Technical Data; Quick Start Set-Up & Programming Tips - Rheem Raypack Temp-Tracker B-40 Installation & Operating Instructions Manual

Modulating temperature controller for raytherm boilers & water heaters h2 514-4001, wh2 2100-4001
Table of Contents

Advertisement

TECHNICAL dATA

(Controller only)
Microprocessor PID control; This is
Controller
Enclosure
Enclosure D, black Noryl plastic
4-3/4" H x 2-7/8" W x 1-7/8" D (120 x
Dimensions
CSA C US, meets ICES & FCC
Approvals
Ambient
Conditions
Power Supply
24 VAC ±10% 50/60 Hz, 75 VA
24VAC 3 VA without alarm; 24 VAC
Demands
Pump/Stage
120 VAC 5 A 1/6 hp, pilot duty
1 Relay
Modulating
0/4-20 mA (1000Ω Maximum)
Analog (mA)
3kHz carrier frequency, 0 to 100%
PWM range, supply 26V (dc)
Modulating
Digital (PWM)
Alarm Relay
NTC thermistor, 10kΩ @ 77 ºF
Sensors
1 outdoor air sensor - P/N 601756
Table V: Technical Data
not a safety (limit) control
74 x 48 mm)
regulations for EMI/RFI
-40 to 140 ºF (-40 to -60ºC),
<90% RH non-condensing
75 VA with alarm
240 VA
through 13kΩ sink,
0.5V (dc) through 1kΩ
24 VAC 3 A 1/6 hp
(25ºC ±0.2ºC)
3 universal water sensors -
P/N 601755
qUICK START SET-UP &
PROGRAMMING TIPS
1. Determine piping arrangement and mode number
as depicted on pages 5 through 7.
2. Install system sensor and air sensor (for Mode 5
only) as positioned in the mode arrangements
located on page 6.
3. Wire the sensors to the Controller as described in
Fig. 22 on page 17.
4. Ensure that entire system is ready to start.
a. Water piping properly filled and purged.
b. Gas pipe properly installed and purged.
c. Electrical connections properly installed in
conduit.
d. Vent properly installed and terminated.
e. Sensor wires properly routed in separate con-
duit.
5. Turn on heater power to allow programming the
Controller.
6. After piping mode has been determined, program
Controller as described on pages 5 to 7.
Remember that the "Item", " " & "▼" buttons (all
three) must be pressed simultaneously for one
second to enter the program mode.
7. Use mode settings as a guide to set up the
Controller. Your settings may differ from the values
given in the manual depending upon the tempera-
ture settings required.
8. After programming Controller, the settings will be
automatically saved after 20 seconds of keypad
inactivity.
9. If the Controller display indicates any error(s), turn
to page 32 to identify and correct the error(s) that
are displayed.
34

Advertisement

Table of Contents
loading

This manual is also suitable for:

Raypack temp-tracker b-41

Table of Contents