Gianni Industries Mortise Series Installation Instruction page 2

Electromagnetic lock

Advertisement

Connecting Diagram
Bond sensor output
N.C. contact output: open status
N.O. contact output: locked status
SPDT relay rated: 0.5A/125VAC
1A/24VDC
Models: 10000R , 10000STR
Power
supply
Control Device
N.C. contact or Access Relay
Dual Voltage Models:
10000,10000R,10000STR
Important Note
Reed
Trouble Shooting
Problem
Door does not lock
Low holding force
Sensor output is not functioning
Copyright © Gianni Industries, Inc. All rights reserved.
P-MU-03M Ver. L Published on: 2012.03.20
(Polarity Free)
Voltage Selection jumpers
Check jumper settings before
connecting the lock to 24 VDC
12VDC
input power. Damage to the lock
may result from incorrect jumper
settings.
24VDC
Make sure the contact area of the
electromagnetic lock and the
armature plate is correct or the
bond sensor output function will
not work.
Make sure the contact surfaces
o f t h e e l e c t r o m a g n e t a n d
armature plate are clean and free
from dust and foreign materials.
Wipe the surface of magnet lock
with anti-rust oil regularly.
Possible Cause
No power
Poor contact between electromagnet and
armature plate
Low voltage or incorrect voltage setting
A secondary diode was installed across
the electromagnetic lock
Misalignment between the armature plate
and electromagnetic lock
Butt Splice(IDC) Connector
Use crimper or pliers and press the header
of connector down to even position
The electromagnetic lock requires a face-to-
face alignment as shown in the Figure.
O t h e r w i s e , t h e h o l d i n g f o r c e w i l l b e
decreased to 25%.
+
Power
Input
-
N.O.
COM.
N.C.
Power
+
+
-
-
UPS
Power
Input
Control
Device
Electromagnetic Locks
Make sure the wires are connected properly
Check that the power supply is connected and works properly
Make sure the lock switch is wired correctly
Make sure the armature plate is not deformed
Make sure the rubber washer was used between the bracket and armature plate
Make sure the contact surfaces of the electromagnet and armature plate are clean
and free from dust and foreign material.
Check the electromagnetic lock is set for the correct voltage.
Check the voltage at the electromagnetic lock input. If low, determine if the
correct wire gauge is being used to prevent excessive voltage drop.
Remove any diode installed across the magnet for "spike"
suppression. (The magnet is fitted with a metal oxide varistor to prevent back EMF)
Make sure the armature plate and electromagnetic lock are aligned correctly
Do not run power wires and signal
wires in the same cable or conduit.
Remove any diode installed
across the magnetic lock for
spike suppression. The magnet
is built-in with a metal oxide
varistor to prevent back EMF.
The electromagnetic locks are
fail safe. Therefore it needs the
p o w e r f r o m U P S t o r e m a i n
locked during the power failure.
Solution
2-2

Advertisement

loading

This manual is also suitable for:

10003m1000010000st