Download Print this page
Regin NO2F Instructions

Regin NO2F Instructions

Nitrogen dioxide transmitter

Advertisement

Available languages

Available languages

Quick Links

INSTRUCTION
EN
NO2F
i
Read this instruction before installation
and wiring of the product
Nitrogen dioxide (NO
) transmitter
2
NO2F is a detector intended for demand-controlled ventilation in
parking garages and road tunnels etc. The detector measures the
NO
concentration using an electrochemical method of measurement
2
characterised by high selectivity and accuracy even in low concentra-
tions. The output signal is a linear representation of the gas concen-
tration.
Technical data
Supply voltage
12...28 V DC
Power consumption
20 mAh
Method of measurement
Electrochemical
Outputs
4...20 mA, two-wire
0...10 V DC, three-wire
Calibration
Automatic zero adjustment
Ambient temperature
-10...+40°C
Ambient humidity
0...90 % RH
Protection class
IP56
Dimensions (WxHxD)
80 x 82 x 86 mm
Weight
0.190 kg
Material, casing
Polycarbonate
Type of gas
Nitrogen dioxide (NO
Measuring range
0...20 ppm
Accuracy
±3 %
Lifetime sensor
~ 2 years
Installation
NO2F is recommended to be mounted about 20-30 cm above the floor.
One detector is to be placed per 200-500 square metres garage surface,
provided that the surface is open (without any "pockets") and that there
is continuous air flow. Install the detector at least 50 cm from ventilation
ducts and room corners. The transmitter must be mounted with the cable
connection pointing up.
Wiring
The output signal is set via a jumper according to the figures below.
(+) 12...28 V DC
(+)
!
0...10 V DC
(-)
0...10 V DC
(+)
(-)
4...20 mA
NO2F
)
Control and alarm levels
2
We recommend using two alarm levels, pre-alarm and full alarm. In
case of a pre-alarm, the fans are to be set to full speed and strategi-
cally placed flashing lights are to be activated. In case of a full alarm,
strategically placed sirens are to be started, advising people to leave
the garage immediately. Recommended levels for these alarms:
Pre-alarm
Full alarm
Service life and length of warranty
Regin recommends that the product be replaced by a new unit every
two years (24 months) due to the service life of the measuring ele-
ment. Therefore, the length of warranty for this particular product is
12 months. Because of the calibration required, the measuring ele-
ment is non-replaceable.
CONTROLLER
This product carries the CE mark. For more information, see
www.regincontrols.com.
This product is TÜV-approved in accordance with VDI 2053.
(+)
Contact
(-)
AB Regin, Box 116, SE-428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, info@regin.se
CONTROLLER
(+) 12...28 V DC
(-)
R = Max. 300 Ohm
2 ppm
5 ppm
1

Advertisement

loading

Summary of Contents for Regin NO2F

  • Page 1 Installation the garage immediately. Recommended levels for these alarms: NO2F is recommended to be mounted about 20-30 cm above the floor. One detector is to be placed per 200-500 square metres garage surface, Pre-alarm 2 ppm provided that the surface is open (without any ”pockets”) and that there...
  • Page 2 Teknisk support REGULATOR Transmitter för kvävedioxid (NO Teknisk hjälp och råd på telefon: 031 720 02 30 NO2F är en detektor avsedd för behovsstyrning av ventilation i ga- Kontakt 0...10 V DC rage och vägtunnlar etc. Detektorn mäter NO -koncentrationen med AB Regin, Box 116, 428 22 Kållered...
  • Page 3 Es werden zwei Alarmstufen empfohlen, Voralarm und Alarm. Bei einem Montage Voralarm laufen die Ventilatoren mit voller Geschwindigkeit und strate- Der NO2F-Detektor sollte ca. 20 – 30 cm über dem Boden montiert gisch günstig positionierte Warnlampen werden aktiviert. Bei einem Alarm werden. Es muss pro 200 – 500 m Garagenfläche ein Detektor...
  • Page 4 Tél. : +33 (0)1 41 71 00 34, Fax : +33 (0)1 41 71 46 46 www.regincontrols.com, info@regin.fr NO2F est un détecteur prévu pour le contrôle de la qualité de l’air dans des zones souterraines, par exemple les parkings ou garages 0...10 V DC...