1. Filter dryer to be applied
1) The filter dryer (one is shipped with each refrigeration unit) is a standard component.
2) In the case of replacement, use the same filter dryer shown below as the standard
component.
Refrigeration Unit
Model No.
OCU-CR1000VF8A
You must not use a filter dryer for HFC refrigerant under any circumstances as it
Caution
does not meet the pressure requirement.
2. Filter dryer attachment
1) The filter dryer has an expanded tip on both ends.
2) Do not remove the filter dryer cap until immediately before use.
3) Connect the filter dryer to the liquid line between the refrigeration unit outlet and the
evaporator by brazing.
4) During brazing operation, protect the filter dryer from heat by covering it with wet cloths, etc.
5) Install with arrow pointing in direction of flow. Reverse flow may cause internal damage.
Filter dryer
Filter dryer Type
Model No.
D-155T
Cap
278 mm
20
CO-085-S
Connection
Diameter
 15.88 mm