EN
INSTRUCTION
PDTX...-C
REV. C, 2022-03-14
N N o o t t e e ! ! More information about the product configuration can be found in
the variable list, which is available for download from www.regincontrols.
com
C C a a u u t t i i o o n n ! ! Read and understand the instruction before using the product.
C C a a u u t t i i o o n n ! ! Ensure that the installation complies with local safety
regulations.
C C a a u u t t i i o o n n ! ! Before installation or maintenance, the power supply should first
be disconnected. Installation or maintenance of this unit should only be
carried out by qualified personnel. The manufacturer is not responsible
for any eventual damage or injury caused by inadequate skills during instal-
lation, or through removal of or deactivation of any security devices.
Function
Presigo PDTX...-C is a range of pressure transmitters equipped with one
or two pressure sensors, two universal inputs, two universal outputs and
an RS485 port for Modbus communication. It operates as a Modbus
slave.
This range of pressure transmitters is especially well suited as distributed
I/O modules for air handling unit controllers. They are designed for easy
installation together with Regin's Corrigo or EXOcompact controllers.
Technical data
Supply voltage
24 V AC/DC (21...27 V AC/DC)
Protection class
IP54
Power consumption
< 4 VA
Ambient humidity
0...95 % RH (non-condensing)
Ambient temperature
-25...+50 °C
Working range, pressure 0...1250 / 0...2500 / 0...7500 Pa (factory setting)
0...12 / 0...25 / 0...75 mbar
0...127 / 0...254 / 0...764 mmH
0...5 / 0...10 / 0...30 inH
Working range, flow
0...65000 m
3
/h (factory setting)
0...31000 l/s
0...65000 Ft
3
/min
Cable glands
2 x M20 (cable diameter 5...12 mm)
1 x M16 (cable diameter 3.5...10 mm)
Max overvoltage
±18 V, on any terminal (not G and G0)
Electronic damping
0 s (0...120 s)
Accessories, included
Two pressure outlets (straight) and 2 m plastic tube.
Art. no.: ANS-20
Dimensions, external
167 x (~130) x 46 mm
(WxHxD)
Pressure data
Media
Air, non-combustible and non-aggressive gases
Annual deviation
±2 Pa (1250 Pa)
±4 Pa (2500 Pa)
±20 Pa (7500 Pa)
K-factor
5 (5...700)
Universal Input, UI1 and UI2
Universal inputs (UI)
2
Configuration
AI (AI / DI), see specifications below
Configured as AI:
Analogue inputs (AI)
0...10 V (0...10 V / PT1000 / Ni1000-01)
Accuracy
± 1 % (0...10 V)
± 0.5 K (PT1000/Ni1000-01)
Measuring range,
-40...+60 °C
temperature
Configured as DI:
Presigo
Digital input (DI)
Output current
Universal Output, UO1 and UO2
Universal outputs (UO)
Configuration
Configured as AO:
O
2
O
2
Analogue outputs (AO)
Load impedance, 0...10 V Min. 10 kΩ
Accuracy
Configured as DO:
Configuration
Power output
Communication port data
Communication ports
Port type
Supported protocols
Port isolation
Cable length
Models
Article
PDTX12-C
PDTX25-C
PDTX75-C
PDTX12-2-C
PDTX25-2-C
PDTX12S25-C
PDTX12S75-C
Potential-free contacts on / off (on = closed)
0.5 mA (max 2.5 V)
2
AO (AO / DO), see specifications below
0...10 V
± 1 %
Mosfet outputs, 24 V AC or DC, 2 A continuous
Max. 2A (total UO1 + UO2)
1
RS485
Modbus
Non-isolated
Max 100 m
Number of
Max overload
Measuring range,
sensors
pressure (kPa)
pressure (Pa)
1
25
0...1250
1
50
0...2500
1
120
0...7500
2
25 / 25
0...1250 (sensor 1) /
0...1250 (sensor 2)
2
50 / 50
0...2500 (sensor 1) /
0...2500 (sensor 2)
2
25 / 50
0...1250 (sensor 1) /
0...2500 (sensor 2)
2
25 / 120
0...1250 (sensor 1) /
0...7500 (sensor 2)
1 (18)