Download Print this page
Regin CO2DT-R Instructions

Regin CO2DT-R Instructions

Co2 transmitter for duct mounting

Advertisement

Available languages

Available languages

Quick Links

INSTRUCTION
EN
CO2DT-R
i
Read this instruction before installation
and wiring of the product
CO
-transmitter for duct mounting
2
CO2DT-R is a transmitter for measuring
carbon dioxide (CO
tration in exhaust air. Measuring range 0...2000ppm and relay output.
CO2DT-R is intended for duct mounting.
Technical data
Measuring principle
NDIR (Non-Dispersive Infrared
Technology)
Measuring range
0...2000 ppm
Inaccuracy at 20°C
< ±(50 ppm + 2% of the measured value)
Temp. influence
typ. 2 ppm / K
Long term stability
typ. 20 ppm / year
Time constant
< 120 seconds
Warm-up time
< 5 minutes
Ambient temperature
-5...55°C
Humidity
0...90 % RH non condensating
Protection class
IP65 with probe downwards, otherwise
IP20
Mounting
CO2DT-R should be mounted at a place in the duct where it can be
expected to give a representative reading. The transmitter should be
placed at least 4 duct diameters after a bend for minimal turbulence.
Open the front cover by removing the screws on the cover with a screw-
driver.
) concen-
2
Wiring
Supply voltage 24 V AC ±20%, 50...60 Hz or 15...35 V DC
Consumption 3 W.
1
Supply voltage 24 V AC/DC or 15...35 V DC
2
System neutral
3
Common
4
Normally open
5
Normally closed
CO
sensing element
2
air flow direction
Hysteresis and level
Hysteresis [% of the set measuring range]
ON
25% of
measuring
range
Level [% of measuring range]
OFF
500
1000
Start-up
After applying power to CO2DT-R, it will take a few minutes before it
shows correct values.
Calibration
CO2DT-R is factory calibrated before delivery and does not need to
be calibrated at installation.
CO2DT-R is calibrated automatically, which means that manual recali-
bration is not required during the lifetime of the sensor.
EMC emissions & immunity standards
This product conforms to the requirements of the EMC Direc-
tive 2004/108/EC through product standards EN 61000-6-1 and
EN 61000-6-3.
RoHS
This product conforms to the Directive 2011/65/EU of the European
Parliament and of the Council.
Contact
AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, info@regin.se
2000
ppm
1

Advertisement

loading

Summary of Contents for Regin CO2DT-R

  • Page 1 Level [% of measuring range] Mounting CO2DT-R should be mounted at a place in the duct where it can be expected to give a representative reading. The transmitter should be 1000 2000 placed at least 4 duct diameters after a bend for minimal turbulence.
  • Page 2 Montering Nivå [% av mätområde] CO2DT-R skall monteras i ventilationskanalen på en plats som kan förväntas ge representativa mätvärden. Givaren ska sitta minst 4 kanaldiametrar efter böj för minimal turbulens. Öppna locket genom att avlägsna skruvarna på lockets ovansida med...
  • Page 3 Seuil [% de la plage de mesure] Arrêt (off) Montage Le CO2DT-R doit être monté dans une gaine dans un endroit qui peut 1 000 2 000 donner des valeurs représentatives. Le transmetteur doit être placé à une distance d’au moins 4 fois le diamètre de la gaine, après un Démarrage...
  • Page 4 Der CO2DT-R ist bei Lieferung werksmäßig kalibriert und braucht deshalb nicht bei der Installation kalibriert zu werden. Diese Anleitung vor Installation und Verdrahtung Der CO2DT-R wird automatisch kalibriert, d. h., dass für die gesamte sensing element des Produktes bitte durchlesen.