Summary of Contents for TriangleTube The Modulating delta
Page 1
Modulating Modulating WARNING This document is intended to be used by a qualified heating contractor or service technician. Read all instructions within this document and within the MODULAT- ING DELTA Installation and Maintenance Manual, before proceeding with the installation. It is recommended to follow the procedures in the steps given, skip- ping or missing procedural steps could result in severe personal injury, death or substantial property damage.
Table of Contents PRODUCT AND SAFETY INFORMATION Definitions ............1 Installer Information .
Page 3
Table of Contents SECTION III - CATEGORY III or IV - INSTALLATION OF VENT/AIR PIPING Category III or IV - Vertical - Thru the Roof or Unused Chimney....23 Determine Termination Location .
Product and Safety Information DEFINITIONS NOTICE The following terms are used throughout this manual to bring attention to the presence of potential hazards or to important information concerning the product. Indicates special instructions on installation, opera- tion or maintenance, which are important to the DANGER equipment but not related to personal injury hazards.
Pre-Installation Items SECTION I - PRE- INSTALLATION ITEMS mum speed. Do not operate a summer exhaust fan. Close fireplace dampers. Removal of an Existing Appliance from a Common 4. Place in operation the appliance being inspected. Vent System Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
Potential contaminating products Spray cans containing chloro/fluorocarbons WARNING Permanent Wave Solutions If the MODULATING DELTA combustion air inlet Chlorinated wax is located in any area likely to cause or contain Chlorine - based swimming pool chemicals / contamination, or if products, which would con-...
(little or no infiltration air), it is recommend- ed to pipe uncontaminated combustion air For installations in which the MODULATING DELTA directly from the outdoors to the appliance. This shares the space with air movers (exhaust fan, clothes practice also promotes higher system efficiency dryers, fireplaces, etc.) and other combustion equip-...
Pre-Installation Items Methods of Accessing Combustion Air Into A Space Combining spaces in different stories. The vol- - Category I, III and IV umes of spaces in different stories shall be con- sidered as communicating spaces where such spaces are connected by one or more openings Indoor Combustion Air in doors or floors having a total minimum free NOTICE...
Page 9
Pre-Installation Items All Combustion Air from outdoors Fig. 2: Fig. 3: All Combustion Air from Outdoors through; One Permanent Air Openings Through Ventilated Attic Two Permanent Openings Method. Two permanent openings, one commencing within 12 in. of the top and one commencing within 12 in. of the bot- tom of the enclosure, shall be provided.
Pre-Installation Items Combination of Indoor and Outdoor Combustion Air The MODULATING DELTA is certified per ANSI Z21.10.3 and CSA 4.3 as a Category I or III or IV (indoor air) or Direct Vent (sealed combustion) appliance. A Indoor Openings: Where used, openings connecting the...
Direct Vent Installation of Vent/Air Piping Vent Piping Materials - Category I Combustion Air Piping and Materials -Direct Vent WARNING WARNING The vent materials must meet the listed require- The combustion air materials must meet the listed ments in this manual. Failure to comply with these requirements in this manual.
Installation Manual for Installation Details shown in Figs. 5 & 6 and are available in accessory kits through Triangle Tube. See Fig. 6 page 10 for Two Pipe installation details or the MODULATING DELTA Concentric Vent Installation Manual for additional Concentric details.
Page 13
Direct Vent Installation of Vent/Air Piping 12” Min. & 24” Max. Radial Distance Rain Cap Storm Elbow Collar 12” Min. - 24” Max. with Bird Adjustable Above Combustion Screen Flashing Air Inlet Adjustable Refer to Vent Manufacturer's 12” Above Roof of Flashing Recommended Clearances Projected Snow Line...
Direct Vent Installation of Vent/Air Piping Determine Termination Location Locate or guard the vent termination to prevent possible condensate damage to exterior finishes. Locate the vent and combustion air termination using the g. Avoid locations of possible accidental contact of following guidelines: flue vapors with persons or pets.
Direct Vent Installation of Vent/Air Piping 5. The installer should provide adequate flashing and Direct Vent - Multiple Installation - Thru the Roof sealing boots sized for the vent pipe and combustion 1. On installations of multiple MODULATING DELTAS, air pipe. terminate each vent and combustion air piping as described in this manual.
Direct Vent Installation of Vent/Air Piping NOTICE Direct Vent -Horizontal The installer has three options when direct venting hori- Installation of the vent and combustion air pip- zontally, Concentric, Wall Thimble or Two Pipe. The ing must comply with local codes and require- three vent options are shown in Figs.
Page 17
Direct Vent Installation of Vent/Air Piping Termination- Straight or Tee or Hood with Bird Screen (s) Horizontal Termination Adapter With AIr Holes Facing Down 36”Max. Vertical 12” Min & 36” Max. Support Leg Above Grade or Projected Snow Line 2 Foot Length 90 Elbow Thimble -...
Page 18
Direct Vent Installation of Vent/Air Piping Refer to Vent Manufacturer's Recommended Spacing of Support Triangle Tube Wall Thimble Kit Installed Flush with Wall Termination - Drain Refer to Vent Straight or Tee or Hood Manufacturer's with Bird Screen(s)* Recommended Clearances Elbow Hanger Strap...
Page 19
Direct Vent Installation of Vent/Air Piping Direct Vent - Horizontal Wall Thimble Termination Assembly Fig. 10A:...
Page 20
Direct Vent Installation of Vent/Air Piping 12” Min. 24” Max. Tee or Hood Vent Termination Venting Horizontally 12” Min. 24” Max. 90º Elbow Above Combustion with Bird Screen Air Inlet Combustion Air Termination 12” Min. Above Grade or Projected Snow Line 12”...
Page 21
Direct Vent Installation of Vent/Air Piping Fig. 11A: Direct Vent - Horizontal Two Pipe Snorkel Terminations...
Direct Vent Installation of Vent/Air Piping Determine Termination Location c. Prevailing winds could cause freezing of flue condensation and a buildup of water / ice on sur- Locate the vent and combustion air termination using the rounding plants, building surfaces or combus- following guidelines: tion air inlet.
Direct Vent Installation of Vent/Air Piping Direct Vent - Vent Installation - Horizontal 2. The combustion air piping must terminate using a 90º elbow as shown in Figs. 11 & 11A, pages 17 & 18. 1. Vent and Combustion Air Penetration 3.
System Vent Appliance Adapters - Direct Vent Combustion Air Adapter The MODULATING DELTA requires the use of an appli- ance adapter as approved by the one of vent manufac- 1. The installer must clean and deburr pipe. turers listed on page 8.
Direct Vent Installation of Vent/Air Piping Vent and Combustion Air Piping Installation Guidelines 9. Maintain minimum clearances per vent manufac- ture’s instructions for both, combustible or non-com- 1. The installer should install the vent / combustion air bustible materials. The installer must seal any wall, piping working from the appliance to the piping termi- floor or ceiling penetrations as per local code nation.
Category III or IV Installation of Vent/Air Piping SECTION III - CATEGORY III OR IV INSTAL- Determine Termination Location LATION OF VENT/AIR PIPING Locate the vent and combustion air termination using the A Category III or IV appliance utilizes uncontaminated following guidelines: indoor or outdoor air (surrounding the appliance) for com- bustion.
Category III or IV Installation of Vent/Air Piping Category III or IV - Vent Installation - Thru the Roof 4. The following should be considered when determin- ing the location of the vent termination: 1. Vent Penetration a. Locate the vent termination where flue vapors Vent pipe penetration maintain vent manufac- will not damage surrounding shrubs, plants or ture’s required clearances to combustibles &...
Category III or IV Installation of Vent/Air Piping Category III or IV - Multiple Installation - Thru the Category III or IV - Horizontal Roof NOTICE 1. On installations of multiple MODULATING DELTAS, terminate each vent pipe as described in this manual. Installation of the vent and combustion air pip- 2.
Page 29
Category III or IV Installation of Vent/Air Piping Refer to Vent Manufacturer's Recommended Spacing of Support Thimble - Seal Around Thimble & pipe with Silicone Termination - Condensate Drain Refer to Vent Manufacturer's Straight or Tee or Hood withTrap Loop Recommended Clearances with Bird Screen (s) Elbow...
Category III or IV Installation of Vent/Air Piping Determine Termination Location g. Avoid locations of possible accidental contact of flue vapors with persons or pets. Locate the vent and combustion air termination using the 5. The vent termination must also maintain the follow- following guidelines: ing clearances;...
Category III or IV Installation of Vent/Air Piping Termination Fittings - Horizontal Category III or IV - Multiple Installation - Sidewall 1. The combustion air pipe termination must include a 1. On installations of multiple MODULATING DELTAS, factory supplied “bird screen” as shown in Fig. 18. terminate each vent pipe as described in this manual.
The MODULATING DELTA requires the use of an appli- ance adapter as approved by the one of vent manufac- Pipe the condensate drain tube to a suitable place of turers listed on page 8.
Page 33
Category III or IV Installation of Vent/Air WARNING NOTICE Do not pitch the vent away from the appliance. Table 3 references a long radius 90º elbow. For Potential condensate damage to the building each additional 90º elbow within the system, the exterior or to the surrounding landscape and/or installer must reduce the maximum allowable potential risks of icing and blockage of the vent...
Type B or other approved The NFPA code book severely limits the instal- material having equivalent insulation qualities. lation of the MODULATING DELTA into a The minimum clearance to combustibles for sin- masonry chimney. For applications using either gle wall vent connectors shall be 6 inches.
Category I - Installation of Vent/Air Piping NOTICE The vent connector should be installed in a manner without any dips or sags and should slope upward toward the vent or chimney at There are certain applications for the MODULAT- least 1/4 inch per 1 foot. ING DELTA in which upsizing the vent connector The location of the appliance should be located to 5 inches will not result in sufficient maximum...
Commonwealth of Massachusetts SECTION V - COMMONWEALTH OF MAS- NOTICE SACHUSETTS The carbon monoxide detector and alarm INSTALLATIONS WITH SIDE WALL VENT installed within the same room as the side wall TERMINATION ELEVATION AT OR BELOW 4 vented appliance must meet ANSI/UL 2034 stan- FEET OF GRADE: dards and comply with NFPA 720 (2005 edition).
COMMONWEALTH of Massachusetts NOTICE INSTALLATIONS WITH THE SIDE WALL TERMINATION ELEVATION ABOVE 4 FEET The carbon monoxide detector and alarm installed within the same room as the direct vent OF GRADE: appliance must comply with NFPA 720 (2005 edi- tion). NOTICE 3.
Page 38
Available in capacities from 25,000 BTU/hr to 5,000,000 BTU/hr MODULATING DELTA CONCENTRIC PRIMARY / SECONDARY MANIFOLD VENT KIT Member of Freeway Center - 1 Triangle Lane - Blackwood, NJ 08012 Tel: (856) 228 8881 - Fax: (856) 228 3584 E-mail: Sales@triangletube.com Group...