VDH ALFA 71 MOD User Manual

VDH ALFA 71 MOD User Manual

Advertisement

Quick Links

User manual
ALFA 71 MODulation
Thermostat.
VDH doc. 052939
Software: ALFA71MOD

* Installation.

On the top side of the ALFA 71 MOD is shown how the sensors, power supply, relays and 0..10Vdc
PI output has to be connected.
After connecting the ALFA 71 MOD to the power supply, a self test function is started. As this test is
finished the measured temperature appears in the display.

* Control.

The ALFA 71 MOD thermostat can be controlled by four pushbuttons on the front. These keys are:
SET
- view / change the setpoint.
UP
- increase the setpoint.
DOWN
- decrease the setpoint.
C
- hidden push button above the SET key and behind C symbol.

* Viewing setpoint.

By pushing the SET key the setpoint appears in the display. The decimal point of the last display
starts blinking. A few seconds after releasing the SET key the setpoint disappears and the
measured temperature is shown again in the display.

* Changing setpoint.

Push the SET key and the setpoint appears in the display. Release the SET key. Now push the SET
key again together with the UP or DOWN keys to change the setpoint. A few seconds after
releasing the keys the measured temperature shows again in the display.

* Status of the Relays.

By pushing the hidden C key the display shows the status of the relays. Each display segment
shows the status of the relay output, showing 0=off and 1=on. The code 110 means relay 1 and 2
are on and relay 3 is off.

* Readout valve position.

By pushing the UP key the display shows the current valve position.

* Setting internal parameters.

Next to the adjustment of the setpoint, internal settings can be made like differential, sensor-offset,
setpoint range and the functions of the thermostat.
Push the DOWN key more than 10 seconds, to enter the 'Internal Programming Menu'. In the left
display the upper and lower segment are blinking. Over the UP and DOWN keys the required
parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the SET key. Pushing
the UP or DOWN key to change the value of this parameter.
If after 20 seconds no key is pushed, the ALFA 71 MOD changes to the normal operation mode.
Version: v1.0
File: DO052939.WPD
1
Date: 03-10-2005
Range: -50/+50,0C

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ALFA 71 MOD and is the answer not in the manual?

Questions and answers

Summary of Contents for VDH ALFA 71 MOD

  • Page 1 On the top side of the ALFA 71 MOD is shown how the sensors, power supply, relays and 0..10Vdc PI output has to be connected. After connecting the ALFA 71 MOD to the power supply, a self test function is started. As this test is finished the measured temperature appears in the display.
  • Page 2 The temperature sensor can be adjusted by using the Sensor Offset parameter 05. Indicates the Sensor e.g. 2C to much, the Sensor Offset has to be decreased with 2C. * Error messages. In the display of the ALFA 71 MOD the following error messages can appear: - Minimum alarm. Solution E1: - Maximum alarm.
  • Page 3 * Parameters ALFA 71 MOD Para- Description Parameter Range Default meter Function thermostat 1=Cool 2=Heat -15.0..+15.0  C Offset temperature sensor-1 0,0..+15,0  C P-band I-time 0..99 Minutes Runtime valve 0..999 Seconds Reset time 0..999 Minutes Reset to minimum or maximum valve...
  • Page 4 * Dimensions. * Connections. * Address. VDH Products BV Tel: +31 (0)50 30 28 900 Produktieweg 1 Fax: +31 (0)50 30 28 980 9301 ZS Roden Email: info@vdhproducts.nl The Netherlands Internet: www.vdhproducts.nl...

Table of Contents