Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended
Practices, Liabilities and Warranties.
GENERAL
bEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED FOR
COMPATIbILITY TO THE PROCESS MEDIA IN CONTACT WITH THE
SENSOR AND WETTED PARTS.
MISuSE OF THIS PRODuCT MAY CAuSE EXPLOSION AND PERSONAL
INjuRY. THESE INSTRuCTIONS MuST bE THOROuGHLY READ AND
uNDERSTOOD bEFORE uNIT IS INSTALLED.
THIS EquIPMENT IS SuITAbLE FOR uSE IN CLASS I, DIvISIONS
1 & 2, GROuPS A, b, C AND D; CLASS II, DIvISIONS 1 & 2, GROuPS
E, F AND G; CLASS III; OR NON-HAzARDOuS LOCATIONS ONLY. -40°C
(-40°F) ≤ Tamb. ≤ 85°C (185°F), ENCLOSuRE TYPE 4X.
THIS EquIPMENT IS ATEX CERTIFIED FOR EquIPMENT CATEGORY 2.
SuITAbLE FOR APPROPRIATE uSE IN GAS zONE 1 AND DuST zONE
21 APPLICATIONS.
0539 DEMKO 07 ATEX 0715718X
II 2 G Ex d IIC T5
II 2 D T+90°C
-40°C ≤ Tamb. ≤+80ºC, IP66
The TX200™ transmitter utilize a bonded foil strain gage bridge sensor
to detect and continuously monitor pressure in a system. The strain gage
is a resistive element whose resistance changes with the amount of strain
(pressure) placed upon it. Flexing of the diaphragm causes the resistance
change and electronically communicates this via a 4 to 20 mA output signal
or optional 1-5 VDC output signal to a digital meter or gauge, a PLC (pro-
grammable logic controller) or other device. The TX200B is "fixed range"
while the TX200A is "field adjustable" with a 5:1 turndown ratio (see Part II
– Adjustments).
PROOF PRESSuRE* LIMITS STATED IN THE LITERATuRE AND ON TRANSMITTER
HOuSING MuST NEvER bE EXCEEDED, EvEN bY SuRGES IN THE SYS-
TEM. OCCASIONAL OPERATION OF uNIT uP TO MAXIMuM PRESSuRE IS
ACCEPTAbLE (E.G., START-uP, TESTING). CONTINuOuS OPERATION SHOuLD NOT
EXCEED THE DESIGNATED OvER RANGE PRESSuRE.
*Proof Pressure
The maximum pressure to which a pressure sensor may be occasionally
subjected, which causes no permanent damage (e.g., start-up, testing). The
units may require re-adjustment.
THESE PRODuCTS DO NOT HAvE ANY FIELD REPLACEAbLE PARTS.
ANY SubSTITuTION OF COMPONENTS MAY IMPAIR SuITAbILITY FOR
CLASS I, DIvISION 1.
TX200™

Pressure Transmitter

IMTX200-02
www.ueonline.com
U N I T E D E L E C T R I C
C O N T R O L S
Installation and Maintenance
Instructions
THE EPOXY RESIN SHALL NOT bE SubjECTED TO A TEMPERATuRE
GrEATEr ThAn 125°C.
Part I - Installation
MouNTING
ALWAYS LOCATE uNITS WHERE SHOCK, vIbRATION AND AMbIENT
TEMPERATuRE FLuCTuATIONS ARE MINIMAL. DO NOT MOuNT IN
AMBIEnT TEMPErATurE ArEAs EXCEEDInG 185°F (IF uL/cuL
APPrOVAL Is APPLICABLE) Or 80 °C (IF ATEX APPrOVAL Is APPLICABLE).
IF SEvERE PRESSuRE SuRGES ARE EXPECTED, CONSIDER THE uSE OF A
PRESSuRE SNubbER.
uNIT MAY bE MOuNTED IN ANY POSITION. ALWAYS HOLD A WRENCH
ON THE SENSOR FLATS (PRESSuRE PORT) WHEN MOuNTING uNIT.
WIRING
DISCONNECT ALL SuPPLY CIRCuITS bEFORE WIRING uNIT. ELECTRICAL
RATINGS STATED IN LITERATuRE AND ON THE TRANSMITTER MuST
NOT bE EXCEEDED.
EXTErnAL GrOunDInG sCrEW (OPTIOn M460) Is rEquIrED FOr
NON-METALLIC CONDuIT SYSTEMS. (ATEX REquIREMENT ONLY).
IN ORDER TO MEET EuROPEAN EMC REquIREMENTS, THE TX200™
WIRING MuST bE INSTALLED IN A GROuNDED METAL CONDuIT OR
WITH OTHER SuITAbLE SHIELDING.
ThE TX200™ TrAnsMITTEr ACCEPTs 10-36 VDC FOr 4-20 MA
OuTPuT unITs AnD 10-30 VDC FOr 1-5 VDC OuTPuT unITs. ThE
suPPLY VOLTAGE shALL nOT EXCEED 36 VDC FOr 4-20 MA OuTPuT
unITs AnD 30 VDC FOr 1-5 VDC OuTPuT unITs. ThE suPPLY MusT BE
IsOLATED FrOM MAIns VOLTAGE BY DOuBLE/rEInFOrCED InsuLATIOn.
EARTH GROuND MuST ALWAYS bE CONNECTED TO THE GREEN WIRE
TO PROvIDE SHIELDING AND ELECTRICAL SAFETY.
WIRE IN ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL
CODES. bY THE INSTALLATION, THE WIRES SHALL bE PROTECTED
AGAINST MECHANICAL DAMAGE. E.G. bY uSE OF A CONDuIT.