Lighting Application Drawings - AMX Radia RE-DM4 Installation Manual

Radia eclipse 4-channel dimmer module (120 or 240 volts)
Hide thumbs Also See for Radia RE-DM4:

Advertisement

Low-Voltage Connections
The low-voltage area in the AMX Lighting controllers contain connections and DIP
switches for AXLink, dry closures, and RDM module connectors. On the controller
cards, low-voltage power for the board is supplied either by line power, optional
auxiliary power supply (RDA-PSM), or the +12 VDC pin on the AXLink connector.
AXLink address DIP switch
AXlink connector
FIG. 4
Low-voltage connections and DIP switches
WARNING: Disconnect the main power to the AMX Lighting controller at the
breaker box if rewiring the low voltage connections.
Dry Closure Connections
Dry contact closures from other equipment can be connected to the Radia Eclipse
dimmer module to provide direct manual control of lighting loads (FIG. 5).
FAILSAFE
GND
RE-DM4
EMERGENCY
GND
FIG. 5
Dry Closure Connections
FIG. 8 Example A
FIG. 9 Example B
3000 RESEARCH DRIVE, RICHARDSON, TX 75082 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993 • www.amx.com
Module connector/LED (CH6)
Module connector/LED (CH5)
Auxiliary power IN
Dry contact closures
Failsafe switch
Alarm system

Lighting Application Drawings

For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s).
©2007 AMX. All rights reserved. AMX and the AMX logo are registered trademarks of AMX.
AMX reserves the right to alter specifications without notice at any time.
Each dry contact closure has two pins: ground and contact. To activate each dry
closure, connect the ground and contact.
Setting AXLink Address Numbers
Set the AXLink address number (1-255) for the RE-DM4. This number must match
the device number in your Axcess program.
Note: By turning all switches off, all circuits will go to 100 percent so that the installer
can test the high-voltage connections without having connections to a control
system.
Connecting AXLink
Connect the 4-pin captive-wire AXLink from the RE-DM4 to the Central Controller for
AXLink control of the dimming system.
PWR
AXP
RE-DM4
AXM
GND
FIG. 6
Connecting AXlink
RE-DM4 4-pin module connector (male)
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
FIG. 7
RE-DM4 module connector
8/07
PWR
Central
AXP
Controller
AXM
GND
Example A
Single input
120 or 240 VAC 1Ø
Single-phase, four load
Example B
Dual Input
120, 120/240, or 240 VAC 1Ø
Single-phase, four load
93-0706-01
REV: C