Rate-of-rise heat detector

Advertisement

h
From zone
of the panel
Connection
If the power of the detectors is turned off, wait for 3-5 seconds before you turn the power on
again.
1. Remove the detector from its base rotating to the left till the side marks are aligned.
2. Fasten the base with the supplied mounting materials (point 5).
3. Connect the power cables (minding the correct polarity) according to the requirements of
the installation (Figure 1, 2).
4. Place the detector carefully so that the side marks are on the same position and rotate the
detector clockwise until it locks. Power the device and after 3-5 seconds it is ready for
operation.
CONNECTION
1. + IN/OUT : It is connected to the zone of the panel or to the (+ IN/OUT)
contact of the previous detector.
2. - IN : It is connected to the zone of the panel or to the (- OUT) contact of the
previous detector.
3. - OUT : It is connected to the next detector (- IN) or if it is the last one to the terminal
resistor.
4. - R : It is connected with BS-572.
5.
: Connected to the cable's shield (when shield is used).
Page 3 from 4
Installation process
Installation process
Side marks
1
Indicating
LED
Mounting base
2
5
5
Figure 1
Figure 2
921660004_09_002
Connection
with exterrnal
LED
+
R