. gross load
max. net load
min. net load
mass loss indication supervision
mass loss indication supervision
available counterweights
mass loss indication
Operating Principle
The weighing device operates on the principle of an eccentric pivot.
An adjustable position balance weight mounted on the weight spindle enables the device to be set to indicate
the mass loss over a range of gross loads. If the cylinder weight and the balancing weight are equal, the
system is stable (balance weight is in the horizontal 'set' position). If the net weight reduces (due to leakage
from the cylinder) the balance weight drops downwards (balance weight moves to the inclined 'tripped'
position). The weighing device is adjusted to indicate a loss of mass of 5% from the suspended cylinder.
The weighing device must be reset manually to resume its function.
Building Technologies
Fire Safety & Security Products
WD2005-67 / WD2005-80
52
220
galvanized steel
0 ... 50° C
70%
200 kg
96kg
10kg
electrical with pos. switch
with counterweights
250g (CX560250), 500g (CX560500), 1000g (CX561000), 1500g (CX561500), 2000g (CX562000)
S54476-B52-A1, S54476-B52-A2, S54476-B52-A3, S54476-B52-A4, S54476-B52-A5
adjustible 5% - 10%
02-01-900
Index
Description
b
adjusting procedure
c
Set, tool new
d
RoHS, CO2 80L
e
NO / NC, CO2 80L
G305001
0786CPR30044
of extinguishant from the
ENGLISH
Date
01.10.06
27.08.10
01.05.14
01.12.15
01.03.18
1/6
02-01-900 E.doc

Advertisement

loading

Summary of Contents for Siemens SBT WD2005

  • Page 1 0786CPR30044 EN 12094-11 of extinguishant from the The weighing device SBT WD2005 by SIEMENS indicates the loss of a critical mass cylinders. The weighing device set consists of weighing device plus counterweight depending of the cylinder volume. S54476-S45-A1 = S54476-B45-A1 + S54476-B52-A4 (counterweight 1.5 kg for 67 L) S54476-S45-A2 = S54476-B45-A1 + S54476-B52-A5 (counterweight 2.0 kg for 80 L)
  • Page 2 The weighing device Pos. 1 Trapeze spindle Pos. 2 Trapeze nut Assembly sleeve with Pos. 3 tommy bar (tool) Pos. 4 Lock nut Pos. 5 Drilled hole Pos. 6 Threaded rods Pos. 7 Neck ring Pos. 8 Trip mechanism Pos. 9 Suspension rail Pos.
  • Page 3 Assembly instructions electrical remote indication switch The weighing device is supplied with a bracket and trip plate fitted. There is type of remote indication switch (optional). · Siemens CX 1562010 / A5Q00032144 including all fixations, documentation 12-01-010 Technische Daten / Technical data Deutsch English...
  • Page 4 Adjusting the weighing device Select the Balance weights according to the weight of the cylinder (refer to the following tables). Extinguishing Cylinder-volume Net load Net load Gross load Filling quantity Filling factor kg/L 13.4L 10 kg 0,75 25.5 ± 1 kg 22.5 kg 0,75 60 ±...
  • Page 5 Adjusting the weighing device Procedure Screw the Balance weight(s) specifed in the table above onto the weight spindle. The weight spindle moves to the ‘tripped’ position (pos. 3). Trick: At start turning weight lift spindle manually to horizontal until selfhoding noticeable. Holding the weight spindle in the ‘set’...
  • Page 6: Maintenance Instructions

    Maintenance instructions Warning! Only readjust the balance weights each time the cylinder is removed from the weighing device for refill or when it cannot be guaranteed that a filled cylinder will be refitted to its original weighing device. Do not adjust the position of the balance weights during routine servicing or due to the weighing device having tripped.