Introduction
This leaflet is intended to support the main Installation and
Maintenance Instructions supplied with the fan unit, available
on request from the Nuaire Technical Library. Telephone:
02920 885911.
1. Getting started
The Ecosmart Twinfan is designed for maximum control
flexibility. Apart from the power supply, an enabling signal is
always required to set the fan running. This enabling signal
can be a switched live signal (connected to the SL terminal of
each fan) or an enabling device plugged in the NET connection
(see table 'Ecosmart compatible devices').
If an enabling signal is not available, connect a link wire
between 'L' & 'SL'
Additional sensor and manual control may be added. For
example: to run the fan with a temperature sensor, connect a
link across L to SL (enabling signal) and connect a temperature
sensor in one of the sockets labelled 'NET' The fan will now
adjust it's speed according to temperature.
To obtain manual control, connect a link across L to SL
(enabling signal) and connect a user control in one of the
sockets labelled 'NET'.
Figure 1. Example Fan Control module connection details.
Note:
Remove the link wire if a switched live
signal is present or an enabling device
or a BMS is connected to the'NET
240V 1ph 50Hz
mains supply
Switch live signal
(if required)
Connection
to Damper
Volt Free Contact
RUN signal
5A resistive
0.5A inductive
Volt Free Contact
FAULT signal
FUSES
F1 & F2 = 20mm *type T fuse for fan 1 and fan 2
F3
= 20mm 1A type T fuse for dampers
F4
= 20mm 1A type T fuse for control circuit
* rated to fan size
Nuaire: A Trading Division of Polypipe Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA
T: 029 2088 5911 F: 029 2088 7033 E: info@nuaire.co.uk W: www.nuaire.co.uk
COMMISSIONING
ECOSMART CLASSIC
(ES) CONTROL
N
N
L
L
Link
wire
SL
OP
CL
N
RET
RUN
RUN
FAULT
FAULT
Ecosmart compatible devices
Enabling Devices
ES-PIR:
PIR Sensor
ES-TC:
7 day Timeclock
Sensors
ES-TEMP:
Temperature Sensor
ES-RH:
Humidity Sensor
User Controls
ES-UCF:
Fan only control
ES-UCFH:
Fan and Heating Control
(heating will only operate within relevant units)
Others
ES-JB:
Junction Box (to add extra sensors etc)
ES-AVI:
Audio Visual Fault Indication
Note that these Ecosmart devices will affect all the fans linked
using the SELV data cable.
The switched live signal will only affect the fan to which it is
connected.
New devices are constantly in development, please contact us
for latest range details.
NET connections for ECOSMART devices
eg sensors and inter-connections of fans
NET
Fan 2
Fan 1
F3
F4
Min
Max SL run on
0
1
Trickle
MIN
= Minimum speed adjustment
MAX
= Maximum speed adjustment
SL
run on
= Switched Live Run-On Timer adjustment
TRICKLE = Selects trickle running: 0=off, 1= selected
TEST
= Test button
1
2014/30/EU
The Low Voltage
directive
2014/35/EU
OV
0-10V signal
from BMS
0-10V
LED indicators
Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx
Test
08. 10. 18. Leaflet Number 671153

Advertisement

loading

Summary of Contents for NuAire ECOSMART CLASSIC CONTROL Series

  • Page 1 TRICKLE = Selects trickle running: 0=off, 1= selected TEST = Test button Nuaire: A Trading Division of Polypipe Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA T: 029 2088 5911 F: 029 2088 7033 E: info@nuaire.co.uk W: www.nuaire.co.uk 08. 10. 18. Leaflet Number 671153...
  • Page 2 Commissioning ECOSMART CLASSIC (ES) CONTROL 2. Commissioning Procedure Figure 2. Typical EST graph (size 1 unit shown). Setting the Maximum air flow i) Ensure the power supply is switched off and that a link wire is connected from the supply L to the SL terminal. 100% Unplug all items connected to the ‘Net‘...