Summary of Contents for Simtronics MultiXplo

  • Page 1 Operating Manual MultiXplo / MultiTox Detectors DM-TX6-X (Catalytic) DM-TT6-K (Catharometer) NOSP15759-Rev 10...
  • Page 2 All rights reserved. No reproduction of all or part of this document, in any form, is permitted without the written consent of Oldham Simtronics S.A.S. All of the information that is provided in this document is accurate to the best of our knowledge.
  • Page 3 SIMTRONICS, even though they may be involved in the sale of OLDHAM SIMTRONICS products. OLDHAM SIMTRONICS shall not be responsible for any direct or indirect damage, or any direct or indirect consequence, resulting from the sale and use of any of its products UNLESS SUCH PRODUCTS HAVE BEEN SELECTED BY OLDHAM SIMTRONICS ACCORDING TO THE APPLICATION.
  • Page 4 (EEE) or a point of exchange for authorized products in the event of the acquisition of a new product of the same type as before. MultiXplo / MultiTox Page 4 / 60 NOSP15759-Rev 10...
  • Page 5: Table Of Contents

    Replacing the cartridge ..................... 47 7.5. Replacing the complete detector ................47 ATEX / IECEx Marking ....................... 49 Accessories and spare parts..................... 50 9.1. Spare parts ........................ 50 9.2. Accessories ........................ 51 MultiXplo / MultiTox Page 5 / 60 NOSP15759-Rev 10...
  • Page 6 9.3. Gas table codes & range table codes ................ 53 Conformity certificate ....................56 MultiXplo / MultiTox Page 6 / 60 NOSP15759-Rev 10...
  • Page 7: Product Description

    These detectors can be configured also using the Hart portable terminal TLH700 (in option). The MultiXplo and MultiTox are also available for use in an addressable network system with distributed intelligence, SYNTEL. For more information, please refer to the Syntel module interface operating manual.
  • Page 8: Dm-Tt6-K

    (DM-TX6-X) and brown for catharometers (DM-TT6-K). The cartridge is located in the lower part of the detector, and it is connected to the detector body by an open ring leaving the label visible. MultiXplo / MultiTox Page 8 / 60 NOSP15759-Rev 10...
  • Page 9 Figure 1 : Layout Drawing (Congestion see Figure 2 MultiXplo / MultiTox Page 9 / 60 NOSP15759-Rev 10...
  • Page 10: Detection Cartridge

    1.5. Detection Cartridge Detection Cartridges are explosion proof designed. They are common to all Oldham Simtronics MultiXplo and MultiTox-K products in order to reduce the number of spare parts. DM-RX6-X and DM-RT6-K: Network versions for Syntel loop, • DM-TX6-X and DM-TT6-K: « Telecapteur » versions, •...
  • Page 11 The HART output is an option. It is available only on the devices equipped with an electronic type C, in HART configuration (H):DGi-**7-****-**H-**-***-*-C-* OLDHAM SIMTRONICS devices under HART protocol enable the use of all the functions available with the TLU600 via the HART terminal.
  • Page 12: Product Code

    4-20 mA protocol (Common fault signal 2 mA) 4 – 20 mA / 0-22 mA configurable & HART protocol 4 – 20 mA / 0-22 mA configurable Wheatstone 4 – 24 mA for compact explosimeter (magnet) MultiXplo / MultiTox Page 12 / 60 NOSP15759-Rev 10...
  • Page 13 Special paint : light grey (10A03 according to « British standards 4800/5252 ») Special paint : red (RAL 3001) Machining of additional cable gland input Paint thickness > 200 µm(ATEX versionIIB) MultiXplo / MultiTox Page 13 / 60 NOSP15759-Rev 10...
  • Page 14 Language Fr / GB French English Portuguese Chinese Hardware version Type 63 Type 65 Type 67 (HART) Type 69 (magnet) Software version Standard MultiXplo / MultiTox Page 14 / 60 NOSP15759-Rev 10...
  • Page 15: Technical Features

    TECHNICAL FEATURES GENERAL Type Gas detector DM-TX6-X MultiXplo (catalytic gas detector) DM-TT6-K MultiTox (catharometer gas detector) DM-RX6 or DM-RT6 Network detector Calibration Factory set, recommended test every 6 months OUTPUT SIGNALS 4-20mA loop signal Type active (source) maximum load impedance 700Ω...
  • Page 16 Material stainless steel 316 L or epoxy coated aluminium Weight 2.3kg (5.1 Lbs) (Aluminium) 4 kg (14.3 Lbs.) (Stainless steel) ATEX/IECEx Please refer to § 8 Dimensions Figure 2: Outline drawing MultiXplo / MultiTox Page 16 / 60 NOSP15759-Rev 10...
  • Page 17: Performances

    Effect of O –enriched or 15 % O 10 % O 15 % O None depleted atmospheres min. min. min. Warm-up or biasing time 90 secs 120 secs  MultiXplo / MultiTox Page 17 / 60 NOSP15759-Rev 10...
  • Page 18 For external probe versions, temperature range is limited to -20 / +60 °C  Under conditions of natural diffusion and available on any of the outputs of the device  (HART, 4-20mA, ...). MultiXplo / MultiTox Page 18 / 60 NOSP15759-Rev 10...
  • Page 19: Installation

    (gas density, ambient temperature…) There are no limit positions of the detector however it is recommended to position the detector vertically (ie with the cartridge pointing downwards). Air velocity limits: 6 m/s. MultiXplo / MultiTox Page 19 / 60 NOSP15759-Rev 10...
  • Page 20: Assembly

    Fit the main housing on the base, placing the excess of cable in the base. Make sure to correctly tighten the 2 fixing screws once the correct position has been obtained. Figure 4 : Housing orientation MultiXplo / MultiTox Page 20 / 60 NOSP15759-Rev 10...
  • Page 21 (M20). On stainless steel version, they are glued with Loctite or equivalent compound. If a plug is moved or removed, it must be glued again with Loctite or an equivalent. MultiXplo / MultiTox Page 21 / 60 NOSP15759-Rev 10...
  • Page 22: Electric Connection

    Never adjust electric connections when detectors are powered. Maintenance must be undertaken by qualified staff. Observe safety site rules. The MultiXplo and MultiTox are sensors with standard current output (4-20mA or 0-22mA). The connection can be on 3 or 4 wires. The 4 wires configuration allows insulation between the signal and power loops.
  • Page 23 The total loop resistance should not exceed 700 Ω with a voltage of 24Vdc. Terminal blocks Point JP11 Description +24VDC power supply +24VDC power supply loop (connected to point 2) 0 V, Connected to point 1 20mA Current loop: entry 20mA Current loop: output MultiXplo / MultiTox Page 23 / 60 NOSP15759-Rev 10...
  • Page 24 The 20mA current loop must be supplied with a PLC. The current return must be connected to the 0V at the level of the L- terminal. To proceed, please connect the 4 (V-) and 6 (L-) terminals at the terminal block level of the devise. MultiXplo / MultiTox Page 24 / 60 NOSP15759-Rev 10...
  • Page 25 In the last case, the relay are opens when the • detector is no longer powered. • on one or more states of the detector (fault, permanent Inhibition, alarms). Relays configured at factory setting : refer to 6.7.5.1 MultiXplo / MultiTox Page 25 / 60 NOSP15759-Rev 10...
  • Page 26 NB : The R1 value is given as an indication. It must comply with the following conditions: • Minimum consumption = 5 Watts • Maximum dissipation = 2.5 Watts MultiXplo / MultiTox Page 26 / 60 NOSP15759-Rev 10...
  • Page 27 • A white wire on the other N (no specific edge) • Figure 5: Connecting drawing of the network versions For more detail, thanks to refer to the operating manual NOSP15251 MultiXplo / MultiTox Page 27 / 60 NOSP15759-Rev 10...
  • Page 28 The hosted sensor NEEDS to get its own power The connecting wires to another detector are limited to a 1 mm² section. Using this board leads to a connection between 0V from power supply and housing ground. MultiXplo / MultiTox Page 28 / 60 NOSP15759-Rev 10...
  • Page 29 1.5mm². The table below shows the maximum cable lengths according to the cable section. Minimum copper conductor section in mm² (AWG) 0,5 (20) 0,9 (18) 1,5 (16) Maximum length 15 m 30 m MultiXplo / MultiTox Page 29 / 60 NOSP15759-Rev 10...
  • Page 30: Detection Cartridge

    O-ring. Then, tighten the locking screw. Switch on the device in order to make the calibration of the new cartridge and the zero adjustment. MultiXplo / MultiTox Page 30 / 60 NOSP15759-Rev 10...
  • Page 31: Commissioning

    Logic Controller. It results in the flashing of the green LED in the communication head. 5.3. Operational tests All MultiXplo / MultiTox detectors are delivered set and tested. Some additional tests are necessary to check the good working of the loop. Please make sure to have all authorizations needed before running the following operations: •...
  • Page 32 MultiXplo / MultiTox Page 32 / 60 NOSP15759-Rev 10...
  • Page 33: Operation

    The permanent inhibition is activated by an order issued by the TLU when an operation is performed at/or around the device, or when the operator wants to inhibit a faulty device. The permanent inhibition must be removed by an operator’s deliberate action using the TLU. MultiXplo / MultiTox Page 33 / 60 NOSP15759-Rev 10...
  • Page 34: Signal Current Loop

    6.5. Wireless communication tool TLU600 All settings and tests of detectors can be done by the wireless communication tool TLU600. This communication tool and its software are compatible with all Oldham Simtronics detectors: MultiFlame, MultiTox and MultiXplo. Communication is made via infrared link (IrDA), similar but more efficient than infrared links for computers.
  • Page 35 Changing displayed value. • Validation and Check-in of the changed value. • The changed value must be confirmed by pressing [VAL] key, otherwise the old value will kept when leaving menu. MultiXplo / MultiTox Page 35 / 60 NOSP15759-Rev 10...
  • Page 36 Maintenance : • The access to the parameters and other maintenance operations is protected by a password. Default password (6 digits which can be changed): 012345. MultiXplo / MultiTox Page 36 / 60 NOSP15759-Rev 10...
  • Page 37: Information Menu [Info]

    Syntel system operating manuals. NETWORK SCREEN: ALIM Information displayed: • Voltage A: ON / OFF • Voltage B: ON / OFF For any further details, please refer to the Syntel system operating manuals MultiXplo / MultiTox Page 37 / 60 NOSP15759-Rev 10...
  • Page 38: Adjustment Menu [Adjt]

    Selecting the inhibition mode will switch the detector in inhibition mode. The message “End of inhibition” is displayed on the TLU. Press on “End of inhibition” to get the detector back to normal operating mode. MultiXplo / MultiTox Page 38 / 60 NOSP15759-Rev 10...
  • Page 39 The detector is in maintenance inhibition mode for 10 minutes after it goes back to main screen. Use the setting menu and validate the INH command for acknowledgement. Press F4 key to stop communication between TLU600 and the detector. MultiXplo / MultiTox Page 39 / 60 NOSP15759-Rev 10...
  • Page 40 Use the setting menu and validate the INH command for acknowledgement. To end of communication between the TLU600 and the detector is done by pressing F4 key on main menu. MultiXplo / MultiTox Page 40 / 60 NOSP15759-Rev 10...
  • Page 41 Press [>>] to go to the next figure in the field. • Press [PAGE] to go next page. • The label or zone modification must be confirmed by pressing the key VALID, otherwise the modification is not taken into account MultiXplo / MultiTox Page 41 / 60 NOSP15759-Rev 10...
  • Page 42 Power loss C1-T1 open Output current configuration This menu allows you to switch the format of the output current between 4-20 mA and 0-22 Factory setting: the output current is 4-20 mA MultiXplo / MultiTox Page 42 / 60 NOSP15759-Rev 10...
  • Page 43: The Maintenance Menu [Main]

    SPIN sends the detectors network identification. • LIEN switches from normal mode to logic link mode. • SWITCH enables the switches to go on mode open/closed/open secured. • MultiXplo / MultiTox Page 43 / 60 NOSP15759-Rev 10...
  • Page 44: Ambiguity Function In Combustible Gas Detector Smart Sensors

    The device then goes in warm-up mode (refer to §6.3) for 90s. The detector is in inhibition mode. The current output and the default relay (if factory configuration) are consequently activated. A warming-up timer starts to countdown from 90 sec. Then, the inhibition is released. MultiXplo / MultiTox Page 44 / 60 NOSP15759-Rev 10...
  • Page 45: Maintenance

    If the detection unit or the PLC signals a detector’s fault, the detector must be tested directly with the wireless communication tool to determine the type of fault. If the detector is configured in 0-22 mA output, it is possible to have a pre-diagnostic of the fault. MultiXplo / MultiTox Page 45 / 60 NOSP15759-Rev 10...
  • Page 46: List Of Main Faults

    Check that the green LED flashes. wireless communication tool Check the wireless communication tool by using Dialogue problem connection it on another detector. Detector fault Electronic fault Replace the detector (Material fault) MultiXplo / MultiTox Page 46 / 60 NOSP15759-Rev 10...
  • Page 47: Replacing The Cartridge

    As the base of the detector remains in place, cable glands do not need to be dismantled. If the detector is not replaced immediately, the “open” base must be protected against humidity, dust and shocks No intervention should be carried out when the detector is powered. MultiXplo / MultiTox Page 47 / 60 NOSP15759-Rev 10...
  • Page 48 MultiXplo / MultiTox Page 48 / 60 NOSP15759-Rev 10...
  • Page 49: Atex / Iecex Marking

    * IP rating does not mean that the equipment will detect the gas during or after exposure to the defined conditions. It is also recommended to use the device with the following accessories: AS056-250, AS019, AS015. MultiXplo / MultiTox Page 49 / 60 NOSP15759-Rev 10...
  • Page 50: Accessories And Spare Parts

    Cartouches Catha Same as detector * Products called « mechanical » in the previous table are : AS045, AS005, AS215, AS015, AS016, AS011-2X, AS02x, AS019, AS052, AS053, AS047, AS048, AS056-250, AS205, AS055. MultiXplo / MultiTox Page 50 / 60 NOSP15759-Rev 10...
  • Page 51: Accessories

    Water, sand and dust Adaptation to all cartridges, the assembly AS019  protection is directly in front of cartridge thanks to the nut of maintain (black on version -A). MultiXplo / MultiTox Page 51 / 60 NOSP15759-Rev 10...
  • Page 52  Detector sensitivity and response time are not modified.  This accessory is included into the EN60079-29-1 Performance Certificate. Wipe non-conductive parts (plastic) that can use in ATEX area with a damp cloth (risk of electrostatic charges) MultiXplo / MultiTox Page 52 / 60 NOSP15759-Rev 10...
  • Page 53 2 ppm*m Ozone 5 ppm*m PFBA PFBA 10 ppm*m Chlorodifluoromethane 20 ppm*m Trifluoromethane 50 ppm*m Sulphur dioxide 100 ppm*m Cyclopentane 200 ppm*m 500 ppm*m White Spirit 1000 ppm*m Gasoil 2000 ppm*m MultiXplo / MultiTox Page 53 / 60 NOSP15759-Rev 10...
  • Page 54 Special customer (EG) HC lourd F1850 Special customer COCH MTBE H2S + CH4 Hydrogen sulfide Methane Special combustible gas App SA Hydrogen in Argon Complement Argon Hydrogen in Azote Complement Azote MultiXplo / MultiTox Page 54 / 60 NOSP15759-Rev 10...
  • Page 55 Regarding reference F2 = DG (100% LEL), the following table defines what OLDHAM SIMTRONICS uses of correspondence between %vol and 100% LEL. Nom produit Name of compound Formule % vol équivalent à 100 Formula % LIE / LEL 63DG 1,3-butadiène...
  • Page 56 CONFORMITY CERTIFICATE MultiXplo / MultiTox Page 56 / 60 NOSP15759-Rev 10...
  • Page 57 MultiXplo / MultiTox Page 57 / 60 NOSP15759-Rev 10...
  • Page 58 MultiXplo / MultiTox Page 58 / 60 NOSP15759-Rev 10...
  • Page 59 MultiXplo / MultiTox Page 59 / 60 NOSP15759-Rev 10...
  • Page 60 EUROPEAN PLANT AND OFFICES Z.I. Est – rue Orfila CS 20417 – 62027 ARRAS Cedex FRANCE Tél.: +33 (0)3 21 60 80 80 – Fax: +33 (0)3 21 60 80 00 Web site: https://teledynegasandflamedetection.com/ AMERICAS ASIA PACIFIC EUROPE Tel : +1-713-559-9280 Tel : +86-21-3127-6373 Tel : +33-321-608-080 Fax : +1-281-292-2860...